- Home
- BACnet points lists
- Wildeboer
- WiVent-B decentralised ventilation unit, BACnet IP
Decentralised ventilation unit (energy recovery) · BACnet points list
Wildeboer WiVent-B decentralised ventilation unit, BACnet IP BACnet points list
Updated 12 November 2026
The WiVent-B is a decentralised facade ventilation unit for classrooms and offices. Its Beckhoff CX9020 controller runs TwinCAT BACnet over BACnet IP and publishes a schedule and holiday calendar, command switches and push buttons as Binary Values, status and alarm flags as Binary Inputs, airflow and temperature settings as Analog Values, measurements for the master and up to five slave units as Analog Inputs, and operating mode, faults and warnings as multi-state objects.
This page lists 115 BACnet objects for the Wildeboer WiVent-B decentralised ventilation unit, BACnet IP — 39 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Wildeboer’s own free documentation, linked below.
- Manufacturer
- Wildeboer
- Model
- WiVent-B decentralised ventilation unit, BACnet IP
- Equipment
- Decentralised ventilation unit (energy recovery)
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 115 (39 writable)
- Transport
- BACnet IP
- Firmware
- TwinCAT BACnet 4.0.1 (PICS)
- Also known as
- WiVent-B, WiVent, WiVent B, Wildeboer WiVent, WiVent dezentrales Lüftungsgerät
Reference only, provided as-is: verify against Wildeboer’s current documentation and the live device before use. Not official Wildeboer information. Terms of use.
BMS integration notes: Wildeboer WiVent-B decentralised ventilation unit, BACnet IP
Command the operating mode with MSV 400 (or let the internal schedule run), keep the watchdog alive if it is enabled, and read the operating mode status, room temperature, CO2 and the fault and warning flags.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 400 | WiVent_Betriebsart | Operating mode command | Write |
| BV 201 | WiVent_Takt_Watchdog | Watchdog pulse, toggle faster than every 10 s | Write |
| BV 209 | WiVent_Externe_Fehlerquittierung | Fault acknowledge | Write |
| MI 450 | WiVent_Betriebsart_Status | Current operating mode | Read |
| AI 352 | WiVent_Temperatur_IDA | Room temperature, °C | Read |
| AI 353 | WiVent_Luftqualität_IDA | Room CO2, ppm | Read |
| AI 355 | WiVent_Temperatur_SUP_Master | Supply air temperature, °C | Read |
| BI 262 | WiVent_Störung_1 | Master fault | Read |
| BI 260 | WiVent_Warnung_1B | Warning with unit shutdown | Read |
| MV 460 | WiVent_Warnung_System | System warning code (filters, schedule) | Read |
Enable & remote start
MSV 400 sets the operating mode; BV 204 (external release) and BV 205 (external fault shutdown) put the unit into protection mode.
Heartbeat & communication loss
BV 200 enables a connection watchdog; BV 201 is the watchdog pulse and must change faster than every 10 s. The document does not say what the unit does when the pulse stops.
Network setup
- BACnet IP on the Beckhoff CX9020 (TwinCAT BACnet, vendor ID 415); the PICS also lists MS/TP via an EL6861 terminal.
- The full set of objects for a given installation is defined in its EDE files.
Watch out for
- Filter test, filter drying, presence and fault acknowledge are push-button Binary Values; write active, not a held state.
- State texts of the multi-states are German.
Wildeboer WiVent-B decentralised ventilation unit, BACnet IP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| SCH | 100 | WiVent_Scheduler | Building automation time schedule | Write | ||
| CAL | 101 | Ferienkalender | Holiday calendar | Write | ||
| BV | 200 | WiVent_Watchdog | Connection watchdog on/off | Write | 0=Inaktive, 1=Aktive | |
| BVmin | 201 | WiVent_Takt_Watchdog | Watchdog pulse (toggle faster than 10 s) | Write | 0=False, 1=True | |
| BV | 202 | WiVent_Filtertest | Start filter test (push button) | Write | 0=Inaktive, 1=Aktive | |
| BV | 203 | WiVent_Filtertrocknung | Start filter drying (push button) | Write | 0=Inaktive, 1=Aktive | |
| BV | 204 | WiVent_Externe_Freigabe | External release; unit goes to protection mode (switch) | Write | 1=Release | |
| BV | 205 | WiVent_Externe_Fehlerabschaltung | External fault shutdown; unit goes to protection mode (switch) | Write | 1=Failure | |
| BV | 206 | WiVent_Gedämpfte_Außentemperatur | Enable damped outdoor temperature (switch) | Write | 0=Inaktive, 1=Aktive | |
| BV | 207 | WiVent_Sekundärluftbetrieb | Enable secondary-air (recirculation) mode (switch) | Write | 0=Inaktive, 1=Aktive | |
| BV | 208 | WiVent_Präsenz | Presence request (push button) | Write | 1=Aktivate | |
| BVmin | 209 | WiVent_Externe_Fehlerquittierung | Fault acknowledge (push button) | Write | 1=Acknowledge | |
| BI | 250 | WiVent_Meldung_Betriebsart | Internal operating mode overridden | Read | 0=Inaktive, 1=Aktive | |
| BI | 251 | WiVent_Status_Manuelle_Steuerung | Manual control active | Read | 0=Inaktive, 1=Aktive | |
| BI | 252 | WiVent_Status_Klappe_ODA | Outdoor air facade damper (master) | Read | 0=OPEN, 1=CLOSED | |
| BI | 253 | WiVent_Status_Klappe_EHA | Exhaust air facade damper (master) | Read | 0=OPEN, 1=CLOSED | |
| BI | 254 | WiVent_Status_ExterneZeitquelle | External time source (NTP) status | Read | 0=Inaktive, 1=Aktive | |
| BI | 255 | WiVent_Status_Freigabekontakt | Release contact status | Read | 0=Inaktive, 1=Aktive | |
| BI | 256 | WiVent_Status_Fehlerabschaltung | Fault shutdown status | Read | 0=Inaktive, 1=Aktive | |
| BI | 257 | WiVent_Status_Präsenz | Presence status | Read | 0=Inaktive, 1=Aktive | |
| BI | 258 | WiVent_Status_Sekundärluftbetrieb | Forced secondary-air mode status | Read | 0=Inaktive, 1=Aktive | |
| BI | 259 | WiVent_Warnung_1A | System warning, unit keeps running | Read | 0=Inaktive, 1=Aktive | |
| BImin | 260 | WiVent_Warnung_1B | System warning with unit shutdown | Read | 0=Inaktive, 1=Aktive | |
| BI | 261 | WiVent_Warnung_2 | Slave unit warning | Read | 0=Inaktive, 1=Aktive | |
| BImin | 262 | WiVent_Störung_1 | Master unit fault | Read | 0=Inaktive, 1=Aktive | |
| BI | 263 | WiVent_Störung_2 | Slave unit fault | Read | 0=Inaktive, 1=Aktive | |
| AV | 300 | WiVent_Volumenstrom_Grundlüftung | Airflow setpoint, base ventilation (100-500, default 300) | m³/h | Write | |
| AV | 301 | WiVent_Volumenstrom_Komfortbetrieb | Airflow setpoint, comfort mode (default 300) | m³/h | Write | |
| AV | 302 | WiVent_Volumenstrom_Außenluftbetrieb | Airflow setpoint, outdoor-air mode (default 300) | m³/h | Write | |
| AV | 303 | WiVent_Volumenstrom_Nachtlüftung | Airflow setpoint, night ventilation (default 300) | m³/h | Write | |
| AV | 304 | WiVent_Volumenstrom_Pausenlüftung | Airflow setpoint, break ventilation (default 500) | m³/h | Write | |
| AV | 305 | WiVent_Volumenstrom_Filtertrocknung | Airflow setpoint, filter drying (default 250) | m³/h | Write | |
| AV | 306 | WiVent_Zeitvorgabe_Filtertrocknung | Filter drying duration (10-180, default 30) | min | Write | |
| AV | 307 | WiVent_Zeitvorgabe_Präsenz | Presence run time after activation (10-480, default 120) | min | Write | |
| AV | 308 | WiVent_Filterverschmutzung_ODA | Outdoor air filter warning threshold (default 85) | % | Write | |
| AV | 309 | WiVent_Filterverschmutzung_ETA | Extract air filter warning threshold (default 85) | % | Write | |
| AV | 310 | WiVent_Temperatur_Schutzbetrieb | Protection mode temperature threshold (default 18) | °C | Write | |
| AV | 311 | WiVent_Temperatur_Heizmedium | Heating medium threshold for heating (default 24) | °C | Write | |
| AV | 312 | WiVent_Temperatur_Kühlmedium | Cooling medium threshold for cooling (default 22) | °C | Write | |
| AV | 313 | WiVent_Einschalttemperatur_IDA_Nachtkühlung | Night cooling on at room temp (default 24) | °C | Write | |
| AV | 314 | WiVent_Ausschalttemperatur_IDA_Nachtkühlung | Night cooling off at room temp (default 20) | °C | Write | |
| AV | 315 | WiVent_Differenztemperatur_Nachtkühlung | Night cooling minimum indoor-outdoor difference (default 4) | K | Write | |
| AV | 316 | WiVent_Min_Temperatur_ODA_Nachtkühlung | Night cooling minimum outdoor temp (default 12) | °C | Write | |
| AV | 317 | WiVent_Max_Untertemperaturdifferenz_SUP-IDA>25°C | Max supply air under-temperature vs room above 25 °C (default 5) | K | Write | |
| AV | 318 | WiVent_Max_Übertemperaturdifferenz_SUP-IDA | Max supply air over-temperature vs room (default 20) | K | Write | |
| AV | 319 | WiVent_Min_Temperatur_RBG | Room unit temperature adjust minimum (default -3) | K | Write | |
| AV | 320 | WiVent_Max_Temperatur_RBG | Room unit temperature adjust maximum (default 3) | K | Write | |
| AV | 321 | WiVent_Min_Volumenstrom_RBG | Room unit airflow adjust minimum (default 120) | m³/h | Write | |
| AV | 322 | WiVent_Max_Volumenstrom_RBG | Room unit airflow adjust maximum (default 120) | m³/h | Write | |
| AV | 323 | WiVent_CO2_Einschaltschwelle | CO2 switch-on threshold (default 700) | ppm | Write | |
| AV | 324 | WiVent_CO2_Ausschaltschwelle | CO2 switch-off threshold (default 600) | ppm | Write | |
| AV | 325 | WiVent_Temperatur_Bereitschaft | Standby temperature threshold (default 19) | °C | Write | |
| AI | 350 | WiVent_Firmware | Current firmware version | Read | ||
| AI | 351 | WiVent_Temperatur_ODA | Outdoor temperature | °C | Read | |
| AImin | 352 | WiVent_Temperatur_IDA | Room temperature | °C | Read | |
| AImin | 353 | WiVent_Luftqualität_IDA | Room air quality, CO2 | ppm | Read | |
| AI | 354 | WiVent_Luftfeuchtigkeit_IDA | Room relative humidity | %RH | Read | |
| AImin | 355 | WiVent_Temperatur_SUP_Master | Supply air temperature, master | °C | Read | |
| AI | 356 | WiVent_Soll_Temperatur_IDA | Room temperature setpoint | °C | Read | |
| AI | 357 | WiVent_Rücklauftemperatur_Heizen_Master | Heating medium return temperature, master | °C | Read | |
| AI | 358 | WiVent_Rücklauftemperatur_Kühlen_Master | Cooling medium return temperature, master | °C | Read | |
| AI | 359 | WiVent_Verschmutzung_Filter_ODA | Outdoor air filter loading | % | Read | |
| AI | 360 | WiVent_Verschmutzung_Filter_ETA | Extract air filter loading | % | Read | |
| AI | 361 | WiVent_Gedämpfte_Temperatur_ODA | Damped outdoor temperature | °C | Read | |
| AI | 362 | WiVent_Durchflusskennwert_ETA | Extract air flow pressure value | Pa | Read | |
| AI | 363 | WiVent_Druckverlust_Filter_ETA | Extract air filter pressure drop | Pa | Read | |
| AI | 364 | WiVent_Durchflusskennwert_ODA | Outdoor air flow pressure value | Pa | Read | |
| AI | 365 | WiVent_Druckverlust_Filter_ODA | Outdoor air filter pressure drop | Pa | Read | |
| AI | 366 | WiVent_Temperatur_Offset_RBG | Temperature offset from room unit | K | Read | |
| AI | 367 | WiVent_Volumensrom_Offset_RBG | Airflow offset from room unit | m³/h | Read | |
| AI | 368 | WiVent_Temperatur_MIA | Mixed air temperature | °C | Read | |
| AI | 369 | WiVent_Restlaufzeit_Präsenz | Remaining presence run time | min | Read | |
| AI | 370 | WiVent_Einschalttemperatur_Heizen | Heating switch point | °C | Read | |
| AI | 371 | WiVent_Einschalttemperatur_Kühlen | Cooling switch point | °C | Read | |
| AI | 372 | WiVent_Offset_Raumregler | Room controller offset | Read | ||
| AI | 373 | WiVent_Betriebsstunden_Gerät | Unit operating hours | h | Read | |
| AI | 374 | WiVent_Betriebsstunden_Ventilatoren | Fan operating hours | h | Read | |
| AI | 375 | WiVent_Zähler_Ventilatorstarts | Fan start count | Read | ||
| AI | 376 | WiVent_Zähler_Klappen_Öffnungen | Facade damper opening count | Read | ||
| AI | 377 | WiVent_Zähler_Gerät_Ein | Unit switch-on count | Read | ||
| AI | 378 | WiVent_Aktive_Slaves | Number of active slave units | Read | ||
| AI | 379 | WiVent_Temperatur_SUP_Slave1 | Supply air temperature, slave 1 | °C | Read | |
| AI | 380 | WiVent_Rücklauftemperatur_Heizen_Slave1 | Heating medium return temperature, slave 1 | °C | Read | |
| AI | 381 | WiVent_Rücklauftemperatur_Kühlen_Slave1 | Cooling medium return temperature, slave 1 | °C | Read | |
| AI | 382 | WiVent_Temperatur_SUP_Slave2 | Supply air temperature, slave 2 | °C | Read | |
| AI | 383 | WiVent_Rücklauftemperatur_Heizen_Slave2 | Heating medium return temperature, slave 2 | °C | Read | |
| AI | 384 | WiVent_Rücklauftemperatur_Kühlen_Slave2 | Cooling medium return temperature, slave 2 | °C | Read | |
| AI | 385 | WiVent_Temperatur_SUP_Slave3 | Supply air temperature, slave 3 | °C | Read | |
| AI | 386 | WiVent_Rücklauftemperatur_Heizen_Slave3 | Heating medium return temperature, slave 3 | °C | Read | |
| AI | 387 | WiVent_Rücklauftemperatur_Kühlen_Slave3 | Cooling medium return temperature, slave 3 | °C | Read | |
| AI | 388 | WiVent_Temperatur_SUP_Slave4 | Supply air temperature, slave 4 | °C | Read | |
| AI | 389 | WiVent_Rücklauftemperatur_Heizen_Slave4 | Heating medium return temperature, slave 4 | °C | Read | |
| AI | 390 | WiVent_Rücklauftemperatur_Kühlen_Slave4 | Cooling medium return temperature, slave 4 | °C | Read | |
| AI | 391 | WiVent_Temperatur_SUP_Slave5 | Supply air temperature, slave 5 | °C | Read | |
| AI | 392 | WiVent_Rücklauftemperatur_Heizen_Slave5 | Heating medium return temperature, slave 5 | °C | Read | |
| AI | 393 | WiVent_Rücklauftemperatur_Kühlen_Slave5 | Cooling medium return temperature, slave 5 | °C | Read | |
| MVmin | 400 | WiVent_Betriebsart | Operating mode command | Write | 1=inaktiv, 2=Gerät Aus, 3=Schutzbetrieb, 4=Grundlüftung, 5=Aufheizen, 6=Komfortbetrieb, 7=Außenluftbetrieb, 8=Bereitschaft, 9=Nachtlüftung, 10=Pausenlüftung | |
| MImin | 450 | WiVent_Betriebsart_Status | Current operating mode | Read | 1=Gerät Aus, 2=Schutzbetrieb, 3=Grundlüftung, 4=Aufheizen, 5=Komfortbetrieb, 6=Außenluftbetrieb, 7=Bereitschaft, 8=Nachtlüftung, 9=Pausenlüftung, 10=Filterüberwachung, 11=Filtertrocknung, 12=Sicherheits/Notbetrieb | |
| MI | 451 | WiVent_Betriebsmodus | Heating/cooling mode | Read | 1=Aus, 2=Kühlen, 3=Heizen | |
| MV | 452 | WiVent_Störungen_Sensoren_Master | Master sensor faults | Read | 1=keine Störung, 2=Master-Raumtempertursensor, 3=Master-Raumluftsensor, 4=Master-Außenluft-Temperatursensor, 5=Master-Zuluft-Temperatursensor, 6=Master-Mischluft-Temperatursensor, 7=Master-Heizmedium-Temperatursensor, 8=Master-Kühlmedium-Temperatursensor, 9=Master-Drucksensoren | |
| MV | 453 | WiVent_Störungen_Aktoren_Master | Master actuator faults | Read | 1=keine Störung, 2=Kondensatpumpe Master, 3=Außenluft-Fassadenklappe, 4=Fortluft-Fassadenklappe | |
| MV | 454 | WiVent_Störungen_Temperatur | Temperature faults | Read | 1=keine Störung, 2=Mischlufttemperatur zu kalt, 3=Zulufttemperatur zu kalt (verzögerte Abschaltung), 4=Zulufttemperatur < 5°C (Sofortabschaltung) | |
| MV | 455 | WiVent_Störungen_Slave1 | Slave 1 faults | Read | 1=keine Störung, 2=Slave 1-Außenluft-Temperatursensor, 3=Slave 1-Zuluft-Temperatursensor, 4=Slave 1-Mischluft-Temperatursensor, 5=Slave 1-Heizmedium-Temperatursensor, 6=Slave 1-Kühlmedium-Temperatursensor, 7=Slave 1-Außenluft-Fassadenklappe, 8=Slave 1-Fortluft-Fassadenklappe, 9=Slave 1-Kondensatpumpe | |
| MV | 456 | WiVent_Störungen_Slave2 | Slave 2 faults | Read | 1=keine Störung, 2=Slave 2-Außenluft-Temperatursensor, 3=Slave 2-Zuluft-Temperatursensor, 4=Slave 2-Mischluft-Temperatursensor, 5=Slave 2-Heizmedium-Temperatursensor, 6=Slave 2-Kühlmedium-Temperatursensor, 7=Slave 2-Außenluft-Fassadenklappe, 8=Slave 2-Fortluft-Fassadenklappe, 9=Slave 2-Kondensatpumpe | |
| MV | 457 | WiVent_Störungen_Slave3 | Slave 3 faults | Read | 1=keine Störung, 2=Slave 3-Außenluft-Temperatursensor, 3=Slave 3-Zuluft-Temperatursensor, 4=Slave 3-Mischluft-Temperatursensor, 5=Slave 3-Heizmedium-Temperatursensor, 6=Slave 3-Kühlmedium-Temperatursensor, 7=Slave 3-Außenluft-Fassadenklappe, 8=Slave 3-Fortluft-Fassadenklappe, 9=Slave 3-Kondensatpumpe | |
| MV | 458 | WiVent_Störungen_Slave4 | Slave 4 faults | Read | 1=keine Störung, 2=Slave 4-Außenluft-Temperatursensor, 3=Slave 4-Zuluft-Temperatursensor, 4=Slave 4-Mischluft-Temperatursensor, 5=Slave 4-Heizmedium-Temperatursensor, 6=Slave 4-Kühlmedium-Temperatursensor, 7=Slave 4-Außenluft-Fassadenklappe, 8=Slave 4-Fortluft-Fassadenklappe, 9=Slave 4-Kondensatpumpe | |
| MV | 459 | WiVent_Störungen_Slave5 | Slave 5 faults | Read | 1=keine Störung, 2=Slave 5-Außenluft-Temperatursensor, 3=Slave 5-Zuluft-Temperatursensor, 4=Slave 5-Mischluft-Temperatursensor, 5=Slave 5-Heizmedium-Temperatursensor, 6=Slave 5-Kühlmedium-Temperatursensor, 7=Slave 5-Außenluft-Fassadenklappe, 8=Slave 5-Fortluft-Fassadenklappe, 9=Slave 5-Kondensatpumpe | |
| MVmin | 460 | WiVent_Warnung_System | System warnings | Read | 1=keine Warnung, 2=keine Einträge Ferien, 3=keine Einträge Zeitplanung, 4=Außenluftfilter bald wechseln, 5=Abluftfilter bald wechseln, 6=Außenluftfilter wechseln, 7=Abluftfilter wechseln, 8=Außenlufttemperatur zu kalt, 9=Winddruckabschaltung | |
| MV | 461 | WiVent_Warnung_Externe_Kontakte | External contact warnings | Read | 1=keine Warnung, 2=Freigabekontalt, 3=Fehlerkontakt | |
| MV | 462 | WiVent_Warnung_Master | Master warnings | Read | 1=keine Warnung, 2=Master kein Heizmedium, 3=Master kein Kühlmedium | |
| MV | 463 | WiVent_Warnung_Slave1 | Slave 1 warnings | Read | 1=keine Warnung, 2=Slave1 kein Heizmedium, 3=Slave1 kein Kühlmedium | |
| MV | 464 | WiVent_Warnung_Slave2 | Slave 2 warnings | Read | 1=keine Warnung, 2=Slave2 kein Heizmedium, 3=Slave2 kein Kühlmedium | |
| MV | 465 | WiVent_Warnung_Slave3 | Slave 3 warnings | Read | 1=keine Warnung, 2=Slave3 kein Heizmedium, 3=Slave3 kein Kühlmedium | |
| MV | 466 | WiVent_Warnung_Slave4 | Slave 4 warnings | Read | 1=keine Warnung, 2=Slave4 kein Heizmedium, 3=Slave4 kein Kühlmedium | |
| MV | 467 | WiVent_Warnung_Slave5 | Slave 5 warnings | Read | 1=keine Warnung, 2=Slave5 kein Heizmedium, 3=Slave5 kein Kühlmedium |
No points match these filters.
Object ID lookup: Wildeboer WiVent-B decentralised ventilation unit, point IDs by name
SCH100WiVent_SchedulerCAL101FerienkalenderBV200WiVent_WatchdogBV201WiVent_Takt_WatchdogBV202WiVent_FiltertestBV203WiVent_FiltertrocknungBV204WiVent_Externe_FreigabeBV205WiVent_Externe_FehlerabschaltungBV206WiVent_Gedämpfte_AußentemperaturBV207WiVent_SekundärluftbetriebBV208WiVent_PräsenzBV209WiVent_Externe_FehlerquittierungBI250WiVent_Meldung_BetriebsartBI251WiVent_Status_Manuelle_SteuerungBI252WiVent_Status_Klappe_ODABI253WiVent_Status_Klappe_EHABI254WiVent_Status_ExterneZeitquelleBI255WiVent_Status_FreigabekontaktBI256WiVent_Status_FehlerabschaltungBI257WiVent_Status_PräsenzBI258WiVent_Status_SekundärluftbetriebBI259WiVent_Warnung_1ABI260WiVent_Warnung_1BBI261WiVent_Warnung_2BI262WiVent_Störung_1BI263WiVent_Störung_2AV300WiVent_Volumenstrom_GrundlüftungAV301WiVent_Volumenstrom_KomfortbetriebAV302WiVent_Volumenstrom_AußenluftbetriebAV303WiVent_Volumenstrom_NachtlüftungAV304WiVent_Volumenstrom_PausenlüftungAV305WiVent_Volumenstrom_FiltertrocknungAV306WiVent_Zeitvorgabe_FiltertrocknungAV307WiVent_Zeitvorgabe_PräsenzAV308WiVent_Filterverschmutzung_ODAAV309WiVent_Filterverschmutzung_ETAAV310WiVent_Temperatur_SchutzbetriebAV311WiVent_Temperatur_HeizmediumAV312WiVent_Temperatur_KühlmediumAV313WiVent_Einschalttemperatur_IDA_NachtkühlungAV314WiVent_Ausschalttemperatur_IDA_NachtkühlungAV315WiVent_Differenztemperatur_NachtkühlungAV316WiVent_Min_Temperatur_ODA_NachtkühlungAV317WiVent_Max_Untertemperaturdifferenz_SUP-IDA>25°CAV318WiVent_Max_Übertemperaturdifferenz_SUP-IDAAV319WiVent_Min_Temperatur_RBGAV320WiVent_Max_Temperatur_RBGAV321WiVent_Min_Volumenstrom_RBGAV322WiVent_Max_Volumenstrom_RBGAV323WiVent_CO2_EinschaltschwelleAV324WiVent_CO2_AusschaltschwelleAV325WiVent_Temperatur_BereitschaftAI350WiVent_FirmwareAI351WiVent_Temperatur_ODAAI352WiVent_Temperatur_IDAAI353WiVent_Luftqualität_IDAAI354WiVent_Luftfeuchtigkeit_IDAAI355WiVent_Temperatur_SUP_MasterAI356WiVent_Soll_Temperatur_IDAAI357WiVent_Rücklauftemperatur_Heizen_MasterAI358WiVent_Rücklauftemperatur_Kühlen_MasterAI359WiVent_Verschmutzung_Filter_ODAAI360WiVent_Verschmutzung_Filter_ETAAI361WiVent_Gedämpfte_Temperatur_ODAAI362WiVent_Durchflusskennwert_ETAAI363WiVent_Druckverlust_Filter_ETAAI364WiVent_Durchflusskennwert_ODAAI365WiVent_Druckverlust_Filter_ODAAI366WiVent_Temperatur_Offset_RBGAI367WiVent_Volumensrom_Offset_RBGAI368WiVent_Temperatur_MIAAI369WiVent_Restlaufzeit_PräsenzAI370WiVent_Einschalttemperatur_HeizenAI371WiVent_Einschalttemperatur_KühlenAI372WiVent_Offset_RaumreglerAI373WiVent_Betriebsstunden_GerätAI374WiVent_Betriebsstunden_VentilatorenAI375WiVent_Zähler_VentilatorstartsAI376WiVent_Zähler_Klappen_ÖffnungenAI377WiVent_Zähler_Gerät_EinAI378WiVent_Aktive_SlavesAI379WiVent_Temperatur_SUP_Slave1AI380WiVent_Rücklauftemperatur_Heizen_Slave1AI381WiVent_Rücklauftemperatur_Kühlen_Slave1AI382WiVent_Temperatur_SUP_Slave2AI383WiVent_Rücklauftemperatur_Heizen_Slave2AI384WiVent_Rücklauftemperatur_Kühlen_Slave2AI385WiVent_Temperatur_SUP_Slave3AI386WiVent_Rücklauftemperatur_Heizen_Slave3AI387WiVent_Rücklauftemperatur_Kühlen_Slave3AI388WiVent_Temperatur_SUP_Slave4AI389WiVent_Rücklauftemperatur_Heizen_Slave4AI390WiVent_Rücklauftemperatur_Kühlen_Slave4AI391WiVent_Temperatur_SUP_Slave5AI392WiVent_Rücklauftemperatur_Heizen_Slave5AI393WiVent_Rücklauftemperatur_Kühlen_Slave5MV400WiVent_BetriebsartMI450WiVent_Betriebsart_StatusMI451WiVent_BetriebsmodusMV452WiVent_Störungen_Sensoren_MasterMV453WiVent_Störungen_Aktoren_MasterMV454WiVent_Störungen_TemperaturMV455WiVent_Störungen_Slave1MV456WiVent_Störungen_Slave2MV457WiVent_Störungen_Slave3MV458WiVent_Störungen_Slave4MV459WiVent_Störungen_Slave5MV460WiVent_Warnung_SystemMV461WiVent_Warnung_Externe_KontakteMV462WiVent_Warnung_MasterMV463WiVent_Warnung_Slave1MV464WiVent_Warnung_Slave2MV465WiVent_Warnung_Slave3MV466WiVent_Warnung_Slave4MV467WiVent_Warnung_Slave5
Integration notes
- The interface description is in German; object names, state texts and Active/Inactive texts are kept as printed and descriptions are translated.
- The table has no read/write column; Binary Values, Analog Values, the schedule, calendar and MSV 400 are listed as writable (settings, switches and buttons), inputs and status/fault multi-states as read-only.
- Some names are printed in quotes ("WiVent_Betriebsart"); the quotes are dropped here.
- Defaults and limits printed for the Analog Values can differ after system parameterisation.
- Slave objects only report when slave units are connected (AI 378 = number of active slaves).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WiVent-B decentralised ventilation unit, BACnet IP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Wildeboer WiVent-B decentralised ventilation unit, BACnet IP
How many BACnet points does the Wildeboer WiVent-B decentralised ventilation unit, BACnet IP have?
This list has 115 BACnet objects: 44 analog inputs, 26 analog values, 14 binary inputs, 10 binary values, 1 calendar, 2 multi-state inputs, 1 schedule, 17 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Wildeboer WiVent-B decentralised ventilation unit, BACnet IP BACnet points are writable?
39 of the 115 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Wildeboer WiVent-B decentralised ventilation unit, BACnet IP BACnet documentation?
The source is BACnet - Schnittstellenbeschreibung WiVent-B Dezentrales Lüftungsgerät (c6584.408.005-00_wivent_bacnet_pics_de_00-00), revision 2019-03-04, published free by Wildeboer at https://wildeboer.de/dokumente/produkte/luftverteilung/wivent-b/sprachuebergreifend/wivent-bac-net-ip-schnittstellenbeschreibung.pdf.
What are the minimum BACnet points to integrate the Wildeboer WiVent-B decentralised ventilation unit, BACnet IP?
Start with MV 400 WiVent_Betriebsart (Operating mode command); BV 201 WiVent_Takt_Watchdog (Watchdog pulse, toggle faster than every 10 s); BV 209 WiVent_Externe_Fehlerquittierung (Fault acknowledge); MI 450 WiVent_Betriebsart_Status (Current operating mode); AI 352 WiVent_Temperatur_IDA (Room temperature, °C); AI 353 WiVent_Luftqualität_IDA (Room CO2, ppm); AI 355 WiVent_Temperatur_SUP_Master (Supply air temperature, °C); BI 262 WiVent_Störung_1 (Master fault); BI 260 WiVent_Warnung_1B (Warning with unit shutdown); MV 460 WiVent_Warnung_System (System warning code (filters, schedule)).
How do I enable BMS control of the Wildeboer WiVent-B decentralised ventilation unit, BACnet IP?
MSV 400 sets the operating mode; BV 204 (external release) and BV 205 (external fault shutdown) put the unit into protection mode.
Does the Wildeboer WiVent-B decentralised ventilation unit, BACnet IP need a BACnet heartbeat or have a communication timeout?
BV 200 enables a connection watchdog; BV 201 is the watchdog pulse and must change faster than every 10 s. The document does not say what the unit does when the pulse stops.
How do I check these points on the real WiVent-B decentralised ventilation unit, BACnet IP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Wildeboer BACnet points lists
Source: BACnet - Schnittstellenbeschreibung WiVent-B Dezentrales Lüftungsgerät · c6584.408.005-00_wivent_bacnet_pics_de_00-00 · rev. 2019-03-04. Object names, instances and units are reproduced as published; descriptions are our own.