Air handling unit controller · BACnet points list

WOLF WRS-K air handling unit controller - BACnet interface BACnet points list

Updated 7 November 2026

Short answer

The BACnet interface card for WOLF's WRS-K air-handling controller gives BACnet IP (or BACnet Ethernet) access to the unit. It publishes fixed binary and analog values: operating states and outputs, temperatures, humidity, pressures and airflows, active special modes, one binary value per alarm, and a write section with BMS setpoints, setpoint offsets, the operating mode, BMS outdoor/room temperature, an electric heater power limit and remote alarm reset.

This page lists 198 BACnet objects for the WOLF WRS-K air handling unit controller - BACnet interface — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WOLF’s own free documentation, linked below.

Manufacturer
WOLF
Model
WRS-K air handling unit controller - BACnet interface
Equipment
Air handling unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
198 (27 writable)
Transport
BACnet IP
Firmware
WRS-K 5.4-5.8 (some objects need the later versions)
Default device instance
77000
Also known as
WOLF WRS-K BACnet, Rozhraní BACnet pro WRS-K, Rozhranie BACnet pre WRS-K, KLM-S, KLM-L, KLM-XL
Source document
Rozhraní BACnet pro WRS-K - Návod k obsluze (BACnet interface for WRS-K, operating instructions, Czech) · 3065168 | 202405 · rev. 2024-05
Download CSV 198 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against WOLF’s current documentation and the live device before use. Not official WOLF information. Terms of use.

BMS integration notes: WOLF WRS-K air handling unit controller - BACnet interface

Integration in brief

Set AV 1006 Operation_Mode to 2 (BMS operation) and write the BMS setpoints (AV 15 temperature, AV 16/17 fan speeds or AV 1015/1016 pressure, AV 1014 fan step). In manual or weekly-program mode, adjust with the Offset objects instead. Read BV 5 Status_AHU, the supply and room temperatures, and BV 1 Alarm_General plus the individual alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 1006Operation_ModeOperating mode: 0 manual, 1 weekly program, 2 BMSWrite
AV 1014Setpoint_Fan_Step_BMSUnit on/off in BMS mode: 1 = off, 2 = onWrite
AV 15Setpoint_Temperature_BMSTemperature setpoint from the BMS, °CWrite
AV 16Setpoint_Speed_SUP_BMSSupply fan speed setpoint from the BMS, %Write
AV 17Setpoint_Speed_ETA_BMSExtract fan speed setpoint from the BMS, %Write
BV 90Alarm_Reset_BMSRemote alarm reset (enable in service menu)Write
BV 5Status_AHUUnit status (1 = running)Read
AV 1Temperature_SUPSupply air temperatureRead
AV 3Temperature_RoomRoom temperatureRead
BV 1Alarm_GeneralCommon faultRead

Enable & remote start

AV 1006 Operation_Mode selects 0 = manual operation, 1 = weekly program, 2 = BMS operation. In BMS operation the _BMS setpoint objects apply and AV 1014 Setpoint_Fan_Step_BMS switches the unit (1 = off, 2 = on); in manual or weekly-program mode the Offset_..._BMS objects shift the local setpoints. Values outside the allowed range are rejected and the old value is kept.

Sensors & values from the BMS

AV 37 Temperature_Outdoor_BMS and AV 71 Temperature_Room_BMS take outdoor and room temperature from the BMS once enabled in the service menu. Each value is plausibility-checked: outside -50 to 60 °C, or unchanged by at least 0.1 K for 24 hours, raises an alarm.

Network setup

Watch out for

WOLF WRS-K air handling unit controller - BACnet interface BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

198 of 198 shown
Type
AnalogBinary
Access
Show
WOLF WRS-K air handling unit controller - BACnet interface BACnet Points List
DescriptionStates
BVmin1Alarm_GeneralCommon faultRead
BV2Ext_Request_EnableRead
BV3HygrostatRead
BV4Humidifier_EnableRead
BV148Dehumidification_EnableRead
BVmin5Status_AHUUnit statusRead0=Unit not running, 1=Unit running
BV117Status_OperationRead0=Standby, 1=Ready
BV60Pump_HeatingRead
BV18Pump_CoolingRead
BV61Request_HeatingRead
BV62Request_Heat_RecoveryRead
BV63Request_Damper_SUPRead
BV64Request_Damper_ETARead
BV87Adiabatic_Cooling_EnableRead
BV89Air_Heater_EnableRead
BVmin90Alarm_Reset_BMSAlarm reset from the BMSWrite
BV91Drain_Valve_SUP_WaterRead
BV92Drain_Valve_TankRead
BV94Feed_Valve_Adiabatic_CoolingRead
BV150FilterPreDreyerRead
BV177Request_PreheaterRead
AVmin1Temperature_SUP°CRead
AV2Temperature_Outdoor°CRead
AVmin3Temperature_Room°CRead
AV4Temperature_ETA°CRead
AV48Temperature_Dewpoint°CRead
AV46Temperature_SUP_HR°CRead
AV5Air_Quality_VOCVRead
AV6Setpoint_Device°CRead
AV7Humidity_Room%RHRead
AV8Humidity_ETA%RHRead
AV9Humidity_SUP%RHRead
AV42Humidity_Outdoor%RHRead
AV10Setpoint_Temperature_SUP°CRead
AV11Setpoint_Temperature°CRead
AV12Setpoint_Fresh_Air%Read
AV13Setpoint_Speed_SUP_Fan%Read
AV14Setpoint_Speed_ETA_Fan%Read
AV23Setpoint_Humidity%RHRead
AV24Setpoint_Humidity_Absg/kgRead
AV27Temperature_Heat_Recovery°CRead
AV28Signal_Valve_Heating%Read
AV29Signal_Valve_Cooling%Read
AV30Signal_Heat_Recovery%Read
AV31Signal_Humidifier%Read
AV47Signal_PreHeat%Read
AV32Temperature_Adiabatic_Cooling°CRead
AV33Signal_Valve_Reheating%Read
AV45Temperature_Outdoor_HR°CRead
AV59Temperature_inlet_heater°CRead
AV60Temperature_return_heater°CRead
AV61Temperature_inlet_cooler°CRead
AV62Temperature_return_cooler°CRead
AV1001Air_Quality_CO2ppmRead
AV1002Pressure_SUPPaRead
AV1003Pressure_ETAPaRead
AV1175Pressure_Static_SUPPaRead
AV1185Pressure_Static_ETAPaRead
AV1004Volume_SUPSupply airflow; real value = transmitted x 10m³/hRead
AV1005Volume_ETAExtract airflow; real value = transmitted x 10m³/hRead
AVmin1006Operation_ModeOperating mode; write 2 for BMS operationWrite0=Manual operation, 1=Weekly program, 2=BMS operation
AV1007Setpoint_Fan_StageRead0=Fans off, 1=Fans on
AV1008Setpoint_Pressure_SUP_AirPaRead
AV1009Setpoint_Pressure_ETA_AirPaRead
AV1010Setpoint_Volume_SUP_AirSupply airflow setpoint; real value = transmitted x 10m³/hRead
AV1011Setpoint_Volume_ETA_AirExtract airflow setpoint; real value = transmitted x 10m³/hRead
AV1025Chiller_StageRead
AV1012Request_CoolingRead
AV1024EHeating_StageRead
AV1047Heatpump-ModeRead0=No release, 1=Heating released, 2=Cooling released
AV1091Pressure_Filter_SUP1PaRead
AV1092Pressure_Filter_SUP3PaRead
AV1093Pressure_Filter_SUP3PaRead
AV1094Pressure_Filter_ETA1PaRead
AV1095Pressure_Filter_ETA2PaRead
BV6Special_HolidaySpecial operating mode activeRead
BV7Special_FilterSpecial operating mode activeRead
BV8Special_PreheatSpecial operating mode activeRead
BV9Special_NightVentilationSpecial operating mode activeRead
BV10Special_BackupModeSpecial operating mode activeRead
BV11Special_UtilisationSpecial operating mode activeRead
BV12Special_PeakVentilationSpecial operating mode activeRead
BV13Special_NaturalCoolingSpecial operating mode activeRead
BV14Special_HygrostatSpecial operating mode activeRead
BV15Special_AirQualitySpecial operating mode activeRead
BV16Special_ExternalDemandSpecial operating mode activeRead
BV17Special_RunOnSpecial operating mode activeRead
BV101Special_HR_IcingSpecial operating mode activeRead
BV102Special_Speed ReductionSpecial operating mode activeRead
BV112Special_Setback ModeSpecial operating mode activeRead
BV113Special_WinterstartSpecial operating mode activeRead
BV125Special_Min_Temp_SUPSpecial operating mode activeRead
BV129Special_QuickheatSpecial operating mode activeRead
BV149Special_Defrost_HPSpecial operating mode activeRead
BV178Special_FrostSpecial operating mode activeRead
BV19Alarm_Inverter_SUPAlarm activeRead
BV20Alarm_Temp_Motor_SUPAlarm activeRead
BV21Alarm_RepairSwitch_SUPAlarm activeRead
BV22Alarm_AirFlow_SUPAlarm activeRead
BV23Alarm_Inverter_ETAAlarm activeRead
BV25Alarm_RepairSwitch_ETAAlarm activeRead
BV26Alarm_AirFlow_ETAAlarm activeRead
BV30Alarm_Pump_HotWaterAlarm activeRead
BV31Alarm_FrostAlarm activeRead
BV32Alarm_Frost_SUPAlarm activeRead
BV33Alarm_TempLimiter_EHeaterAlarm activeRead
BV34Alarm_SafetyTempLimiter_EHeaterAlarm activeRead
BV35Alarm_Pump_ColdWaterAlarm activeRead
BV36Alarm_ChillerAlarm activeRead
BV37Alarm_FireAlarm activeRead
BV47Alarm_Fire_DamperAlarm activeRead
BV48Alarm_Fan_SUPAlarm activeRead
BV49Alarm_Fan_ETAAlarm activeRead
BV50Alarm_KLM_EAlarm activeRead
BV51Alarm_BMK_FAlarm activeRead
BV52Alarm_ServiceAlarm activeRead
BV54Alarm_HRAlarm activeRead
BV55Alarm_Service_HumiAlarm activeRead
BV56Alarm_HumiAlarm activeRead
BV57Alarm_ExternAlarm activeRead
BV58Alarm_SmokeAlarmAlarm activeRead
BV59Alarm_Setpoint_DeviceAlarm activeRead
BV66Alarm_Fire_Damper_1Alarm activeRead
BV67Alarm_Fire_Damper_2Alarm activeRead
BV68Alarm_Fire_Damper_3Alarm activeRead
BV69Alarm_Fire_Damper_4Alarm activeRead
BV70Alarm_Fire_Damper_5Alarm activeRead
BV71Alarm_Fire_Damper_6Alarm activeRead
BV72Alarm_Fire_Damper_7Alarm activeRead
BV73Alarm_Fire_Damper_8Alarm activeRead
BV74Alarm_Fire_Damper_9Alarm activeRead
BV75Alarm_Fire_Damper_10Alarm activeRead
BV76Alarm_Fire_Damper_11Alarm activeRead
BV77Alarm_Fire_Damper_12Alarm activeRead
BV78Alarm_Fire_Damper_13Alarm activeRead
BV79Alarm_Fire_Damper_14Alarm activeRead
BV80Alarm_Fire_Damper_15Alarm activeRead
BV81Alarm_Fire_Damper_16Alarm activeRead
BV82Alarm_Fire_Damper_17Alarm activeRead
BV83Alarm_Fire_Damper_18Alarm activeRead
BV84Alarm_Fire_Damper_19Alarm activeRead
BV85Alarm_Fire_Damper_20Alarm activeRead
BV86Alarm_Fire_Damper_21Alarm activeRead
BV88Alarm_AC_CalcificationAlarm activeRead
BV95Alarm_Air_HeaterAlarm activeRead
BV96Alarm_AC_HumiAlarm activeRead
BV97Alarm_AC_Cooling_PowerAlarm activeRead
BV98Alarm_AC_IcingAlarm activeRead
BV100Alarm_Service_AC_HumiAlarm activeRead
BV114Alarm_HPAlarm activeRead
BV115Alarm_Pump_ReheatingAlarm activeRead
BV116Alarm_Frost_ReheatingAlarm activeRead
BV120Alarm_pLAN_ChillerAlarm activeRead
BV121Alarm_pLAN_CCSAlarm activeRead
BV122Alarm_kvsAlarm activeRead
BV128Alarm_Temp_out_gltAlarm activeRead
BV134Alarm_Temp_Room_BMSAlarm activeRead
BV139SafetyTempLim_PreheaterAlarm activeRead
BV146Alarm_DehumificationAlarm activeRead
BV166Alarm_SUP_Filter_1Alarm activeRead
BV167Alarm_SUP_Filter_2Alarm activeRead
BV168Alarm_SUP_Filter_3Alarm activeRead
BV164Alarm_ETA_Filter_1Alarm activeRead
BV165Alarm_ETA_Filter_2Alarm activeRead
BV169Alarm_Inverter_1Alarm activeRead
BV170Alarm_Inverter_2Alarm activeRead
BV171Alarm_Inverter_3Alarm activeRead
BV173Alarm_Pump_ChOverAlarm activeRead
BV174Alarm_SafetyTempLim_PredryerAlarm activeRead
BV175Alarm_Ventilator2_SUPAlarm activeRead
BV176Alarm_Ventilator2_ETAAlarm activeRead
BV189Alarm_Frost_Return_HeaterAlarm activeRead
BV193Alarm_Condensatepump_HRAlarm activeRead
AVmin15Setpoint_Temperature_BMS°CWrite
AVmin16Setpoint_Speed_SUP_BMS%Write
AVmin17Setpoint_Speed_ETA_BMS%Write
AV1013Setpoint_Fresh_Air_BMS%Write
AVmin1014Setpoint_Fan_Step_BMSUnit on/off in BMS operationWrite1=Unit off, 2=Unit on
AV1015Setpoint_Pressure_SUP_BMSPaWrite
AV1016Setpoint_Pressure_Exh_Air_BMSPaWrite
AV1017Setpoint_Volume_SUP_BMSReal value = transmitted x 10m³/hWrite
AV1018Setpoint_Volume_ETA_BMSReal value = transmitted x 10m³/hWrite
AV25Setpoint_Humidity_BMS%RHWrite
AV26Setpoint_Humidity_Abs_BMSg/kgWrite
AV18Offset_Temperature_BMSKWrite
AV19Offset_Speed_SUP_Fan_BMS%Write
AV20Offset_Speed_ETA_Fan_BMS%Write
AV1019Offset_Fresh_Air_BMS%Write
AV1020Offset_Pressure_SUP_BMSPaWrite
AV1021Offset_Pressure_ETA_BMSPaWrite
AV21Offset_Humidity_BMSWrite
AV22Offset_Humidity_Abs_BMSWrite
AV1022Offset_Volume_SUP_BMSReal value = transmitted x 10m³/hWrite
AV1023Offset_Volume_ETA_BMSReal value = transmitted x 10m³/hWrite
AV1055Max_Power_EheaterElectric heater power limit%Write
AV37Temperature_Outdoor_BMSOutdoor temperature from the BMS°CWrite
AV71Temperature_Room_BMSRoom temperature from the BMS°CWrite
BV179Mode_cool_extWrite0=Heating medium, 1=Cooling medium
Object ID lookup: WOLF WRS-K air handling unit controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WRS-K air handling unit controller - BACnet interface and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the WOLF WRS-K air handling unit controller - BACnet interface

How many BACnet points does the WOLF WRS-K air handling unit controller - BACnet interface have?

This list has 198 BACnet objects: 78 analog values, 120 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which WOLF WRS-K air handling unit controller - BACnet interface BACnet points are writable?

27 of the 198 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official WOLF WRS-K air handling unit controller - BACnet interface BACnet documentation?

The source is Rozhraní BACnet pro WRS-K - Návod k obsluze (BACnet interface for WRS-K, operating instructions, Czech) (3065168 | 202405), revision 2024-05, published free by WOLF at https://wolf.eu/download-asset/Ly95RHEwRzlhSGJQRUt0MlhvRnBKZz09.

What are the minimum BACnet points to integrate the WOLF WRS-K air handling unit controller - BACnet interface?

Start with AV 1006 Operation_Mode (Operating mode: 0 manual, 1 weekly program, 2 BMS); AV 1014 Setpoint_Fan_Step_BMS (Unit on/off in BMS mode: 1 = off, 2 = on); AV 15 Setpoint_Temperature_BMS (Temperature setpoint from the BMS, °C); AV 16 Setpoint_Speed_SUP_BMS (Supply fan speed setpoint from the BMS, %); AV 17 Setpoint_Speed_ETA_BMS (Extract fan speed setpoint from the BMS, %); BV 90 Alarm_Reset_BMS (Remote alarm reset (enable in service menu)); BV 5 Status_AHU (Unit status (1 = running)); AV 1 Temperature_SUP (Supply air temperature); AV 3 Temperature_Room (Room temperature); BV 1 Alarm_General (Common fault).

How do I enable BMS control of the WOLF WRS-K air handling unit controller - BACnet interface?

AV 1006 Operation_Mode selects 0 = manual operation, 1 = weekly program, 2 = BMS operation. In BMS operation the _BMS setpoint objects apply and AV 1014 Setpoint_Fan_Step_BMS switches the unit (1 = off, 2 = on); in manual or weekly-program mode the Offset_..._BMS objects shift the local setpoints. Values outside the allowed range are rejected and the old value is kept.

Can the BMS supply sensor values to the WOLF WRS-K air handling unit controller - BACnet interface?

AV 37 Temperature_Outdoor_BMS and AV 71 Temperature_Room_BMS take outdoor and room temperature from the BMS once enabled in the service menu. Each value is plausibility-checked: outside -50 to 60 °C, or unchanged by at least 0.1 K for 24 hours, raises an alarm.

How do I check these points on the real WRS-K air handling unit controller - BACnet interface?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Rozhraní BACnet pro WRS-K - Návod k obsluze (BACnet interface for WRS-K, operating instructions, Czech) · 3065168 | 202405 · rev. 2024-05. Object names, instances and units are reproduced as published; descriptions are our own.