  4. VX Series DOAS Microprocessor Controller (DOAS v9.4)

Dedicated outdoor air system (DOAS) unit controller · BACnet points list

Valent VX Series DOAS Microprocessor Controller (DOAS v9.4) BACnet points list

Updated 6 November 2026

Short answer

Valent's DOAS controller (DOAS v9.4) offers BACnet MS/TP, BACnet IP, Modbus RTU and Modbus TCP. The BMS can enable the unit, command occupancy, reset alarms, write temperature, dehumidification, economizer, airflow and static pressure setpoints, take over fans and the outdoor air damper, and replace hardwired sensors with BMS values while a watchdog is kept alive. Read-only objects cover temperatures, humidity, pressures, refrigerant circuit values, outputs, unit status mode, latest alarm and bit-packed status and alarm words.

This page lists 171 BACnet objects for the Valent VX Series DOAS Microprocessor Controller (DOAS v9.4) — 62 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Valent’s own free documentation, linked below.

Manufacturer
Valent
Model
VX Series DOAS Microprocessor Controller (DOAS v9.4)
Equipment
Dedicated outdoor air system (DOAS) unit controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
171 (62 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
DOAS v9.4
Also known as
485937, Document 485937, VX, VXE, VXC, Valent DOAS controller, DOAS v9.4, c.pCO
Source document
Microprocessor Controller for Dedicated Outdoor Air System - Reference Guide (DOAS v9.4) · 485937 · rev. 2024-05
Download CSV 171 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Valent’s current documentation and the live device before use. Not official Valent information. Terms of use.

BMS integration notes: Valent VX Series DOAS Microprocessor Controller (DOAS v9.4)

Integration in brief

With BACnet licensed and the protocol set in Network Settings, enable the unit with BV 2 and command occupancy with BV 3, write the temperature setpoint AV 1 and reset alarms with BV 4. If the BMS sends sensor values or controls fans or the damper, keep the BV 1 watchdog toggling. Monitor Unit_Status_Mode, supply temperature, Global_Alarm and LatestAlm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2System_EnableEnables or disables the unitWrite
BV 3BMS_Occupancy_CommandOccupancy; Active = Unoccupied, Inactive = OccupiedWrite
AV 1Temperature_SetpointOccupied temperature setpointWrite
BV 1BMS_WatchdogHeartbeat when BMS controls fans or sensorsWrite
BV 4Reset_All_AlarmsRemote alarm resetWrite
AV 40Unit_Status_ModeCurrent operating mode codeRead
AI 2Supply_Temp_Analog_InputSupply (discharge) air temperatureRead
BV 23Global_AlarmAny active alarmRead
IV 5LatestAlmMost recent alarm codeRead

Enable & remote start

BV 2 System_Enable enables or disables the unit; BV 3 BMS_Occupancy_Command sets occupancy (Active = Unoccupied). BV 5 and BV 6 command emergency exhaust-only and pressurization-only modes.

Heartbeat & communication loss

BV 1 BMS_Watchdog must be toggled by the BMS within the timeout delay whenever the BMS replaces a hardwired sensor (or takes over fan speed or damper control). If the timer expires, the controller alarms (BMS Offline) and falls back to its hardwired sensors and local control until the BMS returns. The watchdog status is shown on a read-only BV.

Sensors & values from the BMS

Set the matching source-select BV (BV 7-16) to BMS, then write the *_from_BMS analog value (AV 26-35, e.g. AV 27 outside temperature, AV 35 space temperature). Supply fan, exhaust fan and outdoor air damper are taken over the same way with BV 17-19. The watchdog must be kept alive.

Network setup

Watch out for

Valent VX Series DOAS Microprocessor Controller (DOAS v9.4) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

171 of 171 shown
Type
Other
Access
Show
Valent VX Series DOAS Microprocessor Controller (DOAS v9.4) BACnet Points List
DescriptionStates
AI1Space_Temp_Analog_InputSpace Temperature°FRead
AImin2Supply_Temp_Analog_InputSupply Temperature°FRead
AI3Outside_Air_Temp_Analog_InputOutside Air Temperature°FRead
AI4Mixed_Temp_Analog_InputMixed Temperature°FRead
AI5Cold_Coil_1_Temp_Analog_InputCold Coil 1 Temperature°FRead
AI7Return_Temp_Analog_InputReturn Temperature°FRead
AI8Exhaust_Temp_Analog_InputExhaust Temperature°FRead
AI9Space_RH_Analog_InputSpace % Relative Humidity%Read
AI10Outside_RH_Analog_InputOutside % Relative Humidity%Read
AI11Return_RH_Analog_InputReturn % Relative Humidity%Read
AI12Return_Duct_Static_Pressure_Analog_InputReturn Duct Static Pressurein. w.c.Read
AI13Space_Static_Pressure_Analog_InputSpace Static Pressurein. w.c.Read
AI14Supply_Duct_Static_Pressure_Analog_InputSupply Duct Static Pressurein. w.c.Read
AI15Space_CO2_1_Analog_InputSpace 1 CO2 ppmppmRead
AI16Space_CO2_2_Analog_InputSpace 2 CO2 ppmppmRead
AI17Return_CO2_Analog_InputReturn CO2 ppmppmRead
AI18CL_Coil_Spt_TempHeatCool Only - Cooling Coil Setpoint InputRead2-10V = 50-75°F
AI19CL_Supply_Spt_TempHeatCool Only - Supply Setpoint TemperatureRead2-10V = 50-95°F
AI20Circuit_A_Discharge_Temp_Analog_InputCircuit A Discharge Temperature°FRead
AI21Circuit_A_Suction_Temp_Analog_InputCircuit A Suction Temperature°FRead
AI22Circuit_B_Discharge_Temp_Analog_InputCircuit B Discharge Temperature°FRead
AI23Circuit_B_Suction_Temp_Analog_InputCircuit B Suction Temperature°FRead
AI28Circuit_A_Discharge_Pressure_Analog_InputCircuit A Discharge PressurepsigRead
AI29Circuit_A_Suction_Pressure_Analog_InputCircuit A Suction PressurepsigRead
AI30Circuit_B_Discharge_Pressure_Analog_InputCircuit B Discharge PressurepsigRead
AI31Circuit_B_Suction_Pressure_Analog_InputCircuit B Suction PressurepsigRead
AI36Aux_In_Customer_1Customer defined auxiliary input (units selectable)Read
AI37Aux_In_Customer_2Customer defined auxiliary input (units selectable)Read
AI38Aux_In_Customer_3Customer defined auxiliary input (units selectable)Read
AI39Aux_In_Customer_4Customer defined auxiliary input (units selectable)Read
AI40Aux_In_Customer_5Customer defined auxiliary input (units selectable)Read
AI41Aux_In_Customer_6Customer defined auxiliary input (units selectable)Read
AI42Aux_In_Customer_7Customer defined auxiliary input (units selectable)Read
AI43Aux_In_Customer_8Customer defined auxiliary input (units selectable)Read
AI44Aux_In_Customer_9Customer defined auxiliary input (units selectable)Read
AI45Aux_In_Customer_10Customer defined auxiliary input (units selectable)Read
AVmin1Temperature_SetpointTemperature Setpoint used for Supply, Space, or Return temperature control°FWrite
AV2Temperature_Heat_Cool_DeadbandHeat/Cool Spt Deadband for Space or Return ResetΔ°FWrite
AV3Temperature_Setpoint_UnoccupiedTemperature Setpoint used for Supply, Space, or Return temperature control°FWrite
AV4Temperature_Heat_Cool_Deadband_UnoccupiedHeat/Cool Spt Deadband for Space or Return ResetΔ°FWrite
AV5Cooling_Coil_Setpoint_MinCooling Coil Leaving Air Setpoint°FWrite
AV6Cooling_Coil_Setpoint_MaxMaximum Coil Leaving Setpoint°FWrite
AV7Dehumidification_SetpointDehumidification Setpoint %RH%Write
AV8Outside_Dewpoint_SetpointOutside Dewpoint Dehumidification Trigger°FWrite
AV9Indoor_Dewpoint_SetpointIndoor Dewpoint Dehumidification Trigger°FWrite
AV10Unocc_Indoor_Dewpoint_SetpointUnoccupied Indoor Dewpoint Dehumidification Trigger°FWrite
AV11Unoccupied_Dehumidification_SetpointUnoccupied Dehumidification %RH Setpoint%Write
AV12Economizer_Temp_Enable_SetpointEconomizer Ambient Temp Enable Setpoint Allow Econ when OAT< Setpoint°FWrite
AV13Economizer_Enthalpy_Enable_SetpointEconomizer Enthalpy Enable Setpoint Allow Econ when OA Enthalpy<SetpointBtu/lbWrite
AV14Supply_Fan_CFM_SetpointSupply Fan CFM SetpointcfmWrite
AV15Exhaust_Fan_CFM_SetpointExhaust Fan CFM SetpointcfmWrite
AV16OAD_CFM_SetpointOAD CFM SetpointcfmWrite
AV17Cooling_Lockout_SetpointCooling Ambient Lockout Setpoint°FWrite
AV18Heating_Lockout_SetpointHeating Ambient Lockout Setpoint°FWrite
AV19Preheat_Lockout_SetpointPreheat Ambient Lockout Setpoint°FWrite
AV20Economizer_Lockout_SetpointEconomizer Ambient Lockout Setpoint°FWrite
AV21Return_Duct_Static_Pressure_SetpointReturn Duct Static Pressure Setpointin. w.c.Write
AV22Space_Static_Pressure_SetpointSpace Static Pressure Setpointin. w.c.Write
AV23Supply_Duct_Static_Pressure_SetpointSupply Duct Static Pressure Setpointin. w.c.Write
AV24Space_CO2_SetpointSpace CO2 SetpointppmWrite
AV25Outside_Air_Damper_Minimum_Setpoint_OccOutside Air Damper Minimum Setpoint%Write
AV26Outside_RH_from_BMSOutside RH from BMS%Write
AV27Outside_Temp_from_BMSOutside Temp from BMS - source is BMS°FWrite
AV28Return_RH_from_BMSReturn RH from BMS - source is BMS%Write
AV29Return_Temp_from_BMSReturn Temp from BMS - source is BMS°FWrite
AV30Space_1_CO2_from_BMSSpace 1 CO2 from BMS - source is BMSppmWrite
AV31Space_2_CO2_from_BMSSpace 2 CO2 from BMS - source is BMSppmWrite
AV32Return_CO2_from_BMSReturn CO2 from BMS - source is BMSppmWrite
AV33Space_RH_from_BMSSpace RH from BMS - source is BMS%Write
AV34Space_Static_from_BMSSpace Static from BMS - source is BMSin. w.c.Write
AV35Space_Temp_from_BMSSpace Temp from BMS - source is BMS°FWrite
AV36SF_Control_Signal_BMSBMS to control signal for supply fan speed%Write
AV37EF_Control_Signal_BMSBMS to control signal for exhaust fan speed%Write
AV38OAD_Control_Signal_BMSAllows the BMS to control OAD position%Write
AV39Aux_BMS_Analog_Output_1BMS Commanded auxilary analog output (units selectable)Write
AVmin40Unit_Status_ModeUnit Status Mode - See TableRead
AV41Supply_Temperature_Calculated_SetpointActive Supply Temperature Setpoint°FRead
AV42Cooling_1_Ramp_CapacityCooling Ramp 1 Status Value%Read
AV44Defrost_RampDefrost Ramp%Read
AV45Economizer_RampEconomizer Ramp%Read
AV46Head_Pressure_Control_Ramp_1_RampHead Pressure Control Ramp 1%Read
AV47Head_Pressure_Control_Ramp_2_RampHead Pressure Control Ramp 2%Read
AV50HP_Ramp_CapacityHeat Pump Heating Ramp%Read
AV51Heating_CapacityHeating Ramp%Read
AV52Case_Heat_Control_RampCase Heat Ramp%Read
AV53Hot_Gas_Reheat_RampHot Gas Reheat Ramp%Read
AV54Outside_DewpointOutside Dewpoint°FRead
AV55Outside_EnthalpyOutside EnthalpyBtu/lbRead
AV56Return_DewpointReturn Dewpoint°FRead
AV57Return_EnthalpyReturn EnthalpyBtu/lbRead
AV58Space_DewpointSpace Dewpoint°FRead
AV59Space_EnthalpySpace EnthalpyBtu/lbRead
AV60Circuit_A_SuperheatCircuit A Superheat°FRead
AV61Circuit_B_SuperheatCircuit B Superheat°FRead
AV64Total_Exhaust_Fan_CFM_BMSTotal Exhaust Fan CFMcfmRead
AV65Total_Supply_Fan_CFM_BMSTotal Supply Fan CFMcfmRead
AV66OAD_CFM_BMSOAD CFMcfmRead
AV67Active_Temperature_SetpointActive Temperature Setpoint°FRead
AV68Chilled_Water_1_Valve_Analog_OutputChilled Water 1 Valve Analog Output%Read
AV70Electric_Heater_1_Analog_OutputElectric Heater 1 Analog Output%Read
AV72Energy_Recovery_Analog_OutputEnergy Recovery Analog Output%Read
AV73Exhaust_Fan_Speed_Analog_OutputExhaust Fan Speed Analog Output%Read
AV74Hot_Water_Valve_1_Analog_OutputHot Water Valve 1 Analog Output%Read
AV76Mod_Gas_Furnace_1_Analog_OutputMod Gas Furnace 1 Analog Output%Read
AV78Outside_Air_Damper_Analog_OutputOutside Air Damper Analog Output%Read
AV79Supply_Fan_Speed_Analog_OutputSupply Fan Speed Analog Output%Read
AV80Modulating_Compressor_Analog_Output_BMSFirst Modulating Compressor Analog Output - BMS%Read
AV82Circuit_A_Sat_Discharge_TemperatureCircuit A Saturated Discharge Temperature°FRead
AV83Circuit_B_Sat_Discharge_TemperatureCircuit B Saturated Discharge Temperature°FRead
AV86Circuit_A_Sat_Suction_TemperatureCircuit A Saturated Suciton Temperature°FRead
AV87Circuit_B_Sat_Suction_TemperatureCircuit B Saturated Suciton Temperature°FRead
AV90Coil_Temperature_Calculated_SetpointCalculated Coil Leaving Set point°FRead
AV91Active_Cooling_SetpointActive Cooling Setpoint°FRead
AV92Active_Heating_SetpointActive Heating Setpoint°FRead
AV93LatestAlm_AVMost recent alarm - See Alarm TableRead
AV94Device_Enable_DO_Word_Real_1Device Enable DO Word - See TableReadBit-packed word (bit table in the manual)
AV95Device_Enable_DO_Word_Real_2Device Enable DO Word - See TableReadBit-packed word (bit table in the manual)
AV96Ref_Ckt_PressTemp_Alarm_Word_Real_1Refrigeration Circuit Word - See TableReadBit-packed word (bit table in the manual)
AV97Ref_Ckt_PressTemp_Alarm_Word_Real_2Refrigeration Circuit Word - See TableReadBit-packed word (bit table in the manual)
AV98Device_Offline_Word_Real_1Device Offline Word - See TableReadBit-packed word (bit table in the manual)
AV99Device_Offline_Word_Real_2Device Offline Word - See TableReadBit-packed word (bit table in the manual)
AV100Device_Alarm_Word_Real_1Device Alarm Word - See TableReadBit-packed word (bit table in the manual)
AV101Device_Alarm_Word_Real_2Device Alarm Word - See TableReadBit-packed word (bit table in the manual)
AV102System_Word_Real_1System Word - See TableReadBit-packed word (bit table in the manual)
AV103System_Word_Real_2System Word - See TableReadBit-packed word (bit table in the manual)
AV104Unit_Status_Word_Real_1Unit Status Word - See TableReadBit-packed word (bit table in the manual)
AV105Unit_Status_Word_Real_2Unit Status Word - See TableReadBit-packed word (bit table in the manual)
IV1Temperature_Reset_ModeOccupied Reset Type SetpointWrite1-Discharge, 2-Space 3-Return, 4-Outside
IV2Temperature_Reset_Mode_UnoccupiedUnoccupied Reset Type SetpointWrite1-Discharge, 2-Space 3-Return
IV3Active_Temperature_Reset_ModeActive Occupied Reset Type SetpointRead1-Discharge, 2-Space 3-Return, 4-Outside
IV4Active_Temperature_Reset_Mode_UnoccActive Unoccupied Reset Type SetpointRead1-Discharge, 2-Space 3-Return
IVmin5LatestAlmMost recent alarm - See Alarm TableRead
IV6Device_Enable_DO_WordDevice Enable DO Word - See TableReadBit-packed word (bit table in the manual)
IV7Ref_Ckt_PressTemp_Alarm_WordRefrigeration Circuit Word - See TableReadBit-packed word (bit table in the manual)
IV8Device_Offline_WordDevice Offline Word - See TableReadBit-packed word (bit table in the manual)
IV9Device_Alarm_WordDevice Alarm Word - See TableReadBit-packed word (bit table in the manual)
IV10System_WordSystem Word - See TableReadBit-packed word (bit table in the manual)
IV11Unit_Status_WordUnit Status Word - See TableReadBit-packed word (bit table in the manual)
BI1Exhaust_Fan_1_Status_Digital_InputExhaust Fan StatusReadActive=Active, Inactive=Inactive
BI2Supply_Fan_1_Status_Digital_InputSupply Fan StatusReadActive=Active, Inactive=Inactive
BVmin1BMS_WatchdogBMS Watchdog command Used to determine BMS comm statusWriteActive=Active, Inactive=Inactive
BVmin2System_EnableMaster system enable/disable pointWriteActive=Enable, Inactive=Disable
BVmin3BMS_Occupancy_CommandOccupancy CommandWriteActive=Unoccupied, Inactive=Occupied
BVmin4Reset_All_AlarmsAlarm Reset CommandWriteActive=Reset, Inactive=Normal
BV5Exhaust_Only_Mode_BMS_CmdEmergancy Exhaust Mode CommandWriteActive=Enable, Inactive=Disable
BV6Pressurization_Only_Mode_BMS_CmdEmergancy Pressurization Mode CommandWriteActive=Enable, Inactive=Disable
BV7Outside_RH_Source_BMSOutside RH Source SelectionWriteActive=BMS, Inactive=Local
BV8Outside_Temp_Source_BMSOutside Temp Source SelectionWriteActive=BMS, Inactive=Local
BV9Return_RH_Source_BMSReturn RH Source SelectionWriteActive=BMS, Inactive=Local
BV10Return_Temp_Source_BMSReturn Temp Source SelectionWriteActive=BMS, Inactive=Local
BV11Space_1_CO2_Source_BMSSpace 1 CO2 Source SelectionWriteActive=BMS, Inactive=Local
BV12Space_2_CO2_Source_BMSSpace 2 CO2 Source SelectionWriteActive=BMS, Inactive=Local
BV13Return_CO2_Source_BMSReturn CO2 Source SelectionWriteActive=BMS, Inactive=Local
BV14Space_RH_Source_BMSSpace RH Source SelectionWriteActive=BMS, Inactive=Local
BV15Space_Static_Source_BMSSpace Static Source SelectionWriteActive=BMS, Inactive=Local
BV16Space_Temp_Source_BMSSpace Temp Source SelectionWriteActive=BMS, Inactive=Local
BV17SF_Control_Source_BMSAllows the BMS to control supply fan speedWriteActive=BMS, Inactive=Local
BV18EF_Control_Source_BMSAllows the BMS to control exhaust fan speedWriteActive=BMS, Inactive=Local
BV19OAD_Control_Source_BMSAllows the BMS to control OAD positionWriteActive=BMS, Inactive=Local
BV20Aux_BMS_Digital_Output_1BMS Commanded auxilary digital outputWriteActive=Active, Inactive=Inactive
BV21Aux_BMS_Digital_Output_2BMS Commanded auxilary digital outputWriteActive=Active, Inactive=Inactive
BV22OccupiedOccupancyReadActive=Occupied, Inactive=Unoccupied
BVmin23Global_AlarmGeneral alarm point, default set to indicate any alarm is activeReadActive=Alarm, Inactive=Normal
BV24BMS_Watchdog_ActiveStatus of the BMS watchdog heartbeatReadActive=Active, Inactive=Inactive
BV25OAD_Feedback_Error_Not_Economizing.ActiveFeedback indicates OAD is not opening during economizerReadActive=Alarm, Inactive=Normal
BV26OAD_Feedback_Error_Economizing.ActiveFeedback indicates OAD is openReadActive=Alarm, Inactive=Normal
BV27OAD_Feedback_Error_OAD_Not_Modulating.ActiveFeedback indicates the OAD is not modulatingReadActive=Alarm, Inactive=Normal
BV28OAD_Feedback_Error_Excess_OA.ActiveFeedback indicates the OAD is not closingReadActive=Alarm, Inactive=Normal
BV29Supply_Fan_1_Alarm.ActiveSupply Fan Alarm ActiveReadActive=Alarm, Inactive=Normal
BV30Exhaust_Fan_1_Alarm.ActiveExhaust Fan Alarm ActiveReadActive=Alarm, Inactive=Normal
BV31Drain_Pan_Alarm.ActiveCondensate Drain Pan Alarm ActiveReadActive=Alarm, Inactive=Normal
Object ID lookup: Valent VX Series DOAS Microprocessor Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the VX Series DOAS Microprocessor Controller (DOAS v9.4) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Valent VX Series DOAS Microprocessor Controller (DOAS v9.4)

How many BACnet points does the Valent VX Series DOAS Microprocessor Controller (DOAS v9.4) have?

This list has 171 BACnet objects: 36 analog inputs, 91 analog values, 2 binary inputs, 31 binary values, 11 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Valent VX Series DOAS Microprocessor Controller (DOAS v9.4) BACnet points are writable?

62 of the 171 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Valent VX Series DOAS Microprocessor Controller (DOAS v9.4) BACnet documentation?

The source is Microprocessor Controller for Dedicated Outdoor Air System - Reference Guide (DOAS v9.4) (485937), revision 2024-05, published free by Valent at https://content.valentair.com/valent-content-prod/docs/librariesprovider2/default-document-library/valent_vx_series_controller_iom.pdf?sfvrsn=c79e7ad3_19.

What are the minimum BACnet points to integrate the Valent VX Series DOAS Microprocessor Controller (DOAS v9.4)?

Start with BV 2 System_Enable (Enables or disables the unit); BV 3 BMS_Occupancy_Command (Occupancy; Active = Unoccupied, Inactive = Occupied); AV 1 Temperature_Setpoint (Occupied temperature setpoint); BV 1 BMS_Watchdog (Heartbeat when BMS controls fans or sensors); BV 4 Reset_All_Alarms (Remote alarm reset); AV 40 Unit_Status_Mode (Current operating mode code); AI 2 Supply_Temp_Analog_Input (Supply (discharge) air temperature); BV 23 Global_Alarm (Any active alarm); IV 5 LatestAlm (Most recent alarm code).

How do I enable BMS control of the Valent VX Series DOAS Microprocessor Controller (DOAS v9.4)?

BV 2 System_Enable enables or disables the unit; BV 3 BMS_Occupancy_Command sets occupancy (Active = Unoccupied). BV 5 and BV 6 command emergency exhaust-only and pressurization-only modes.

Does the Valent VX Series DOAS Microprocessor Controller (DOAS v9.4) need a BACnet heartbeat or have a communication timeout?

BV 1 BMS_Watchdog must be toggled by the BMS within the timeout delay whenever the BMS replaces a hardwired sensor (or takes over fan speed or damper control). If the timer expires, the controller alarms (BMS Offline) and falls back to its hardwired sensors and local control until the BMS returns. The watchdog status is shown on a read-only BV.

Can the BMS supply sensor values to the Valent VX Series DOAS Microprocessor Controller (DOAS v9.4)?

Set the matching source-select BV (BV 7-16) to BMS, then write the *_from_BMS analog value (AV 26-35, e.g. AV 27 outside temperature, AV 35 space temperature). Supply fan, exhaust fan and outdoor air damper are taken over the same way with BV 17-19. The watchdog must be kept alive.

How do I check these points on the real VX Series DOAS Microprocessor Controller (DOAS v9.4)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Valent BACnet points lists

Source: Microprocessor Controller for Dedicated Outdoor Air System - Reference Guide (DOAS v9.4) · 485937 · rev. 2024-05. Object names, instances and units are reproduced as published; descriptions are our own.