- OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP
Duct smoke detector / smoke release device · BACnet points list
Wildeboer OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP BACnet points list
Updated 12 November 2026
The OR4 pro is a duct smoke release device built around the RM4 optical smoke switch. Its BACnet interface is small: airflow and contamination level as Analog Inputs, operating hours of the OR4 and RM4 as Analog Values, and alarm, contamination trend, fault and airflow flags as Binary Inputs. Nothing is writable.
This page lists 9 BACnet objects for the Wildeboer OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Wildeboer’s own free documentation, linked below.
- Manufacturer
- Wildeboer
- Model
- OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP
- Equipment
- Duct smoke detector / smoke release device
- Equipment type
- Other equipment
- BACnet objects
- 9 (0 writable)
- Transport
- BACnet IP
- Firmware
- FW_006 V1.0.0 (PICS)
- Default device instance
- 2000
- Also known as
- OR4 pro, OR4, OR4-02, Wildeboer OR4, RM4, Rauchauslöseeinrichtung OR4
Reference only, provided as-is: verify against Wildeboer’s current documentation and the live device before use. Not official Wildeboer information. Terms of use.
BMS integration notes: Wildeboer OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP
Read-only device: map the smoke alarm, fault and contamination flags and the airflow flag, plus the contamination level for service planning.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BI 9 | Stroemungssensor | Airflow present in duct | Read |
| AI 2 | Verschmutzung | Smoke switch contamination, % | Read |
| BI 5 | RM4 Alarm | Smoke alarm | Read |
| BI 8 | RM4 Fault | Smoke switch fault | Read |
| BI 6 | RM4 Trend2 | Heavy contamination, service needed | Read |
Network setup
- Device object OR4-02 Device, instance 2000 in the EDE file.
Watch out for
- All objects are read-only.
- The EDE and the PICS number the objects differently (running 1-9 vs per type); confirm instances with a device scan before mapping.
Wildeboer OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Stroemungssensor FS7 | Duct air velocity from flow sensor FS7 | % | Read | |
| AImin | 2 | Verschmutzung | RM4 contamination tracking | % | Read | |
| AV | 3 | Betriebsstunden OR4 | OR4 smoke release device operating hours | h | Read | |
| AV | 4 | Betriebsstunden RM4 | RM4 optical smoke switch operating hours | h | Read | |
| BImin | 5 | RM4 Alarm | Smoke alarm flag from RM4 status byte | Read | 0=Normal, 1=Alarm | |
| BImin | 6 | RM4 Trend2 | Heavy contamination flag from RM4 | Read | 0=Normal, 1=Stark verschmutzt | |
| BI | 7 | RM4 Trend1 | Light contamination flag from RM4 | Read | 0=Normal, 1=Leicht verschmutzt | |
| BImin | 8 | RM4 Fault | Fault flag from RM4 status byte | Read | 0=Normal, 1=Stoerung | |
| BImin | 9 | Stroemungssensor | Airflow present | Read | 0=Keine Stroemung, 1=Stroemung vorhanden |
No points match these filters.
Object ID lookup: Wildeboer OR4 pro smoke release device, point IDs by name
Integration notes
- Objects come from the EDE file (bacnet_EDE_OR4_02.csv) in Wildeboer's interface ZIP; all are marked not settable.
- Object names and state texts are German, kept as in the EDE (ASCII spellings such as Stroemung).
- The ZIP also holds a German PICS (or4pro_bacnet_pics_de_01-00) titled BACnet IP.
- Instance numbers follow the EDE object-instance column (1-9 running). The PICS in the same ZIP numbers the same objects per type instead (AI 1-2, AV 1-2, BI 1-5); check with a scan.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Wildeboer OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP
How many BACnet points does the Wildeboer OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP have?
This list has 9 BACnet objects: 2 analog inputs, 2 analog values, 5 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Wildeboer OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official Wildeboer OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP BACnet documentation?
The source is BACnet Interface description OR4 pro (EDE files + PICS, ZIP) (OR4-02 EDE v1.0), revision 2021-10-04, published free by Wildeboer at https://wildeboer.de/dokumente/produkte/brandschutz-entrauchung/or4/sprachuebergreifend/or4pro_bacnet_schnittstellenbeschreibung.zip.
What are the minimum BACnet points to integrate the Wildeboer OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP?
Start with BI 9 Stroemungssensor (Airflow present in duct); AI 2 Verschmutzung (Smoke switch contamination, %); BI 5 RM4 Alarm (Smoke alarm); BI 8 RM4 Fault (Smoke switch fault); BI 6 RM4 Trend2 (Heavy contamination, service needed).
How do I check these points on the real OR4 pro smoke release device (RM4 optical smoke switch), BACnet IP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.