- WRS-K air handling unit controller - BACnet interface
Air handling unit controller · BACnet points list
WOLF WRS-K air handling unit controller - BACnet interface BACnet points list
Updated 7 November 2026
The BACnet interface card for WOLF's WRS-K air-handling controller gives BACnet IP (or BACnet Ethernet) access to the unit. It publishes fixed binary and analog values: operating states and outputs, temperatures, humidity, pressures and airflows, active special modes, one binary value per alarm, and a write section with BMS setpoints, setpoint offsets, the operating mode, BMS outdoor/room temperature, an electric heater power limit and remote alarm reset.
This page lists 198 BACnet objects for the WOLF WRS-K air handling unit controller - BACnet interface — 27 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from WOLF’s own free documentation, linked below.
- Manufacturer
- WOLF
- Model
- WRS-K air handling unit controller - BACnet interface
- Equipment
- Air handling unit controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 198 (27 writable)
- Transport
- BACnet IP
- Firmware
- WRS-K 5.4-5.8 (some objects need the later versions)
- Default device instance
- 77000
- Also known as
- WOLF WRS-K BACnet, Rozhraní BACnet pro WRS-K, Rozhranie BACnet pre WRS-K, KLM-S, KLM-L, KLM-XL
Reference only, provided as-is: verify against WOLF’s current documentation and the live device before use. Not official WOLF information. Terms of use.
BMS integration notes: WOLF WRS-K air handling unit controller - BACnet interface
Set AV 1006 Operation_Mode to 2 (BMS operation) and write the BMS setpoints (AV 15 temperature, AV 16/17 fan speeds or AV 1015/1016 pressure, AV 1014 fan step). In manual or weekly-program mode, adjust with the Offset objects instead. Read BV 5 Status_AHU, the supply and room temperatures, and BV 1 Alarm_General plus the individual alarm BVs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AV 1006 | Operation_Mode | Operating mode: 0 manual, 1 weekly program, 2 BMS | Write |
| AV 1014 | Setpoint_Fan_Step_BMS | Unit on/off in BMS mode: 1 = off, 2 = on | Write |
| AV 15 | Setpoint_Temperature_BMS | Temperature setpoint from the BMS, °C | Write |
| AV 16 | Setpoint_Speed_SUP_BMS | Supply fan speed setpoint from the BMS, % | Write |
| AV 17 | Setpoint_Speed_ETA_BMS | Extract fan speed setpoint from the BMS, % | Write |
| BV 90 | Alarm_Reset_BMS | Remote alarm reset (enable in service menu) | Write |
| BV 5 | Status_AHU | Unit status (1 = running) | Read |
| AV 1 | Temperature_SUP | Supply air temperature | Read |
| AV 3 | Temperature_Room | Room temperature | Read |
| BV 1 | Alarm_General | Common fault | Read |
Enable & remote start
AV 1006 Operation_Mode selects 0 = manual operation, 1 = weekly program, 2 = BMS operation. In BMS operation the _BMS setpoint objects apply and AV 1014 Setpoint_Fan_Step_BMS switches the unit (1 = off, 2 = on); in manual or weekly-program mode the Offset_..._BMS objects shift the local setpoints. Values outside the allowed range are rejected and the old value is kept.
Sensors & values from the BMS
AV 37 Temperature_Outdoor_BMS and AV 71 Temperature_Room_BMS take outdoor and room temperature from the BMS once enabled in the service menu. Each value is plausibility-checked: outside -50 to 60 °C, or unchanged by at least 0.1 K for 24 hours, raises an alarm.
Network setup
- Factory device instance 77000; choose BACnet IP or BACnet Ethernet on the card's BACnet web page.
- Out of the box the card's web pages answer at 172.16.0.1 (factory login in the manual); IP settings are on Configuration > Network.
- An EDE file for the interface is offered on wolf.eu.
Watch out for
- AV 1055 Max_Power_Eheater is held in controller memory and saved to permanent memory only hourly, to spare the memory cells; after a power cut the last saved value applies until a new one is sent.
- With an active setpoint device on the unit, the temperature setpoint cannot be changed over the interface.
- In BMS operation a supply fan speed or pressure setpoint of 0 also sets the extract setpoint to 0.
- Remote alarm reset (BV 90) must be enabled by a service technician and is only offered on some series (CGL2 edu, CFL edu).
WOLF WRS-K air handling unit controller - BACnet interface BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BVmin | 1 | Alarm_General | Common fault | Read | ||
| BV | 2 | Ext_Request_Enable | Read | |||
| BV | 3 | Hygrostat | Read | |||
| BV | 4 | Humidifier_Enable | Read | |||
| BV | 148 | Dehumidification_Enable | Read | |||
| BVmin | 5 | Status_AHU | Unit status | Read | 0=Unit not running, 1=Unit running | |
| BV | 117 | Status_Operation | Read | 0=Standby, 1=Ready | ||
| BV | 60 | Pump_Heating | Read | |||
| BV | 18 | Pump_Cooling | Read | |||
| BV | 61 | Request_Heating | Read | |||
| BV | 62 | Request_Heat_Recovery | Read | |||
| BV | 63 | Request_Damper_SUP | Read | |||
| BV | 64 | Request_Damper_ETA | Read | |||
| BV | 87 | Adiabatic_Cooling_Enable | Read | |||
| BV | 89 | Air_Heater_Enable | Read | |||
| BVmin | 90 | Alarm_Reset_BMS | Alarm reset from the BMS | Write | ||
| BV | 91 | Drain_Valve_SUP_Water | Read | |||
| BV | 92 | Drain_Valve_Tank | Read | |||
| BV | 94 | Feed_Valve_Adiabatic_Cooling | Read | |||
| BV | 150 | FilterPreDreyer | Read | |||
| BV | 177 | Request_Preheater | Read | |||
| AVmin | 1 | Temperature_SUP | °C | Read | ||
| AV | 2 | Temperature_Outdoor | °C | Read | ||
| AVmin | 3 | Temperature_Room | °C | Read | ||
| AV | 4 | Temperature_ETA | °C | Read | ||
| AV | 48 | Temperature_Dewpoint | °C | Read | ||
| AV | 46 | Temperature_SUP_HR | °C | Read | ||
| AV | 5 | Air_Quality_VOC | V | Read | ||
| AV | 6 | Setpoint_Device | °C | Read | ||
| AV | 7 | Humidity_Room | %RH | Read | ||
| AV | 8 | Humidity_ETA | %RH | Read | ||
| AV | 9 | Humidity_SUP | %RH | Read | ||
| AV | 42 | Humidity_Outdoor | %RH | Read | ||
| AV | 10 | Setpoint_Temperature_SUP | °C | Read | ||
| AV | 11 | Setpoint_Temperature | °C | Read | ||
| AV | 12 | Setpoint_Fresh_Air | % | Read | ||
| AV | 13 | Setpoint_Speed_SUP_Fan | % | Read | ||
| AV | 14 | Setpoint_Speed_ETA_Fan | % | Read | ||
| AV | 23 | Setpoint_Humidity | %RH | Read | ||
| AV | 24 | Setpoint_Humidity_Abs | g/kg | Read | ||
| AV | 27 | Temperature_Heat_Recovery | °C | Read | ||
| AV | 28 | Signal_Valve_Heating | % | Read | ||
| AV | 29 | Signal_Valve_Cooling | % | Read | ||
| AV | 30 | Signal_Heat_Recovery | % | Read | ||
| AV | 31 | Signal_Humidifier | % | Read | ||
| AV | 47 | Signal_PreHeat | % | Read | ||
| AV | 32 | Temperature_Adiabatic_Cooling | °C | Read | ||
| AV | 33 | Signal_Valve_Reheating | % | Read | ||
| AV | 45 | Temperature_Outdoor_HR | °C | Read | ||
| AV | 59 | Temperature_inlet_heater | °C | Read | ||
| AV | 60 | Temperature_return_heater | °C | Read | ||
| AV | 61 | Temperature_inlet_cooler | °C | Read | ||
| AV | 62 | Temperature_return_cooler | °C | Read | ||
| AV | 1001 | Air_Quality_CO2 | ppm | Read | ||
| AV | 1002 | Pressure_SUP | Pa | Read | ||
| AV | 1003 | Pressure_ETA | Pa | Read | ||
| AV | 1175 | Pressure_Static_SUP | Pa | Read | ||
| AV | 1185 | Pressure_Static_ETA | Pa | Read | ||
| AV | 1004 | Volume_SUP | Supply airflow; real value = transmitted x 10 | m³/h | Read | |
| AV | 1005 | Volume_ETA | Extract airflow; real value = transmitted x 10 | m³/h | Read | |
| AVmin | 1006 | Operation_Mode | Operating mode; write 2 for BMS operation | Write | 0=Manual operation, 1=Weekly program, 2=BMS operation | |
| AV | 1007 | Setpoint_Fan_Stage | Read | 0=Fans off, 1=Fans on | ||
| AV | 1008 | Setpoint_Pressure_SUP_Air | Pa | Read | ||
| AV | 1009 | Setpoint_Pressure_ETA_Air | Pa | Read | ||
| AV | 1010 | Setpoint_Volume_SUP_Air | Supply airflow setpoint; real value = transmitted x 10 | m³/h | Read | |
| AV | 1011 | Setpoint_Volume_ETA_Air | Extract airflow setpoint; real value = transmitted x 10 | m³/h | Read | |
| AV | 1025 | Chiller_Stage | Read | |||
| AV | 1012 | Request_Cooling | Read | |||
| AV | 1024 | EHeating_Stage | Read | |||
| AV | 1047 | Heatpump-Mode | Read | 0=No release, 1=Heating released, 2=Cooling released | ||
| AV | 1091 | Pressure_Filter_SUP1 | Pa | Read | ||
| AV | 1092 | Pressure_Filter_SUP3 | Pa | Read | ||
| AV | 1093 | Pressure_Filter_SUP3 | Pa | Read | ||
| AV | 1094 | Pressure_Filter_ETA1 | Pa | Read | ||
| AV | 1095 | Pressure_Filter_ETA2 | Pa | Read | ||
| BV | 6 | Special_Holiday | Special operating mode active | Read | ||
| BV | 7 | Special_Filter | Special operating mode active | Read | ||
| BV | 8 | Special_Preheat | Special operating mode active | Read | ||
| BV | 9 | Special_NightVentilation | Special operating mode active | Read | ||
| BV | 10 | Special_BackupMode | Special operating mode active | Read | ||
| BV | 11 | Special_Utilisation | Special operating mode active | Read | ||
| BV | 12 | Special_PeakVentilation | Special operating mode active | Read | ||
| BV | 13 | Special_NaturalCooling | Special operating mode active | Read | ||
| BV | 14 | Special_Hygrostat | Special operating mode active | Read | ||
| BV | 15 | Special_AirQuality | Special operating mode active | Read | ||
| BV | 16 | Special_ExternalDemand | Special operating mode active | Read | ||
| BV | 17 | Special_RunOn | Special operating mode active | Read | ||
| BV | 101 | Special_HR_Icing | Special operating mode active | Read | ||
| BV | 102 | Special_Speed Reduction | Special operating mode active | Read | ||
| BV | 112 | Special_Setback Mode | Special operating mode active | Read | ||
| BV | 113 | Special_Winterstart | Special operating mode active | Read | ||
| BV | 125 | Special_Min_Temp_SUP | Special operating mode active | Read | ||
| BV | 129 | Special_Quickheat | Special operating mode active | Read | ||
| BV | 149 | Special_Defrost_HP | Special operating mode active | Read | ||
| BV | 178 | Special_Frost | Special operating mode active | Read | ||
| BV | 19 | Alarm_Inverter_SUP | Alarm active | Read | ||
| BV | 20 | Alarm_Temp_Motor_SUP | Alarm active | Read | ||
| BV | 21 | Alarm_RepairSwitch_SUP | Alarm active | Read | ||
| BV | 22 | Alarm_AirFlow_SUP | Alarm active | Read | ||
| BV | 23 | Alarm_Inverter_ETA | Alarm active | Read | ||
| BV | 25 | Alarm_RepairSwitch_ETA | Alarm active | Read | ||
| BV | 26 | Alarm_AirFlow_ETA | Alarm active | Read | ||
| BV | 30 | Alarm_Pump_HotWater | Alarm active | Read | ||
| BV | 31 | Alarm_Frost | Alarm active | Read | ||
| BV | 32 | Alarm_Frost_SUP | Alarm active | Read | ||
| BV | 33 | Alarm_TempLimiter_EHeater | Alarm active | Read | ||
| BV | 34 | Alarm_SafetyTempLimiter_EHeater | Alarm active | Read | ||
| BV | 35 | Alarm_Pump_ColdWater | Alarm active | Read | ||
| BV | 36 | Alarm_Chiller | Alarm active | Read | ||
| BV | 37 | Alarm_Fire | Alarm active | Read | ||
| BV | 47 | Alarm_Fire_Damper | Alarm active | Read | ||
| BV | 48 | Alarm_Fan_SUP | Alarm active | Read | ||
| BV | 49 | Alarm_Fan_ETA | Alarm active | Read | ||
| BV | 50 | Alarm_KLM_E | Alarm active | Read | ||
| BV | 51 | Alarm_BMK_F | Alarm active | Read | ||
| BV | 52 | Alarm_Service | Alarm active | Read | ||
| BV | 54 | Alarm_HR | Alarm active | Read | ||
| BV | 55 | Alarm_Service_Humi | Alarm active | Read | ||
| BV | 56 | Alarm_Humi | Alarm active | Read | ||
| BV | 57 | Alarm_Extern | Alarm active | Read | ||
| BV | 58 | Alarm_SmokeAlarm | Alarm active | Read | ||
| BV | 59 | Alarm_Setpoint_Device | Alarm active | Read | ||
| BV | 66 | Alarm_Fire_Damper_1 | Alarm active | Read | ||
| BV | 67 | Alarm_Fire_Damper_2 | Alarm active | Read | ||
| BV | 68 | Alarm_Fire_Damper_3 | Alarm active | Read | ||
| BV | 69 | Alarm_Fire_Damper_4 | Alarm active | Read | ||
| BV | 70 | Alarm_Fire_Damper_5 | Alarm active | Read | ||
| BV | 71 | Alarm_Fire_Damper_6 | Alarm active | Read | ||
| BV | 72 | Alarm_Fire_Damper_7 | Alarm active | Read | ||
| BV | 73 | Alarm_Fire_Damper_8 | Alarm active | Read | ||
| BV | 74 | Alarm_Fire_Damper_9 | Alarm active | Read | ||
| BV | 75 | Alarm_Fire_Damper_10 | Alarm active | Read | ||
| BV | 76 | Alarm_Fire_Damper_11 | Alarm active | Read | ||
| BV | 77 | Alarm_Fire_Damper_12 | Alarm active | Read | ||
| BV | 78 | Alarm_Fire_Damper_13 | Alarm active | Read | ||
| BV | 79 | Alarm_Fire_Damper_14 | Alarm active | Read | ||
| BV | 80 | Alarm_Fire_Damper_15 | Alarm active | Read | ||
| BV | 81 | Alarm_Fire_Damper_16 | Alarm active | Read | ||
| BV | 82 | Alarm_Fire_Damper_17 | Alarm active | Read | ||
| BV | 83 | Alarm_Fire_Damper_18 | Alarm active | Read | ||
| BV | 84 | Alarm_Fire_Damper_19 | Alarm active | Read | ||
| BV | 85 | Alarm_Fire_Damper_20 | Alarm active | Read | ||
| BV | 86 | Alarm_Fire_Damper_21 | Alarm active | Read | ||
| BV | 88 | Alarm_AC_Calcification | Alarm active | Read | ||
| BV | 95 | Alarm_Air_Heater | Alarm active | Read | ||
| BV | 96 | Alarm_AC_Humi | Alarm active | Read | ||
| BV | 97 | Alarm_AC_Cooling_Power | Alarm active | Read | ||
| BV | 98 | Alarm_AC_Icing | Alarm active | Read | ||
| BV | 100 | Alarm_Service_AC_Humi | Alarm active | Read | ||
| BV | 114 | Alarm_HP | Alarm active | Read | ||
| BV | 115 | Alarm_Pump_Reheating | Alarm active | Read | ||
| BV | 116 | Alarm_Frost_Reheating | Alarm active | Read | ||
| BV | 120 | Alarm_pLAN_Chiller | Alarm active | Read | ||
| BV | 121 | Alarm_pLAN_CCS | Alarm active | Read | ||
| BV | 122 | Alarm_kvs | Alarm active | Read | ||
| BV | 128 | Alarm_Temp_out_glt | Alarm active | Read | ||
| BV | 134 | Alarm_Temp_Room_BMS | Alarm active | Read | ||
| BV | 139 | SafetyTempLim_Preheater | Alarm active | Read | ||
| BV | 146 | Alarm_Dehumification | Alarm active | Read | ||
| BV | 166 | Alarm_SUP_Filter_1 | Alarm active | Read | ||
| BV | 167 | Alarm_SUP_Filter_2 | Alarm active | Read | ||
| BV | 168 | Alarm_SUP_Filter_3 | Alarm active | Read | ||
| BV | 164 | Alarm_ETA_Filter_1 | Alarm active | Read | ||
| BV | 165 | Alarm_ETA_Filter_2 | Alarm active | Read | ||
| BV | 169 | Alarm_Inverter_1 | Alarm active | Read | ||
| BV | 170 | Alarm_Inverter_2 | Alarm active | Read | ||
| BV | 171 | Alarm_Inverter_3 | Alarm active | Read | ||
| BV | 173 | Alarm_Pump_ChOver | Alarm active | Read | ||
| BV | 174 | Alarm_SafetyTempLim_Predryer | Alarm active | Read | ||
| BV | 175 | Alarm_Ventilator2_SUP | Alarm active | Read | ||
| BV | 176 | Alarm_Ventilator2_ETA | Alarm active | Read | ||
| BV | 189 | Alarm_Frost_Return_Heater | Alarm active | Read | ||
| BV | 193 | Alarm_Condensatepump_HR | Alarm active | Read | ||
| AVmin | 15 | Setpoint_Temperature_BMS | °C | Write | ||
| AVmin | 16 | Setpoint_Speed_SUP_BMS | % | Write | ||
| AVmin | 17 | Setpoint_Speed_ETA_BMS | % | Write | ||
| AV | 1013 | Setpoint_Fresh_Air_BMS | % | Write | ||
| AVmin | 1014 | Setpoint_Fan_Step_BMS | Unit on/off in BMS operation | Write | 1=Unit off, 2=Unit on | |
| AV | 1015 | Setpoint_Pressure_SUP_BMS | Pa | Write | ||
| AV | 1016 | Setpoint_Pressure_Exh_Air_BMS | Pa | Write | ||
| AV | 1017 | Setpoint_Volume_SUP_BMS | Real value = transmitted x 10 | m³/h | Write | |
| AV | 1018 | Setpoint_Volume_ETA_BMS | Real value = transmitted x 10 | m³/h | Write | |
| AV | 25 | Setpoint_Humidity_BMS | %RH | Write | ||
| AV | 26 | Setpoint_Humidity_Abs_BMS | g/kg | Write | ||
| AV | 18 | Offset_Temperature_BMS | K | Write | ||
| AV | 19 | Offset_Speed_SUP_Fan_BMS | % | Write | ||
| AV | 20 | Offset_Speed_ETA_Fan_BMS | % | Write | ||
| AV | 1019 | Offset_Fresh_Air_BMS | % | Write | ||
| AV | 1020 | Offset_Pressure_SUP_BMS | Pa | Write | ||
| AV | 1021 | Offset_Pressure_ETA_BMS | Pa | Write | ||
| AV | 21 | Offset_Humidity_BMS | Write | |||
| AV | 22 | Offset_Humidity_Abs_BMS | Write | |||
| AV | 1022 | Offset_Volume_SUP_BMS | Real value = transmitted x 10 | m³/h | Write | |
| AV | 1023 | Offset_Volume_ETA_BMS | Real value = transmitted x 10 | m³/h | Write | |
| AV | 1055 | Max_Power_Eheater | Electric heater power limit | % | Write | |
| AV | 37 | Temperature_Outdoor_BMS | Outdoor temperature from the BMS | °C | Write | |
| AV | 71 | Temperature_Room_BMS | Room temperature from the BMS | °C | Write | |
| BV | 179 | Mode_cool_ext | Write | 0=Heating medium, 1=Cooling medium |
No points match these filters.
Object ID lookup: WOLF WRS-K air handling unit controller point IDs by name
BV1Alarm_GeneralBV2Ext_Request_EnableBV3HygrostatBV4Humidifier_EnableBV148Dehumidification_EnableBV5Status_AHUBV117Status_OperationBV60Pump_HeatingBV18Pump_CoolingBV61Request_HeatingBV62Request_Heat_RecoveryBV63Request_Damper_SUPBV64Request_Damper_ETABV87Adiabatic_Cooling_EnableBV89Air_Heater_EnableBV90Alarm_Reset_BMSBV91Drain_Valve_SUP_WaterBV92Drain_Valve_TankBV94Feed_Valve_Adiabatic_CoolingBV150FilterPreDreyerBV177Request_PreheaterAV1Temperature_SUPAV2Temperature_OutdoorAV3Temperature_RoomAV4Temperature_ETAAV48Temperature_DewpointAV46Temperature_SUP_HRAV5Air_Quality_VOCAV6Setpoint_DeviceAV7Humidity_RoomAV8Humidity_ETAAV9Humidity_SUPAV42Humidity_OutdoorAV10Setpoint_Temperature_SUPAV11Setpoint_TemperatureAV12Setpoint_Fresh_AirAV13Setpoint_Speed_SUP_FanAV14Setpoint_Speed_ETA_FanAV23Setpoint_HumidityAV24Setpoint_Humidity_AbsAV27Temperature_Heat_RecoveryAV28Signal_Valve_HeatingAV29Signal_Valve_CoolingAV30Signal_Heat_RecoveryAV31Signal_HumidifierAV47Signal_PreHeatAV32Temperature_Adiabatic_CoolingAV33Signal_Valve_ReheatingAV45Temperature_Outdoor_HRAV59Temperature_inlet_heaterAV60Temperature_return_heaterAV61Temperature_inlet_coolerAV62Temperature_return_coolerAV1001Air_Quality_CO2AV1002Pressure_SUPAV1003Pressure_ETAAV1175Pressure_Static_SUPAV1185Pressure_Static_ETAAV1004Volume_SUPAV1005Volume_ETAAV1006Operation_ModeAV1007Setpoint_Fan_StageAV1008Setpoint_Pressure_SUP_AirAV1009Setpoint_Pressure_ETA_AirAV1010Setpoint_Volume_SUP_AirAV1011Setpoint_Volume_ETA_AirAV1025Chiller_StageAV1012Request_CoolingAV1024EHeating_StageAV1047Heatpump-ModeAV1091Pressure_Filter_SUP1AV1092Pressure_Filter_SUP3AV1093Pressure_Filter_SUP3AV1094Pressure_Filter_ETA1AV1095Pressure_Filter_ETA2BV6Special_HolidayBV7Special_FilterBV8Special_PreheatBV9Special_NightVentilationBV10Special_BackupModeBV11Special_UtilisationBV12Special_PeakVentilationBV13Special_NaturalCoolingBV14Special_HygrostatBV15Special_AirQualityBV16Special_ExternalDemandBV17Special_RunOnBV101Special_HR_IcingBV102Special_Speed ReductionBV112Special_Setback ModeBV113Special_WinterstartBV125Special_Min_Temp_SUPBV129Special_QuickheatBV149Special_Defrost_HPBV178Special_FrostBV19Alarm_Inverter_SUPBV20Alarm_Temp_Motor_SUPBV21Alarm_RepairSwitch_SUPBV22Alarm_AirFlow_SUPBV23Alarm_Inverter_ETABV25Alarm_RepairSwitch_ETABV26Alarm_AirFlow_ETABV30Alarm_Pump_HotWaterBV31Alarm_FrostBV32Alarm_Frost_SUPBV33Alarm_TempLimiter_EHeaterBV34Alarm_SafetyTempLimiter_EHeaterBV35Alarm_Pump_ColdWaterBV36Alarm_ChillerBV37Alarm_FireBV47Alarm_Fire_DamperBV48Alarm_Fan_SUPBV49Alarm_Fan_ETABV50Alarm_KLM_EBV51Alarm_BMK_FBV52Alarm_ServiceBV54Alarm_HRBV55Alarm_Service_HumiBV56Alarm_HumiBV57Alarm_ExternBV58Alarm_SmokeAlarmBV59Alarm_Setpoint_DeviceBV66Alarm_Fire_Damper_1BV67Alarm_Fire_Damper_2BV68Alarm_Fire_Damper_3BV69Alarm_Fire_Damper_4BV70Alarm_Fire_Damper_5BV71Alarm_Fire_Damper_6BV72Alarm_Fire_Damper_7BV73Alarm_Fire_Damper_8BV74Alarm_Fire_Damper_9BV75Alarm_Fire_Damper_10BV76Alarm_Fire_Damper_11BV77Alarm_Fire_Damper_12BV78Alarm_Fire_Damper_13BV79Alarm_Fire_Damper_14BV80Alarm_Fire_Damper_15BV81Alarm_Fire_Damper_16BV82Alarm_Fire_Damper_17BV83Alarm_Fire_Damper_18BV84Alarm_Fire_Damper_19BV85Alarm_Fire_Damper_20BV86Alarm_Fire_Damper_21BV88Alarm_AC_CalcificationBV95Alarm_Air_HeaterBV96Alarm_AC_HumiBV97Alarm_AC_Cooling_PowerBV98Alarm_AC_IcingBV100Alarm_Service_AC_HumiBV114Alarm_HPBV115Alarm_Pump_ReheatingBV116Alarm_Frost_ReheatingBV120Alarm_pLAN_ChillerBV121Alarm_pLAN_CCSBV122Alarm_kvsBV128Alarm_Temp_out_gltBV134Alarm_Temp_Room_BMSBV139SafetyTempLim_PreheaterBV146Alarm_DehumificationBV166Alarm_SUP_Filter_1BV167Alarm_SUP_Filter_2BV168Alarm_SUP_Filter_3BV164Alarm_ETA_Filter_1BV165Alarm_ETA_Filter_2BV169Alarm_Inverter_1BV170Alarm_Inverter_2BV171Alarm_Inverter_3BV173Alarm_Pump_ChOverBV174Alarm_SafetyTempLim_PredryerBV175Alarm_Ventilator2_SUPBV176Alarm_Ventilator2_ETABV189Alarm_Frost_Return_HeaterBV193Alarm_Condensatepump_HRAV15Setpoint_Temperature_BMSAV16Setpoint_Speed_SUP_BMSAV17Setpoint_Speed_ETA_BMSAV1013Setpoint_Fresh_Air_BMSAV1014Setpoint_Fan_Step_BMSAV1015Setpoint_Pressure_SUP_BMSAV1016Setpoint_Pressure_Exh_Air_BMSAV1017Setpoint_Volume_SUP_BMSAV1018Setpoint_Volume_ETA_BMSAV25Setpoint_Humidity_BMSAV26Setpoint_Humidity_Abs_BMSAV18Offset_Temperature_BMSAV19Offset_Speed_SUP_Fan_BMSAV20Offset_Speed_ETA_Fan_BMSAV1019Offset_Fresh_Air_BMSAV1020Offset_Pressure_SUP_BMSAV1021Offset_Pressure_ETA_BMSAV21Offset_Humidity_BMSAV22Offset_Humidity_Abs_BMSAV1022Offset_Volume_SUP_BMSAV1023Offset_Volume_ETA_BMSAV1055Max_Power_EheaterAV37Temperature_Outdoor_BMSAV71Temperature_Room_BMSBV179Mode_cool_ext
Integration notes
- Taken from section 7 (Interface description) of WOLF's Czech-language BACnet interface manual for the WRS-K (3065168, 2024-05); object types, instances, object names and units are printed in the tables, the descriptions there are Czech.
- Access follows the manual's sections: 7.1 read-only access, 7.2 write access. AV 1006 Operation_Mode is listed in both and is writable.
- The manual prints BV 90 twice: as Adiabatic_Cooling_Enable (air-heater thermostat) in the read table and as Alarm_Reset_BMS (WRS-K 5.7.000+) in the write section. Only the Alarm_Reset_BMS entry is kept; check on site.
- BV 87 and BV 90 both carry the name Adiabatic_Cooling_Enable in the read table; AV 1092 and AV 1093 are both printed as Pressure_Filter_SUP3. Names are kept as printed.
- Airflow objects marked in the manual (AV 1004/1005, 1010/1011, 1017/1018, 1022/1023) carry the real value divided by 10.
- Several objects need a minimum WRS-K software version (5.4.000 to 5.8.000), as footnoted in the manual.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WRS-K air handling unit controller - BACnet interface and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the WOLF WRS-K air handling unit controller - BACnet interface
How many BACnet points does the WOLF WRS-K air handling unit controller - BACnet interface have?
This list has 198 BACnet objects: 78 analog values, 120 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which WOLF WRS-K air handling unit controller - BACnet interface BACnet points are writable?
27 of the 198 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official WOLF WRS-K air handling unit controller - BACnet interface BACnet documentation?
The source is Rozhraní BACnet pro WRS-K - Návod k obsluze (BACnet interface for WRS-K, operating instructions, Czech) (3065168 | 202405), revision 2024-05, published free by WOLF at https://wolf.eu/download-asset/Ly95RHEwRzlhSGJQRUt0MlhvRnBKZz09.
What are the minimum BACnet points to integrate the WOLF WRS-K air handling unit controller - BACnet interface?
Start with AV 1006 Operation_Mode (Operating mode: 0 manual, 1 weekly program, 2 BMS); AV 1014 Setpoint_Fan_Step_BMS (Unit on/off in BMS mode: 1 = off, 2 = on); AV 15 Setpoint_Temperature_BMS (Temperature setpoint from the BMS, °C); AV 16 Setpoint_Speed_SUP_BMS (Supply fan speed setpoint from the BMS, %); AV 17 Setpoint_Speed_ETA_BMS (Extract fan speed setpoint from the BMS, %); BV 90 Alarm_Reset_BMS (Remote alarm reset (enable in service menu)); BV 5 Status_AHU (Unit status (1 = running)); AV 1 Temperature_SUP (Supply air temperature); AV 3 Temperature_Room (Room temperature); BV 1 Alarm_General (Common fault).
How do I enable BMS control of the WOLF WRS-K air handling unit controller - BACnet interface?
AV 1006 Operation_Mode selects 0 = manual operation, 1 = weekly program, 2 = BMS operation. In BMS operation the _BMS setpoint objects apply and AV 1014 Setpoint_Fan_Step_BMS switches the unit (1 = off, 2 = on); in manual or weekly-program mode the Offset_..._BMS objects shift the local setpoints. Values outside the allowed range are rejected and the old value is kept.
Can the BMS supply sensor values to the WOLF WRS-K air handling unit controller - BACnet interface?
AV 37 Temperature_Outdoor_BMS and AV 71 Temperature_Room_BMS take outdoor and room temperature from the BMS once enabled in the service menu. Each value is plausibility-checked: outside -50 to 60 °C, or unchanged by at least 0.1 K for 24 hours, raises an alarm.
How do I check these points on the real WRS-K air handling unit controller - BACnet interface?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
Source: Rozhraní BACnet pro WRS-K - Návod k obsluze (BACnet interface for WRS-K, operating instructions, Czech) · 3065168 | 202405 · rev. 2024-05. Object names, instances and units are reproduced as published; descriptions are our own.