Air handling unit controller · BACnet points list

WOLF WRS-K air handling unit controller - BACnet-Pro interface BACnet points list

Updated 12 November 2026

Short answer

The BACnet-Pro interface is WOLF's newer BACnet connection for the WRS-K air-handling controller. Unlike the older BACnet interface it publishes measurements as Analog Inputs, BMS setpoints and offsets as commandable Analog Outputs, states and alarms as Binary Inputs, stages as Multistate Inputs, the operating mode as a Multistate Value, plus trend logs, schedules for the BMS setpoints and notification classes.

This page lists 264 BACnet objects for the WOLF WRS-K air handling unit controller - BACnet-Pro interface — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WOLF’s own free documentation, linked below.

Manufacturer
WOLF
Model
WRS-K air handling unit controller - BACnet-Pro interface
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
264 (27 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
2000
Also known as
WOLF BACnet-Pro, BACnet-Pro-Schnittstelle WRS-K, WRS-K BACnet-Pro
Source document
EDE-File BACnet-Pro-Schnittstelle fuer WRS-K, Index05 (BACnet-Pro_Index05_EDE_komplett.csv) · Index05 · rev. 08.07.2025
Download CSV 264 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against WOLF’s current documentation and the live device before use. Not official WOLF information. Terms of use.

BMS integration notes: WOLF WRS-K air handling unit controller - BACnet-Pro interface

Integration in brief

Set MV 1006 Operation_Mode and write the BMS setpoints (AO 15 temperature, AO 16 / 17 fan speeds, MO 222 fan step). Read BI 5 Status_AHU, the supply and room temperatures and BI 1 Alarm_General plus the individual alarm BIs; reset alarms with BV 1.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 1006Operation_ModeOperating mode: 1 manual, 2 7-day program, 3 BMSWrite
MO 222Setpoint_Fan_Step_BMSFan stage from BMS: 1 off, 2 on, 3-4 stagesCommand
AO 15Setpoint_Temperature_BMSTemperature setpoint from the BMS, °CCommand
AO 16Setpoint_Speed_SUP_BMSSupply fan speed setpoint, %Command
AO 17Setpoint_Speed_ETA_BMSExtract fan speed setpoint, %Command
BV 1Alarm_Reset_BMSRemote alarm resetWrite
BI 5Status_AHUUnit statusRead
AI 1Temperature_SUPSupply air temperature, °CRead
AI 3Temperature_RoomRoom temperature, °CRead
BI 1Alarm_GeneralGeneral alarmRead

Enable & remote start

MV 1006 Operation_Mode selects manual mode, the 7-day program or BMS mode. The EDE does not say which BMS setpoints take effect in which mode; check on site.

Sensors & values from the BMS

Outdoor and room temperature can be written from the BMS (AO 37 Temperature_Outdoor_BMS, AO 71 Temperature_Room_BMS, -50 to 60 °C); BI 128 / BI 134 flag problems with them.

Network setup

Watch out for

WOLF WRS-K air handling unit controller - BACnet-Pro interface BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

264 of 264 shown
Type
Access
Show
WOLF WRS-K air handling unit controller - BACnet-Pro interface BACnet Points List
DescriptionStates
AImin1Temperature_SUPTemperature supply°CRead
AI2Temperature_OutdoorTemperature Outdoor°CRead
AImin3Temperature_RoomTemperature Room°CRead
AI4Temperature_ETATemperature extract°CRead
AI5Air_Quality_VOCAir Quality VOCVRead
AI6Setpoint_DeviceSetpoint Device°CRead
AI7Humidity_RoomHumidity Room%RHRead
AI8Humidity_ETAHumidity extract%RHRead
AI9Humidity_SUPHumidity supply%RHRead
AI10Setpoint_Temperature_SUPSetpoint Temperature supply°CRead
AI11Setpoint_TemperatureSetpoint Temperature°CRead
AI12Setpoint_Fresh_AirSetpoint Fresh Air%Read
AI13Setpoint_Speed_SUP_FanSetpoint Speed supply Fan%Read
AI14Setpoint_Speed_ETA_FanSetpoint Speed extract Fan%Read
AI23Setpoint_HumiditySetpoint Humidity%RHRead
AI24Setpoint_Humidity_AbsSetpoint Humidity Abs%RHRead
AI27Temperature_EHATemperature exhaust°CRead
AI28Signal_Valve_HeatingSignal Valve Heating%Read
AI29Signal_Valve_CoolingSignal Valve Cooling%Read
AI30Signal_Heat_RecoverySignal Heat Recovery%Read
AI31Signal_HumidifierSignal Humidifier%Read
AI32Temperature_Adiabatic_CoolingTemperature Adiabatic Cooling°CRead
AI33Signal_Valve_ReheatingSignal Valve Reheating%Read
AI42Humidity_OutdoorHumidity Outdoor%RHRead
AI45Temperature_Outdoor_HRTemperature Outdoor heat recovery°CRead
AI46Temperature_SUP_HRTemperature supply heat recovery°CRead
AI47Signal_Valve_PreHeatingSignal Valve Pre Heating%Read
AI48Temperature_DewpointTemperature Dewpoint°CRead
AI59Temperature_Inlet_HeaterTemperature Inlet Heater°CRead
AI60Temperature_Return_HeaterTemperature Return Heater°CRead
AI61Temperature_Inlet_CoolerTemperature Inlet Cooler°CRead
AI62Temperature_Return_CoolerTemperature Return Cooler°CRead
AI1001Air_Quality_CO2Air Quality CO2ppmRead
AI1002Pressure_SUPPressure supplyPaRead
AI1003Pressure_ETAPressure extractPaRead
AI1004Volume_SUPVolume supplym³/hRead
AI1005Volume_ETAVolume extractm³/hRead
AI1008Setpoint_Pressure_SUPSetpoint Pressure supplyPaRead
AI1009Setpoint_Pressure_ETASetpoint Pressure extractPaRead
AI1010Setpoint_Volume_SUPSetpoint Volume supplym³/hRead
AI1011Setpoint_Volume_ETASetpoint Volume extractm³/hRead
AI1091Pressure_Filter_SUP1Pressure Filter SUP1PaRead
AI1092Pressure_Filter_SUP2Pressure Filter SUP2PaRead
AI1093Pressure_Filter_SUP3Pressure Filter SUP3PaRead
AI1094Pressure_Filter_ETA1Pressure Filter ETA1PaRead
AI1095Pressure_Filter_ETA2Pressure Filter ETA2PaRead
AI1175Pressure_Static_SUPPressure Static supplyPaRead
AI1185Pressure_Static_ETAPressure Static extractPaRead
AOmin15Setpoint_Temperature_BMSSetpoint Temperature from BMS°CCommand
AOmin16Setpoint_Speed_SUP_BMSSetpoint Speed supply from BMS%Command
AOmin17Setpoint_Speed_ETA_BMSSetpoint Speed extract from BMS%Command
AO18Offset_Temperature_BMSOffset Temperature from BMS°CCommand
AO19Offset_Speed_SUP_Fan_BMSOffset Speed supply Fan from BMS%Command
AO20Offset_Speed_ETA_Fan_BMSOffset Speed extract Fan from BMS%Command
AO21Offset_Humidity_BMSOffset Humidity from BMS, range -30.0 to 30.0%RHCommand
AO22Offset_Humidity_Abs_BMSOffset Humidity Abs from BMS, range -10.0 to 10.0g/kgCommand
AO25Setpoint_Humidity_BMSSetpoint Humidity from BMS, range 0.0 to 95.0%RHCommand
AO26Setpoint_Humidity_Abs_BMSSetpoint Humidity Abs from BMS, range 0.0 to 25.0g/kgCommand
AO37Temperature_Outdoor_BMSTemperature Outdoor from BMS, range -50.0 to 60.0°CCommand
AO71Temperature_Room_BMSTemperature Room from BMS, range -50.0 to 60.0°CCommand
AO1013Setpoint_Fresh_Air_BMSSetpoint Fresh Air from BMS%Command
AO1015Setpoint_Pressure_SUP_BMSSetpoint Pressure supply from BMSPaCommand
AO1016Setpoint_Pressure_ETA_BMSSetpoint Pressure extract from BMSPaCommand
AO1017Setpoint_Volume_SUP_BMSSetpoint Volume supply from BMSm³/hCommand
AO1018Setpoint_Volume_ETA_BMSSetpoint Volume extract from BMSm³/hCommand
AO1019Offset_Fresh_Air_BMSOffset Fresh Air from BMS%Command
AO1020Offset_Pressure_SUP_BMSOffset Pressure supply from BMSPaCommand
AO1021Offset_Pressure_ETA_BMSOffset Pressure extract from BMSPaCommand
AO1022Offset_Volume_SUP_BMSOffset Volume supply from BMSm³/hCommand
AO1023Offset_Volume_ETA_BMSOffset Volume extract from BMSm³/hCommand
AV1055Max_Power_EheaterMax Power electric heater, range 0.0 to 100.0%Write
BImin1Alarm_GeneralAlarm GeneralReadInactive=inactive, Active=active
BI2Ext_Request_EnableExt Request EnableReadInactive=inactive, Active=active
BI3HygrostatHygrostatReadInactive=inactive, Active=active
BI4Humidifier_EnableHumidifier EnableReadInactive=inactive, Active=active
BImin5Status_AHUStatus unitReadInactive=inactive, Active=active
BI6Special_HolidaySpecial HolidayReadInactive=inactive, Active=active
BI7Special_FilterSpecial FilterReadInactive=inactive, Active=active
BI8Special_PreheatSpecial PreheatReadInactive=inactive, Active=active
BI9Special_NightVentilationSpecial Night VentilationReadInactive=inactive, Active=active
BI10Special_BackupModeSpecial Backup ModeReadInactive=inactive, Active=active
BI11Special_UtilisationSpecial UtilisationReadInactive=inactive, Active=active
BI12Special_PeakVentilationSpecial Peak VentilationReadInactive=inactive, Active=active
BI13Special_NaturalCoolingSpecial Natural CoolingReadInactive=inactive, Active=active
BI14Special_HygrostatSpecial HygrostatReadInactive=inactive, Active=active
BI15Special_AirQualitySpecial Air QualityReadInactive=inactive, Active=active
BI16Special_ExternalDemandSpecial External DemandReadInactive=inactive, Active=active
BI17Special_RunOnSpecial Run OnReadInactive=inactive, Active=active
BI18Pump_CoolingPump CoolingReadInactive=inactive, Active=active
BI19Alarm_Inverter_SUPAlarm Inverter supplyReadInactive=inactive, Active=active
BI21Alarm_RepairSwitch_SUPAlarm Repair Switch supplyReadInactive=inactive, Active=active
BI22Alarm_AirFlow_SUPAlarm Air Flow supplyReadInactive=inactive, Active=active
BI23Alarm_Inverter_ETAAlarm Inverter extractReadInactive=inactive, Active=active
BI25Alarm_RepairSwitch_ETAAlarm Repair Switch extractReadInactive=inactive, Active=active
BI26Alarm_AirFlow_ETAAlarm Air Flow extractReadInactive=inactive, Active=active
BI30Alarm_Pump_HotWaterAlarm Pump Hot WaterReadInactive=inactive, Active=active
BI31Alarm_FrostAlarm FrostReadInactive=inactive, Active=active
BI32Alarm_Frost_SUPAlarm Frost supplyReadInactive=inactive, Active=active
BI33Alarm_TempLimiter_EheaterAlarm Temp Limiter electric heaterReadInactive=inactive, Active=active
BI34Alarm_SafetyTempLimiter_EheaterAlarm Safety Temp Limiter electric heaterReadInactive=inactive, Active=active
BI35Alarm_Pump_ColdWaterAlarm Pump Cold WaterReadInactive=inactive, Active=active
BI36Alarm_ChillerAlarm ChillerReadInactive=inactive, Active=active
BI37Alarm_FireAlarm FireReadInactive=inactive, Active=active
BI48Alarm_Fan_SUPAlarm Fan supplyReadInactive=inactive, Active=active
BI49Alarm_Fan_ETAAlarm Fan extractReadInactive=inactive, Active=active
BI50Alarm_KLM_EAlarm KLM EReadInactive=inactive, Active=active
BI51Alarm_BMK_FAlarm BMK FReadInactive=inactive, Active=active
BI52Alarm_ServiceAlarm ServiceReadInactive=inactive, Active=active
BI54Alarm_HRAlarm heat recoveryReadInactive=inactive, Active=active
BI55Alarm_Service_HumiAlarm Service humidifierReadInactive=inactive, Active=active
BI56Alarm_HumiAlarm humidifierReadInactive=inactive, Active=active
BI57Alarm_ExternAlarm ExternReadInactive=inactive, Active=active
BI58Alarm_SmokeAlarmAlarm Smoke AlarmReadInactive=inactive, Active=active
BI59Alarm_Setpoint_DeviceAlarm Setpoint DeviceReadInactive=inactive, Active=active
BI60Pump_HeatingPump HeatingReadInactive=inactive, Active=active
BI61Request_HeatingRequest HeatingReadInactive=inactive, Active=active
BI62Request_Heat_RecoveryRequest Heat RecoveryReadInactive=inactive, Active=active
BI63Request_Damper_SUPRequest Damper supplyReadInactive=closed, Active=open
BI64Request_Damper_ETARequest Damper extractReadInactive=closed, Active=open
BI66Alarm_Fire_Damper_1Alarm Fire Damper 1ReadInactive=inactive, Active=active
BI67Alarm_Fire_Damper_2Alarm Fire Damper 2ReadInactive=inactive, Active=active
BI68Alarm_Fire_Damper_3Alarm Fire Damper 3ReadInactive=inactive, Active=active
BI69Alarm_Fire_Damper_4Alarm Fire Damper 4ReadInactive=inactive, Active=active
BI70Alarm_Fire_Damper_5Alarm Fire Damper 5ReadInactive=inactive, Active=active
BI71Alarm_Fire_Damper_6Alarm Fire Damper 6ReadInactive=inactive, Active=active
BI72Alarm_Fire_Damper_7Alarm Fire Damper 7ReadInactive=inactive, Active=active
BI73Alarm_Fire_Damper_8Alarm Fire Damper 8ReadInactive=inactive, Active=active
BI74Alarm_Fire_Damper_9Alarm Fire Damper 9ReadInactive=inactive, Active=active
BI75Alarm_Fire_Damper_10Alarm Fire Damper 10ReadInactive=inactive, Active=active
BI76Alarm_Fire_Damper_11Alarm Fire Damper 11ReadInactive=inactive, Active=active
BI77Alarm_Fire_Damper_12Alarm Fire Damper 12ReadInactive=inactive, Active=active
BI78Alarm_Fire_Damper_13Alarm Fire Damper 13ReadInactive=inactive, Active=active
BI79Alarm_Fire_Damper_14Alarm Fire Damper 14ReadInactive=inactive, Active=active
BI80Alarm_Fire_Damper_15Alarm Fire Damper 15ReadInactive=inactive, Active=active
BI81Alarm_Fire_Damper_16Alarm Fire Damper 16ReadInactive=inactive, Active=active
BI82Alarm_Fire_Damper_17Alarm Fire Damper 17ReadInactive=inactive, Active=active
BI83Alarm_Fire_Damper_18Alarm Fire Damper 18ReadInactive=inactive, Active=active
BI84Alarm_Fire_Damper_19Alarm Fire Damper 19ReadInactive=inactive, Active=active
BI85Alarm_Fire_Damper_20Alarm Fire Damper 20ReadInactive=inactive, Active=active
BI86Alarm_Fire_Damper_21Alarm Fire Damper 21ReadInactive=inactive, Active=active
BI87Adiabatic_Cooling_EnableAdiabatic Cooling EnableReadInactive=inactive, Active=active
BI88Alarm_AC_CalcificationAlarm adiabatic cooling CalcificationReadInactive=inactive, Active=active
BI91Drain_Valve_Supply_WaterDrain Valve Supply WaterReadInactive=closed, Active=open
BI92Drain_Valve_TankDrain Valve TankReadInactive=closed, Active=open
BI94Feed_Valve_Adiabatic_CoolingFeed Valve Adiabatic CoolingReadInactive=closed, Active=open
BI96Alarm_AC_HumiAlarm adiabatic cooling humidifierReadInactive=inactive, Active=active
BI97Alarm_AC_Cooling_PowerAlarm adiabatic cooling Cooling PowerReadInactive=inactive, Active=active
BI100Alarm_Service_AC_HumiAlarm Service adiabatic cooling humidifierReadInactive=inactive, Active=active
BI101Special_HR_IcingSpecial heat recovery IcingReadInactive=inactive, Active=active
BI102Special_Speed ReductionSpecial Speed ReductionReadInactive=inactive, Active=active
BI105FilterPreDreyerFilter Pre DreyerReadInactive=inactive, Active=active
BI112Special_Setback ModeSpecial Setback ModeReadInactive=inactive, Active=active
BI113Special_WinterstartSpecial WinterstartReadInactive=inactive, Active=active
BI114Alarm_HPAlarm HPReadInactive=inactive, Active=active
BI115Alarm_Pump_ReheatingAlarm Pump ReheatingReadInactive=inactive, Active=active
BI116Alarm_Frost_ReheatingAlarm Frost ReheatingReadInactive=inactive, Active=active
BI117Status_OperationStatus OperationReadInactive=inactive, Active=active
BI120Alarm_pLAN_ChillerAlarm p LAN ChillerReadInactive=inactive, Active=active
BI122Alarm_kvsAlarm kvsReadInactive=inactive, Active=active
BI125Special_Min_Temp_SUPSpecial Min Temp supplyReadInactive=inactive, Active=active
BI128Alarm_Temp_Out_BMSAlarm Temp Out from BMSReadInactive=inactive, Active=active
BI129Special_QuickheatSpecial QuickheatReadInactive=inactive, Active=active
BI134Alarm_Temp_Room_BMSAlarm Temp Room from BMSReadInactive=inactive, Active=active
BI139SafetyTempLim_PreheaterSafety Temp Lim PreheaterReadInactive=inactive, Active=active
BI143Request_Bypass_Coil1Request Bypass Coil1ReadInactive=open, Active=closed
BI146Alarm_DehumificationAlarm DehumificationReadInactive=inactive, Active=active
BI148Dehumidification_EnableDehumidification EnableReadInactive=inactive, Active=active
BI149Special_Defrost_HPSpecial Defrost HPReadInactive=inactive, Active=active
BI154Request_Bypass_Coil2Request Bypass Coil2ReadInactive=open, Active=closed
BI164Alarm_ETA_Filter_1Alarm extract Filter 1ReadInactive=inactive, Active=active
BI165Alarm_ETA_Filter_2Alarm extract Filter 2ReadInactive=inactive, Active=active
BI166Alarm_SUP_Filter_1Alarm supply Filter 1ReadInactive=inactive, Active=active
BI167Alarm_SUP_Filter_2Alarm supply Filter 2ReadInactive=inactive, Active=active
BI168Alarm_SUP_Filter_3Alarm supply Filter 3ReadInactive=inactive, Active=active
BI169Alarm_Inverter_1Alarm Inverter 1ReadInactive=inactive, Active=active
BI170Alarm_Inverter_2Alarm Inverter 2ReadInactive=inactive, Active=active
BI171Alarm_Inverter_3Alarm Inverter 3ReadInactive=inactive, Active=active
BI173Alarm_Pump_ChOverAlarm Pump Ch OverReadInactive=inactive, Active=active
BI174Alarm_SafetyTempLim_PredryerAlarm Safety Temp Lim PredryerReadInactive=inactive, Active=active
BI175Alarm_Ventilator2_SUPAlarm Ventilator2 supplyReadInactive=inactive, Active=active
BI176Alarm_Ventilator2_ETAAlarm Ventilator2 extractReadInactive=inactive, Active=active
BI177Request_PreheaterRequest PreheaterReadInactive=inactive, Active=active
BI178Special_FrostSpecial FrostReadInactive=inactive, Active=active
BI189Alarm_Frost_Return_HeaterAlarm Frost Return HeaterReadInactive=inactive, Active=active
BI193Alarm_Condensatepump_HRAlarm Condensatepump heat recoveryReadInactive=inactive, Active=active
BI300Alarm_Watchdog_KLMAlarm Watchdog KLMReadInactive=Normal, Active=Alarm
BVmin1Alarm_Reset_BMSAlarm Reset from BMSWriteInactive=inactive, Active=active
BV179Mode_cool_extMode cool extWriteInactive=Heating, Active=Cooling
MI7Setpoint_Fan_StageSetpoint Fan StageRead1=OFF, 2=ON, 3=Stage 2, 4=Stage 3
MI12Request_CoolingRequest CoolingRead1=OFF, 2=Stage 1, 3=Stage 2
MI24EHeating_StageEHeating StageRead1=OFF, 2=Stage 1, 3=Stage 2, 4=Stage 3, 5=Stage 4, 6=Stage 5
MI25Chiller_StageChiller StageRead1=OFF, 2=Stage 1, 3=Stage 2
MI47Heatpump-ModeHeatpump-ModeRead1=OFF, 2=Heating, 3=Cooling
MOmin222Setpoint_Fan_Step_BMSSetpoint Fan Step from BMSCommand1=OFF, 2=ON, 3=Stage 2, 4=Stage 3
NC1NC1Notification class: Fire alarmRead
NC2NC2Notification class: System failureRead
NC3NC3Notification class: Fault messageRead
NC4NC4Notification class: Warning messageRead
MVmin1006Operation_ModeOperation ModeWrite1=Manual mode, 2=7-day programm, 3=BMS mode
TL1TL_Temperature_SUPTrend log of Temperature_SUPRead
TL2TL_Temperature_OutdoorTrend log of Temperature_OutdoorRead
TL3TL_Temperature_RoomTrend log of Temperature_RoomRead
TL4TL_Temperature_ETATrend log of Temperature_ETARead
TL5TL_Air_Quality_VOCTrend log of Air_Quality_VOCRead
TL6TL_Setpoint_DeviceTrend log of Setpoint_DeviceRead
TL7TL_Humidity_RoomTrend log of Humidity_RoomRead
TL8TL_Humidity_ETATrend log of Humidity_ETARead
TL9TL_Humidity_SUPTrend log of Humidity_SUPRead
TL10TL_Setpoint_Temperature_SUPTrend log of Setpoint_Temperature_SUPRead
TL11TL_Setpoint_TemperatureTrend log of Setpoint_TemperatureRead
TL12TL_Setpoint_Fresh_AirTrend log of Setpoint_Fresh_AirRead
TL13TL_Setpoint_Speed_SUP_FanTrend log of Setpoint_Speed_SUP_FanRead
TL14TL_Setpoint_Speed_ETA_FanTrend log of Setpoint_Speed_ETA_FanRead
TL23TL_Setpoint_HumidityTrend log of Setpoint_HumidityRead
TL24TL_Setpoint_Humidity_AbsTrend log of Setpoint_Humidity_AbsRead
TL27TL_Temperature_EHATrend log of Temperature_EHARead
TL28TL_Signal_Valve_HeatingTrend log of Signal_Valve_HeatingRead
TL29TL_Signal_Valve_CoolingTrend log of Signal_Valve_CoolingRead
TL30TL_Signal_Heat_RecoveryTrend log of Signal_Heat_RecoveryRead
TL31TL_Signal_HumidifierTrend log of Signal_HumidifierRead
TL32TL_Temperature_Adiabatic_CoolingTrend log of Temperature_Adiabatic_CoolingRead
TL33TL_Signal_Valve_ReheatingTrend log of Signal_Valve_ReheatingRead
TL42TL_Humidity_OutdoorTrend log of Humidity_OutdoorRead
TL45TL_Temperature_Outdoor_HRTrend log of Temperature_Outdoor_HRRead
TL46TL_Temperature_SUP_HRTrend log of Temperature_SUP_HRRead
TL47TL_Signal_Valve_PreHeatingTrend log of Signal_Valve_PreHeatingRead
TL48TL_Temperature_DewpointTrend log of Temperature_DewpointRead
TL59TL_Temperature_Inlet_HeaterTrend log of Temperature_Inlet_HeaterRead
TL60TL_Temperature_Return_HeaterTrend log of Temperature_Return_HeaterRead
TL61TL_Temperature_Inlet_CoolerTrend log of Temperature_Inlet_CoolerRead
TL62TL_Temperature_Return_CoolerTrend log of Temperature_Return_CoolerRead
TL1001TL_Air_Quality_CO2Trend log of Air_Quality_CO2Read
TL1002TL_Pressure_SUPTrend log of Pressure_SUPRead
TL1003TL_Pressure_ETATrend log of Pressure_ETARead
TL1004TL_Volume_SUPTrend log of Volume_SUPRead
TL1005TL_Volume_ETATrend log of Volume_ETARead
TL1008TL_Setpoint_Pressure_SUPTrend log of Setpoint_Pressure_SUPRead
TL1009TL_Setpoint_Pressure_ETATrend log of Setpoint_Pressure_ETARead
TL1010TL_Setpoint_Volume_SUPTrend log of Setpoint_Volume_SUPRead
TL1011TL_Setpoint_Volume_ETATrend log of Setpoint_Volume_ETARead
TL1091TL_Pressure_Filter_SUP1Trend log of Pressure_Filter_SUP1Read
TL1092TL_Pressure_Filter_SUP2Trend log of Pressure_Filter_SUP2Read
TL1093TL_Pressure_Filter_SUP3Trend log of Pressure_Filter_SUP3Read
TL1094TL_Pressure_Filter_ETA1Trend log of Pressure_Filter_ETA1Read
TL1095TL_Pressure_Filter_ETA2Trend log of Pressure_Filter_ETA2Read
TL1175TL_Pressure_Static_SUPTrend log of Pressure_Static_SUPRead
TL1185TL_Pressure_Static_ETATrend log of Pressure_Static_ETARead
TL30105TL_FilterPreDreyerTrend log of FilterPreDreyerRead
TL130007TL_Setpoint_Fan_StageTrend log of Setpoint_Fan_StageRead
TL130012TL_Request_CoolingTrend log of Request_CoolingRead
TL130024TL_EHeating_StageTrend log of EHeating_StageRead
TL130025TL_Chiller_StageTrend log of Chiller_StageRead
TL130047TL_Heatpump-ModeTrend log of Heatpump-ModeRead
SCH10015SC_Setpoint_Temperature_BMSSchedule for Setpoint_Temperature_BMSRead
SCH10016SC_Setpoint_Speed_SUP_BMSSchedule for Setpoint_Speed_SUP_BMSRead
SCH10017SC_Setpoint_Speed_ETA_BMSSchedule for Setpoint_Speed_ETA_BMSRead
SCH10025SC_Setpoint_Humidity_BMSSchedule for Setpoint_Humidity_BMSRead
SCH10026SC_Setpoint_Humidity_Abs_BMSSchedule for Setpoint_Humidity_Abs_BMSRead
SCH11013SC_Setpoint_Fresh_Air_BMSSchedule for Setpoint_Fresh_Air_BMSRead
SCH11015SC_Setpoint_Pressure_SUP_BMSSchedule for Setpoint_Pressure_SUP_BMSRead
SCH11016SC_Setpoint_Pressure_ETA_BMSSchedule for Setpoint_Pressure_ETA_BMSRead
SCH11017SC_Setpoint_Volume_SUP_BMSSchedule for Setpoint_Volume_SUP_BMSRead
SCH11018SC_Setpoint_Volume_ETA_BMSSchedule for Setpoint_Volume_ETA_BMSRead
SCH140222SC_Setpoint_Fan_Step_BMSSchedule for Setpoint_Fan_Step_BMSRead
Object ID lookup: WOLF WRS-K air handling unit controller - BACnet-Pro interface point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WRS-K air handling unit controller - BACnet-Pro interface and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WOLF WRS-K air handling unit controller - BACnet-Pro interface

How many BACnet points does the WOLF WRS-K air handling unit controller - BACnet-Pro interface have?

This list has 264 BACnet objects: 48 analog inputs, 22 analog outputs, 1 analog value, 115 binary inputs, 2 binary values, 5 multi-state inputs, 1 multi-state output, 4 notification classs, 11 schedules, 1 multi-state value, 54 trend logs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WOLF WRS-K air handling unit controller - BACnet-Pro interface BACnet points are writable?

27 of the 264 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WOLF WRS-K air handling unit controller - BACnet-Pro interface BACnet documentation?

The source is EDE-File BACnet-Pro-Schnittstelle fuer WRS-K, Index05 (BACnet-Pro_Index05_EDE_komplett.csv) (Index05), revision 08.07.2025, published free by WOLF at https://www.wolf.eu/download-asset/RmlkbTRXT2hDOHpMWEN6ZVZOOUVPQT09.

What are the minimum BACnet points to integrate the WOLF WRS-K air handling unit controller - BACnet-Pro interface?

Start with MV 1006 Operation_Mode (Operating mode: 1 manual, 2 7-day program, 3 BMS); MO 222 Setpoint_Fan_Step_BMS (Fan stage from BMS: 1 off, 2 on, 3-4 stages); AO 15 Setpoint_Temperature_BMS (Temperature setpoint from the BMS, °C); AO 16 Setpoint_Speed_SUP_BMS (Supply fan speed setpoint, %); AO 17 Setpoint_Speed_ETA_BMS (Extract fan speed setpoint, %); BV 1 Alarm_Reset_BMS (Remote alarm reset); BI 5 Status_AHU (Unit status); AI 1 Temperature_SUP (Supply air temperature, °C); AI 3 Temperature_Room (Room temperature, °C); BI 1 Alarm_General (General alarm).

How do I enable BMS control of the WOLF WRS-K air handling unit controller - BACnet-Pro interface?

MV 1006 Operation_Mode selects manual mode, the 7-day program or BMS mode. The EDE does not say which BMS setpoints take effect in which mode; check on site.

Can the BMS supply sensor values to the WOLF WRS-K air handling unit controller - BACnet-Pro interface?

Outdoor and room temperature can be written from the BMS (AO 37 Temperature_Outdoor_BMS, AO 71 Temperature_Room_BMS, -50 to 60 °C); BI 128 / BI 134 flag problems with them.

How do I check these points on the real WRS-K air handling unit controller - BACnet-Pro interface?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More WOLF BACnet points lists

Source: EDE-File BACnet-Pro-Schnittstelle fuer WRS-K, Index05 (BACnet-Pro_Index05_EDE_komplett.csv) · Index05 · rev. 08.07.2025. Object names, instances and units are reproduced as published; descriptions are our own.