  4. WiVent-B decentralised ventilation unit, BACnet IP

Decentralised ventilation unit (energy recovery) · BACnet points list

Wildeboer WiVent-B decentralised ventilation unit, BACnet IP BACnet points list

Updated 12 November 2026

Short answer

The WiVent-B is a decentralised facade ventilation unit for classrooms and offices. Its Beckhoff CX9020 controller runs TwinCAT BACnet over BACnet IP and publishes a schedule and holiday calendar, command switches and push buttons as Binary Values, status and alarm flags as Binary Inputs, airflow and temperature settings as Analog Values, measurements for the master and up to five slave units as Analog Inputs, and operating mode, faults and warnings as multi-state objects.

This page lists 115 BACnet objects for the Wildeboer WiVent-B decentralised ventilation unit, BACnet IP — 39 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Wildeboer’s own free documentation, linked below.

Manufacturer
Wildeboer
Model
WiVent-B decentralised ventilation unit, BACnet IP
Equipment
Decentralised ventilation unit (energy recovery)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
115 (39 writable)
Transport
BACnet IP
Firmware
TwinCAT BACnet 4.0.1 (PICS)
Also known as
WiVent-B, WiVent, WiVent B, Wildeboer WiVent, WiVent dezentrales Lüftungsgerät
Source document
BACnet - Schnittstellenbeschreibung WiVent-B Dezentrales Lüftungsgerät · c6584.408.005-00_wivent_bacnet_pics_de_00-00 · rev. 2019-03-04
Download CSV 115 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Wildeboer’s current documentation and the live device before use. Not official Wildeboer information. Terms of use.

BMS integration notes: Wildeboer WiVent-B decentralised ventilation unit, BACnet IP

Integration in brief

Command the operating mode with MSV 400 (or let the internal schedule run), keep the watchdog alive if it is enabled, and read the operating mode status, room temperature, CO2 and the fault and warning flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 400WiVent_BetriebsartOperating mode commandWrite
BV 201WiVent_Takt_WatchdogWatchdog pulse, toggle faster than every 10 sWrite
BV 209WiVent_Externe_FehlerquittierungFault acknowledgeWrite
MI 450WiVent_Betriebsart_StatusCurrent operating modeRead
AI 352WiVent_Temperatur_IDARoom temperature, °CRead
AI 353WiVent_Luftqualität_IDARoom CO2, ppmRead
AI 355WiVent_Temperatur_SUP_MasterSupply air temperature, °CRead
BI 262WiVent_Störung_1Master faultRead
BI 260WiVent_Warnung_1BWarning with unit shutdownRead
MV 460WiVent_Warnung_SystemSystem warning code (filters, schedule)Read

Enable & remote start

MSV 400 sets the operating mode; BV 204 (external release) and BV 205 (external fault shutdown) put the unit into protection mode.

Heartbeat & communication loss

BV 200 enables a connection watchdog; BV 201 is the watchdog pulse and must change faster than every 10 s. The document does not say what the unit does when the pulse stops.

Network setup

Watch out for

Wildeboer WiVent-B decentralised ventilation unit, BACnet IP BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

115 of 115 shown
Type
Access
Show
Wildeboer WiVent-B decentralised ventilation unit, BACnet IP BACnet Points List
DescriptionStates
SCH100WiVent_SchedulerBuilding automation time scheduleWrite
CAL101FerienkalenderHoliday calendarWrite
BV200WiVent_WatchdogConnection watchdog on/offWrite0=Inaktive, 1=Aktive
BVmin201WiVent_Takt_WatchdogWatchdog pulse (toggle faster than 10 s)Write0=False, 1=True
BV202WiVent_FiltertestStart filter test (push button)Write0=Inaktive, 1=Aktive
BV203WiVent_FiltertrocknungStart filter drying (push button)Write0=Inaktive, 1=Aktive
BV204WiVent_Externe_FreigabeExternal release; unit goes to protection mode (switch)Write1=Release
BV205WiVent_Externe_FehlerabschaltungExternal fault shutdown; unit goes to protection mode (switch)Write1=Failure
BV206WiVent_Gedämpfte_AußentemperaturEnable damped outdoor temperature (switch)Write0=Inaktive, 1=Aktive
BV207WiVent_SekundärluftbetriebEnable secondary-air (recirculation) mode (switch)Write0=Inaktive, 1=Aktive
BV208WiVent_PräsenzPresence request (push button)Write1=Aktivate
BVmin209WiVent_Externe_FehlerquittierungFault acknowledge (push button)Write1=Acknowledge
BI250WiVent_Meldung_BetriebsartInternal operating mode overriddenRead0=Inaktive, 1=Aktive
BI251WiVent_Status_Manuelle_SteuerungManual control activeRead0=Inaktive, 1=Aktive
BI252WiVent_Status_Klappe_ODAOutdoor air facade damper (master)Read0=OPEN, 1=CLOSED
BI253WiVent_Status_Klappe_EHAExhaust air facade damper (master)Read0=OPEN, 1=CLOSED
BI254WiVent_Status_ExterneZeitquelleExternal time source (NTP) statusRead0=Inaktive, 1=Aktive
BI255WiVent_Status_FreigabekontaktRelease contact statusRead0=Inaktive, 1=Aktive
BI256WiVent_Status_FehlerabschaltungFault shutdown statusRead0=Inaktive, 1=Aktive
BI257WiVent_Status_PräsenzPresence statusRead0=Inaktive, 1=Aktive
BI258WiVent_Status_SekundärluftbetriebForced secondary-air mode statusRead0=Inaktive, 1=Aktive
BI259WiVent_Warnung_1ASystem warning, unit keeps runningRead0=Inaktive, 1=Aktive
BImin260WiVent_Warnung_1BSystem warning with unit shutdownRead0=Inaktive, 1=Aktive
BI261WiVent_Warnung_2Slave unit warningRead0=Inaktive, 1=Aktive
BImin262WiVent_Störung_1Master unit faultRead0=Inaktive, 1=Aktive
BI263WiVent_Störung_2Slave unit faultRead0=Inaktive, 1=Aktive
AV300WiVent_Volumenstrom_GrundlüftungAirflow setpoint, base ventilation (100-500, default 300)m³/hWrite
AV301WiVent_Volumenstrom_KomfortbetriebAirflow setpoint, comfort mode (default 300)m³/hWrite
AV302WiVent_Volumenstrom_AußenluftbetriebAirflow setpoint, outdoor-air mode (default 300)m³/hWrite
AV303WiVent_Volumenstrom_NachtlüftungAirflow setpoint, night ventilation (default 300)m³/hWrite
AV304WiVent_Volumenstrom_PausenlüftungAirflow setpoint, break ventilation (default 500)m³/hWrite
AV305WiVent_Volumenstrom_FiltertrocknungAirflow setpoint, filter drying (default 250)m³/hWrite
AV306WiVent_Zeitvorgabe_FiltertrocknungFilter drying duration (10-180, default 30)minWrite
AV307WiVent_Zeitvorgabe_PräsenzPresence run time after activation (10-480, default 120)minWrite
AV308WiVent_Filterverschmutzung_ODAOutdoor air filter warning threshold (default 85)%Write
AV309WiVent_Filterverschmutzung_ETAExtract air filter warning threshold (default 85)%Write
AV310WiVent_Temperatur_SchutzbetriebProtection mode temperature threshold (default 18)°CWrite
AV311WiVent_Temperatur_HeizmediumHeating medium threshold for heating (default 24)°CWrite
AV312WiVent_Temperatur_KühlmediumCooling medium threshold for cooling (default 22)°CWrite
AV313WiVent_Einschalttemperatur_IDA_NachtkühlungNight cooling on at room temp (default 24)°CWrite
AV314WiVent_Ausschalttemperatur_IDA_NachtkühlungNight cooling off at room temp (default 20)°CWrite
AV315WiVent_Differenztemperatur_NachtkühlungNight cooling minimum indoor-outdoor difference (default 4)KWrite
AV316WiVent_Min_Temperatur_ODA_NachtkühlungNight cooling minimum outdoor temp (default 12)°CWrite
AV317WiVent_Max_Untertemperaturdifferenz_SUP-IDA>25°CMax supply air under-temperature vs room above 25 °C (default 5)KWrite
AV318WiVent_Max_Übertemperaturdifferenz_SUP-IDAMax supply air over-temperature vs room (default 20)KWrite
AV319WiVent_Min_Temperatur_RBGRoom unit temperature adjust minimum (default -3)KWrite
AV320WiVent_Max_Temperatur_RBGRoom unit temperature adjust maximum (default 3)KWrite
AV321WiVent_Min_Volumenstrom_RBGRoom unit airflow adjust minimum (default 120)m³/hWrite
AV322WiVent_Max_Volumenstrom_RBGRoom unit airflow adjust maximum (default 120)m³/hWrite
AV323WiVent_CO2_EinschaltschwelleCO2 switch-on threshold (default 700)ppmWrite
AV324WiVent_CO2_AusschaltschwelleCO2 switch-off threshold (default 600)ppmWrite
AV325WiVent_Temperatur_BereitschaftStandby temperature threshold (default 19)°CWrite
AI350WiVent_FirmwareCurrent firmware versionRead
AI351WiVent_Temperatur_ODAOutdoor temperature°CRead
AImin352WiVent_Temperatur_IDARoom temperature°CRead
AImin353WiVent_Luftqualität_IDARoom air quality, CO2ppmRead
AI354WiVent_Luftfeuchtigkeit_IDARoom relative humidity%RHRead
AImin355WiVent_Temperatur_SUP_MasterSupply air temperature, master°CRead
AI356WiVent_Soll_Temperatur_IDARoom temperature setpoint°CRead
AI357WiVent_Rücklauftemperatur_Heizen_MasterHeating medium return temperature, master°CRead
AI358WiVent_Rücklauftemperatur_Kühlen_MasterCooling medium return temperature, master°CRead
AI359WiVent_Verschmutzung_Filter_ODAOutdoor air filter loading%Read
AI360WiVent_Verschmutzung_Filter_ETAExtract air filter loading%Read
AI361WiVent_Gedämpfte_Temperatur_ODADamped outdoor temperature°CRead
AI362WiVent_Durchflusskennwert_ETAExtract air flow pressure valuePaRead
AI363WiVent_Druckverlust_Filter_ETAExtract air filter pressure dropPaRead
AI364WiVent_Durchflusskennwert_ODAOutdoor air flow pressure valuePaRead
AI365WiVent_Druckverlust_Filter_ODAOutdoor air filter pressure dropPaRead
AI366WiVent_Temperatur_Offset_RBGTemperature offset from room unitKRead
AI367WiVent_Volumensrom_Offset_RBGAirflow offset from room unitm³/hRead
AI368WiVent_Temperatur_MIAMixed air temperature°CRead
AI369WiVent_Restlaufzeit_PräsenzRemaining presence run timeminRead
AI370WiVent_Einschalttemperatur_HeizenHeating switch point°CRead
AI371WiVent_Einschalttemperatur_KühlenCooling switch point°CRead
AI372WiVent_Offset_RaumreglerRoom controller offsetRead
AI373WiVent_Betriebsstunden_GerätUnit operating hourshRead
AI374WiVent_Betriebsstunden_VentilatorenFan operating hourshRead
AI375WiVent_Zähler_VentilatorstartsFan start countRead
AI376WiVent_Zähler_Klappen_ÖffnungenFacade damper opening countRead
AI377WiVent_Zähler_Gerät_EinUnit switch-on countRead
AI378WiVent_Aktive_SlavesNumber of active slave unitsRead
AI379WiVent_Temperatur_SUP_Slave1Supply air temperature, slave 1°CRead
AI380WiVent_Rücklauftemperatur_Heizen_Slave1Heating medium return temperature, slave 1°CRead
AI381WiVent_Rücklauftemperatur_Kühlen_Slave1Cooling medium return temperature, slave 1°CRead
AI382WiVent_Temperatur_SUP_Slave2Supply air temperature, slave 2°CRead
AI383WiVent_Rücklauftemperatur_Heizen_Slave2Heating medium return temperature, slave 2°CRead
AI384WiVent_Rücklauftemperatur_Kühlen_Slave2Cooling medium return temperature, slave 2°CRead
AI385WiVent_Temperatur_SUP_Slave3Supply air temperature, slave 3°CRead
AI386WiVent_Rücklauftemperatur_Heizen_Slave3Heating medium return temperature, slave 3°CRead
AI387WiVent_Rücklauftemperatur_Kühlen_Slave3Cooling medium return temperature, slave 3°CRead
AI388WiVent_Temperatur_SUP_Slave4Supply air temperature, slave 4°CRead
AI389WiVent_Rücklauftemperatur_Heizen_Slave4Heating medium return temperature, slave 4°CRead
AI390WiVent_Rücklauftemperatur_Kühlen_Slave4Cooling medium return temperature, slave 4°CRead
AI391WiVent_Temperatur_SUP_Slave5Supply air temperature, slave 5°CRead
AI392WiVent_Rücklauftemperatur_Heizen_Slave5Heating medium return temperature, slave 5°CRead
AI393WiVent_Rücklauftemperatur_Kühlen_Slave5Cooling medium return temperature, slave 5°CRead
MVmin400WiVent_BetriebsartOperating mode commandWrite1=inaktiv, 2=Gerät Aus, 3=Schutzbetrieb, 4=Grundlüftung, 5=Aufheizen, 6=Komfortbetrieb, 7=Außenluftbetrieb, 8=Bereitschaft, 9=Nachtlüftung, 10=Pausenlüftung
MImin450WiVent_Betriebsart_StatusCurrent operating modeRead1=Gerät Aus, 2=Schutzbetrieb, 3=Grundlüftung, 4=Aufheizen, 5=Komfortbetrieb, 6=Außenluftbetrieb, 7=Bereitschaft, 8=Nachtlüftung, 9=Pausenlüftung, 10=Filterüberwachung, 11=Filtertrocknung, 12=Sicherheits/Notbetrieb
MI451WiVent_BetriebsmodusHeating/cooling modeRead1=Aus, 2=Kühlen, 3=Heizen
MV452WiVent_Störungen_Sensoren_MasterMaster sensor faultsRead1=keine Störung, 2=Master-Raumtempertursensor, 3=Master-Raumluftsensor, 4=Master-Außenluft-Temperatursensor, 5=Master-Zuluft-Temperatursensor, 6=Master-Mischluft-Temperatursensor, 7=Master-Heizmedium-Temperatursensor, 8=Master-Kühlmedium-Temperatursensor, 9=Master-Drucksensoren
MV453WiVent_Störungen_Aktoren_MasterMaster actuator faultsRead1=keine Störung, 2=Kondensatpumpe Master, 3=Außenluft-Fassadenklappe, 4=Fortluft-Fassadenklappe
MV454WiVent_Störungen_TemperaturTemperature faultsRead1=keine Störung, 2=Mischlufttemperatur zu kalt, 3=Zulufttemperatur zu kalt (verzögerte Abschaltung), 4=Zulufttemperatur < 5°C (Sofortabschaltung)
MV455WiVent_Störungen_Slave1Slave 1 faultsRead1=keine Störung, 2=Slave 1-Außenluft-Temperatursensor, 3=Slave 1-Zuluft-Temperatursensor, 4=Slave 1-Mischluft-Temperatursensor, 5=Slave 1-Heizmedium-Temperatursensor, 6=Slave 1-Kühlmedium-Temperatursensor, 7=Slave 1-Außenluft-Fassadenklappe, 8=Slave 1-Fortluft-Fassadenklappe, 9=Slave 1-Kondensatpumpe
MV456WiVent_Störungen_Slave2Slave 2 faultsRead1=keine Störung, 2=Slave 2-Außenluft-Temperatursensor, 3=Slave 2-Zuluft-Temperatursensor, 4=Slave 2-Mischluft-Temperatursensor, 5=Slave 2-Heizmedium-Temperatursensor, 6=Slave 2-Kühlmedium-Temperatursensor, 7=Slave 2-Außenluft-Fassadenklappe, 8=Slave 2-Fortluft-Fassadenklappe, 9=Slave 2-Kondensatpumpe
MV457WiVent_Störungen_Slave3Slave 3 faultsRead1=keine Störung, 2=Slave 3-Außenluft-Temperatursensor, 3=Slave 3-Zuluft-Temperatursensor, 4=Slave 3-Mischluft-Temperatursensor, 5=Slave 3-Heizmedium-Temperatursensor, 6=Slave 3-Kühlmedium-Temperatursensor, 7=Slave 3-Außenluft-Fassadenklappe, 8=Slave 3-Fortluft-Fassadenklappe, 9=Slave 3-Kondensatpumpe
MV458WiVent_Störungen_Slave4Slave 4 faultsRead1=keine Störung, 2=Slave 4-Außenluft-Temperatursensor, 3=Slave 4-Zuluft-Temperatursensor, 4=Slave 4-Mischluft-Temperatursensor, 5=Slave 4-Heizmedium-Temperatursensor, 6=Slave 4-Kühlmedium-Temperatursensor, 7=Slave 4-Außenluft-Fassadenklappe, 8=Slave 4-Fortluft-Fassadenklappe, 9=Slave 4-Kondensatpumpe
MV459WiVent_Störungen_Slave5Slave 5 faultsRead1=keine Störung, 2=Slave 5-Außenluft-Temperatursensor, 3=Slave 5-Zuluft-Temperatursensor, 4=Slave 5-Mischluft-Temperatursensor, 5=Slave 5-Heizmedium-Temperatursensor, 6=Slave 5-Kühlmedium-Temperatursensor, 7=Slave 5-Außenluft-Fassadenklappe, 8=Slave 5-Fortluft-Fassadenklappe, 9=Slave 5-Kondensatpumpe
MVmin460WiVent_Warnung_SystemSystem warningsRead1=keine Warnung, 2=keine Einträge Ferien, 3=keine Einträge Zeitplanung, 4=Außenluftfilter bald wechseln, 5=Abluftfilter bald wechseln, 6=Außenluftfilter wechseln, 7=Abluftfilter wechseln, 8=Außenlufttemperatur zu kalt, 9=Winddruckabschaltung
MV461WiVent_Warnung_Externe_KontakteExternal contact warningsRead1=keine Warnung, 2=Freigabekontalt, 3=Fehlerkontakt
MV462WiVent_Warnung_MasterMaster warningsRead1=keine Warnung, 2=Master kein Heizmedium, 3=Master kein Kühlmedium
MV463WiVent_Warnung_Slave1Slave 1 warningsRead1=keine Warnung, 2=Slave1 kein Heizmedium, 3=Slave1 kein Kühlmedium
MV464WiVent_Warnung_Slave2Slave 2 warningsRead1=keine Warnung, 2=Slave2 kein Heizmedium, 3=Slave2 kein Kühlmedium
MV465WiVent_Warnung_Slave3Slave 3 warningsRead1=keine Warnung, 2=Slave3 kein Heizmedium, 3=Slave3 kein Kühlmedium
MV466WiVent_Warnung_Slave4Slave 4 warningsRead1=keine Warnung, 2=Slave4 kein Heizmedium, 3=Slave4 kein Kühlmedium
MV467WiVent_Warnung_Slave5Slave 5 warningsRead1=keine Warnung, 2=Slave5 kein Heizmedium, 3=Slave5 kein Kühlmedium
Object ID lookup: Wildeboer WiVent-B decentralised ventilation unit, point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WiVent-B decentralised ventilation unit, BACnet IP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Wildeboer WiVent-B decentralised ventilation unit, BACnet IP

How many BACnet points does the Wildeboer WiVent-B decentralised ventilation unit, BACnet IP have?

This list has 115 BACnet objects: 44 analog inputs, 26 analog values, 14 binary inputs, 10 binary values, 1 calendar, 2 multi-state inputs, 1 schedule, 17 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Wildeboer WiVent-B decentralised ventilation unit, BACnet IP BACnet points are writable?

39 of the 115 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Wildeboer WiVent-B decentralised ventilation unit, BACnet IP BACnet documentation?

The source is BACnet - Schnittstellenbeschreibung WiVent-B Dezentrales Lüftungsgerät (c6584.408.005-00_wivent_bacnet_pics_de_00-00), revision 2019-03-04, published free by Wildeboer at https://wildeboer.de/dokumente/produkte/luftverteilung/wivent-b/sprachuebergreifend/wivent-bac-net-ip-schnittstellenbeschreibung.pdf.

What are the minimum BACnet points to integrate the Wildeboer WiVent-B decentralised ventilation unit, BACnet IP?

Start with MV 400 WiVent_Betriebsart (Operating mode command); BV 201 WiVent_Takt_Watchdog (Watchdog pulse, toggle faster than every 10 s); BV 209 WiVent_Externe_Fehlerquittierung (Fault acknowledge); MI 450 WiVent_Betriebsart_Status (Current operating mode); AI 352 WiVent_Temperatur_IDA (Room temperature, °C); AI 353 WiVent_Luftqualität_IDA (Room CO2, ppm); AI 355 WiVent_Temperatur_SUP_Master (Supply air temperature, °C); BI 262 WiVent_Störung_1 (Master fault); BI 260 WiVent_Warnung_1B (Warning with unit shutdown); MV 460 WiVent_Warnung_System (System warning code (filters, schedule)).

How do I enable BMS control of the Wildeboer WiVent-B decentralised ventilation unit, BACnet IP?

MSV 400 sets the operating mode; BV 204 (external release) and BV 205 (external fault shutdown) put the unit into protection mode.

Does the Wildeboer WiVent-B decentralised ventilation unit, BACnet IP need a BACnet heartbeat or have a communication timeout?

BV 200 enables a connection watchdog; BV 201 is the watchdog pulse and must change faster than every 10 s. The document does not say what the unit does when the pulse stops.

How do I check these points on the real WiVent-B decentralised ventilation unit, BACnet IP?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Wildeboer BACnet points lists

Source: BACnet - Schnittstellenbeschreibung WiVent-B Dezentrales Lüftungsgerät · c6584.408.005-00_wivent_bacnet_pics_de_00-00 · rev. 2019-03-04. Object names, instances and units are reproduced as published; descriptions are our own.