Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) BACnet points list

Updated 7 November 2026

Short answer

This is the full Appendix E points list of the IVE microprocessor controller (program IVE v1.3). It adds detailed alarm, status and configuration objects to the shorter BACnet integration guide subset. Objects marked as the BACnet short list are flagged in the descriptions; the controller talks BACnet MS/TP or BACnet IP once BACnet is licensed.

This page lists 152 BACnet objects for the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) — 66 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Valent’s own free documentation, linked below.

Manufacturer
Valent
Model
IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)
Equipment
Energy recovery ventilator controller
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
152 (66 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
IVE v1.3 (version date 5/26)
Also known as
IVE, IVE v1.3, 487416, Valent IVE, Greenheck IVE
Source document
Microprocessor Controller for IVE - Reference Guide, Appendix E: Points List · 487416 Rev. 2 · rev. 2026-05
Download CSV 152 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Valent’s current documentation and the live device before use. Not official Valent information. Terms of use.

BMS integration notes: Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)

Integration in brief

Enable the unit with BV 2 and command occupancy with BV 3, and write the temperature setpoint AV 1 if needed. Watch BV 23 Global Alarm and IV 5 LatestAlm. If the BMS replaces hardwired sensors or drives fans, it must toggle BV 1 BMS Watchdog within the timeout delay.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2System_EnableEnables or disables the unitWrite
BV 3BMS_Occupancy_CommandOccupancy; Active = Unoccupied, Inactive = OccupiedWrite
AV 1Temperature_SetpointOccupied temperature setpointWrite
BV 1BMS_WatchdogHeartbeat when BMS controls fans or sensorsWrite
BV 4Reset_All_AlarmsRemote alarm resetWrite
AV 40Unit_Status_ModeCurrent operating mode codeRead
AI 2Supply_Temp_Analog_InputSupply (discharge) air temperatureRead
BV 23Global_AlarmAny active alarmRead
IV 5LatestAlmMost recent alarm codeRead

Enable & remote start

BV 2 System_Enable enables or disables the unit from the BMS; BV 3 BMS_Occupancy_Command sets occupancy (Active = Unoccupied).

Heartbeat & communication loss

BV 1 BMS_Watchdog is required when the BMS takes the place of a hardwired sensor: the BMS toggles it between true and false within the timeout delay. If the timer expires the controller falls back to hardwired sensors and raises the BMS watchdog alarm (alarm 79). BV 24 shows the watchdog status.

Sensors & values from the BMS

Set the sensor source-select binary (BV 7-16, e.g. BV 8 Outside_Temp_Source_BMS) to BMS, then write the matching *_from_BMS analog value (e.g. AV 27 Outside_Temp_from_BMS). Fan speed, energy recovery and economizer control can be handed to the BMS with BV 17, BV 18, BV 35 and BV 36.

Network setup

Watch out for

Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

152 of 152 shown
Type
Other
Access
Show
Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) BACnet Points List
DescriptionStates
AI1Space_Temp_Analog_InputSpace Temperature [BACnet short list]°FRead
AImin2Supply_Temp_Analog_InputSupply Temperature [BACnet short list]°FRead
AI3Outside_Air_Temp_Analog_InputOutside Air Temperature [BACnet short list]°FRead
AI4Mixed_Temp_Analog_InputMixed Temperature°FRead
AI5Cold_Coil_1_Temp_Analog_InputCold Coil 1 Temperature°FRead
AI7Return_Temp_Analog_InputReturn Temperature [BACnet short list]°FRead
AI8Exhaust_Temp_Analog_InputExhaust Temperature [BACnet short list]°FRead
AI9Space_RH_Analog_InputSpace % Relative Humidity [BACnet short list]%Read
AI10Outside_RH_Analog_InputOutside % Relative Humidity [BACnet short list]%Read
AI11Return_RH_Analog_InputReturn % Relative Humidity [BACnet short list]%Read
AI12Return_Duct_Static_Pressure_Analog_InputReturn Duct Static Pressure [BACnet short list]inH2ORead
AI13Space_Static_Pressure_Analog_InputSpace Static Pressure [BACnet short list]inH2ORead
AI14Supply_Duct_Static_Pressure_Analog_InputSupply Duct Static Pressure [BACnet short list]inH2ORead
AI15Space_CO2_1_Analog_InputSpace 1 CO2 ppm [BACnet short list]ppmRead
AI16Space_CO2_2_Analog_InputSpace 2 CO2 ppm [BACnet short list]ppmRead
AI17Return_CO2_Analog_InputReturn CO2 ppm [BACnet short list]ppmRead
AI36Aux_In_Customer_1Customer defined auxiliary input [BACnet short list]Read
AI37Aux_In_Customer_2Customer defined auxiliary input [BACnet short list]Read
AI38Aux_In_Customer_3Customer defined auxiliary input [BACnet short list]Read
AI39Aux_In_Customer_4Customer defined auxiliary input [BACnet short list]Read
AI40Aux_In_Customer_5Customer defined auxiliary input [BACnet short list]Read
AI41Aux_In_Customer_6Customer defined auxiliary input [BACnet short list]Read
AI42Aux_In_Customer_7Customer defined auxiliary input [BACnet short list]Read
AI43Aux_In_Customer_8Customer defined auxiliary input [BACnet short list]Read
AI44Aux_In_Customer_9Customer defined auxiliary input [BACnet short list]Read
AI45Aux_In_Customer_10Customer defined auxiliary input [BACnet short list]Read
AVmin1Temperature_SetpointTemperature Setpoint used for Supply, Space, or Return temperature control [BACnet short list]°FWrite
AV2Temperature_Heat_Cool_DeadbandHeat/Cool Spt Deadband for Space or Return Reset [BACnet short list]Δ°FWrite
AV3Temperature_Setpoint_UnoccupiedTemperature Setpoint used for Supply, Space, or Return temperature control [BACnet short list]°FWrite
AV4Temperature_Heat_Cool_Deadband_UnoccupiedHeat/Cool Spt Deadband for Space or Return Reset [BACnet short list]Δ°FWrite
AV5Cooling_Coil_Setpoint_MinCooling Coil Leaving Air Setpoint°FWrite
AV6Cooling_Coil_Setpoint_MaxMaximum Coil Leaving Setpoint°FWrite
AV7Dehumidification_SetpointDehumidification Setpoint %RH%Write
AV8Outside_Dewpoint_SetpointOutside Dewpoint Dehumidification Trigger [BACnet short list]°FWrite
AV9Indoor_Dewpoint_SetpointIndoor Dewpoint Dehumidification Trigger [BACnet short list]°FWrite
AV10Unocc_Indoor_Dewpoint_SetpointUnoccupied Indoor Dewpoint Dehumidification°FWrite
AV11Unoccupied_Dehumidification_SetpointUnoccupied Dehumidification %RH Setpoint%Write
AV12Economizer_Temp_Enable_SetpointEconomizer Ambient Temp Enable Setpoint Allow Econ when OAT< Setpoint [BACnet short list]°FWrite
AV13Economizer_Enthalpy_Enable_SetpointEconomizer Enthalpy Enable Setpoint Allow Econ when OA Enthalpy<Setpoint [BACnet short list]BTU/lbWrite
AV14Supply_Fan_CFM_SetpointSupply Fan CFM SetpointCFMWrite
AV15Exhaust_Fan_CFM_SetpointExhaust Fan CFM SetpointCFMWrite
AV16OAD_CFM_SetpointOAD CFM SetpointCFMWrite
AV17Cooling_Lockout_SetpointCooling Ambient Lockout Setpoint [BACnet short list]°FWrite
AV18Heating_Lockout_SetpointHeating Ambient Lockout Setpoint [BACnet short list]°FWrite
AV19Preheat_Lockout_SetpointPreheat Ambient Lockout Setpoint [BACnet short list]°FWrite
AV20Economizer_Lockout_SetpointEconomizer Ambient Lockout Setpoint [BACnet short list]°FWrite
AV21Return_Duct_Static_Pressure_SetpointReturn Duct Static Pressure Setpoint [BACnet short list]inH2OWrite
AV22Space_Static_Pressure_SetpointSpace Static Pressure Setpoint [BACnet short list]inH2OWrite
AV23Supply_Duct_Static_Pressure_SetpointSupply Duct Static Pressure Setpoint [BACnet short list]inH2OWrite
AV24Space_CO2_SetpointSpace CO2 Setpoint [BACnet short list]ppmWrite
AV25Outside_Air_Damper_Minimum_Setpoint_OccOutside Air Damper Minimum Setpoint%Write
AV26Outside_RH_from_BMSOutside RH from BMS - source is BMS [BACnet short list]%Write
AV27Outside_Temp_from_BMSOutside Temp from BMS - source is BMS [BACnet short list]°FWrite
AV28Return_RH_from_BMSReturn RH from BMS - source is BMS [BACnet short list]%Write
AV29Return_Temp_from_BMSReturn Temp from BMS - source is BMS [BACnet short list]°FWrite
AV30Space_1_CO2_from_BMSSpace 1 CO2 from BMS - source is BMS [BACnet short list]ppmWrite
AV31Space_2_CO2_from_BMSSpace 2 CO2 from BMS - source is BMS [BACnet short list]ppmWrite
AV32Return_CO2_from_BMSReturn CO2 from BMS - source is BMS [BACnet short list]ppmWrite
AV33Space_RH_from_BMSSpace RH from BMS - source is BMS [BACnet short list]%Write
AV34Space_Static_from_BMSSpace Static from BMS - source is BMS [BACnet short list]inH2OWrite
AV35Space_Temp_from_BMSSpace Temp from BMS - source is BMS [BACnet short list]°FWrite
AV36SF_Control_Signal_BMSBMS to control signal for supply fan speed [BACnet short list]%Write
AV37EF_Control_Signal_BMSBMS to control signal for exhaust fan speed [BACnet short list]%Write
AV38OAD_Control_Signal_BMSAllows the BMS to control OAD position%Write
AV39Aux_BMS_Analog_Output_1BMS Commanded auxiliary analog output [BACnet short list]Write
AVmin40Unit_Status_ModeUnit Status Mode - See Table [BACnet short list]Read
AV41Supply_Temperature_Calculated_SetpointActive Supply Temperature Setpoint [BACnet short list]°FRead
AV42Cooling_1_Ramp_CapacityCooling Ramp 1 Status Value%Read
AV44Defrost_RampDefrost Ramp [BACnet short list]%Read
AV45Economizer_RampEconomizer Ramp [BACnet short list]%Read
AV46Head_Pressure_Control_Ramp_1_RampHead Pressure Control Ramp 1%Read
AV47Head_Pressure_Control_Ramp_2_RampHead Pressure Control Ramp 2%Read
AV50HP_Ramp_CapacityHeat Pump Heating Ramp%Read
AV51Heating_CapacityHeating Ramp [BACnet short list]%Read
AV52Case_Heat_Control_RampCase Heat Ramp%Read
AV53Hot_Gas_Reheat_RampHot Gas Reheat Ramp%Read
AV54Outside_DewpointOutside Dewpoint [BACnet short list]°FRead
AV55Outside_EnthalpyOutside Enthalpy [BACnet short list]BTU/lbRead
AV56Return_DewpointReturn Dewpoint [BACnet short list]°FRead
AV57Return_EnthalpyReturn Enthalpy [BACnet short list]BTU/lbRead
AV58Space_DewpointSpace Dewpoint [BACnet short list]°FRead
AV59Space_EnthalpySpace Enthalpy [BACnet short list]BTU/lbRead
AV64Total_Exhaust_Fan_CFM_BMSTotal Exhaust Fan CFM [BACnet short list]CFMRead
AV65Total_Supply_Fan_CFM_BMSTotal Supply Fan CFM [BACnet short list]CFMRead
AV66OAD_CFM_BMSOAD CFM [BACnet short list]CFMRead
AV67Active_Temperature_SetpointActive Temperature Setpoint [BACnet short list]°FRead
AV68Chilled_Water_1_Valve_Analog_OutputChilled Water 1 Valve Analog Output [BACnet short list]%Read
AV70Electric_Heater_1_Analog_OutputElectric Heater 1 Analog Output [BACnet short list]%Read
AV72Energy_Recovery_Analog_OutputEnergy Recovery Analog Output [BACnet short list]%Read
AV73Exhaust_Fan_Speed_Analog_OutputExhaust Fan Speed Analog Output [BACnet short list]%Read
AV74Hot_Water_Valve_1_Analog_OutputHot Water Valve 1 Analog Output [BACnet short list]%Read
AV78Outside_Air_Damper_Analog_OutputOutside Air Damper Analog Output%Read
AV79Supply_Fan_Speed_Analog_OutputSupply Fan Speed Analog Output [BACnet short list]%Read
AV90Coil_Temperature_Calculated_SetpointCalculated Coil Leaving Set point°FRead
AV91Active_Cooling_SetpointActive Cooling Setpoint [BACnet short list]°FRead
AV92Active_Heating_SetpointActive Heating Setpoint [BACnet short list]°FRead
AV93LatestAlm_RealMost recent alarm - See Alarm Table [BACnet short list]Read
AV94Device_Enable_DO_Word_Real_1Device Enable DO Word - See Table [BACnet short list] (bit-packed)Read
AV95Device_Enable_DO_Word_Real_2Device Enable DO Word - See Table [BACnet short list] (bit-packed)Read
AV98Device_Offline_Word_Real_1Device Offline Word - See Table [BACnet short list] (bit-packed)Read
AV99Device_Offline_Word_Real_2Device Offline Word - See Table [BACnet short list] (bit-packed)Read
AV100Device_Alarm_Word_Real_1Device Alarm Word - See Table [BACnet short list] (bit-packed)Read
AV101Device_Alarm_Word_Real_2Device Alarm Word - See Table [BACnet short list] (bit-packed)Read
AV102System_Word_Real_1System Word - See Table [BACnet short list] (bit-packed)Read
AV103System_Word_Real_2System Word - See Table [BACnet short list] (bit-packed)Read
AV104Unit_Status_Word_Real_1Unit Status Word - See Table [BACnet short list] (bit-packed)Read
AV105Unit_Status_Word_Real_2Unit Status Word - See Table [BACnet short list] (bit-packed)Read
AV106ER_Control_Signal_BMSBMS to control signal for Energy Recovery. [BACnet short list]%Write
AV107Heating_RampHeating Ramp [BACnet short list]%Read
AV108Cooling_1_RampCooling 1 Ramp [BACnet short list]%Read
BI1Exhaust_Fan_1_Status_Digital_InputExhaust Fan Status [BACnet short list]Read0=Inactive, 1=Active
BI2Supply_Fan_1_Status_Digital_InputSupply Fan Status [BACnet short list]Read0=Inactive, 1=Active
BVmin1BMS_WatchdogBMS Watchdog command Used to determine BMS comm status [BACnet short list]Write0=Inactive, 1=Active
BVmin2System_EnableMaster system enable/disable point [BACnet short list]Write0=Disable, 1=Enable
BVmin3BMS_Occupancy_CommandOccupancy Command [BACnet short list]Write0=Occupied, 1=Unoccupied
BVmin4Reset_All_AlarmsAlarm Reset Command [BACnet short list]Write0=Normal, 1=Reset
BV5Exhaust_Only_Mode_BMS_CmdExhaust Mode Command [BACnet short list]Write0=Disable, 1=Enable
BV6Pressurization_Only_Mode_BMS_CmdPressurization Mode CommandWrite0=Disable, 1=Enable
BV7Outside_RH_Source_BMSOutside RH Source Selection [BACnet short list]Write0=Local, 1=BMS
BV8Outside_Temp_Source_BMSOutside Temp Source Selection [BACnet short list]Write0=Local, 1=BMS
BV9Return_RH_Source_BMSReturn RH Source Selection [BACnet short list]Write0=Local, 1=BMS
BV10Return_Temp_Source_BMSReturn Temp Source Selection [BACnet short list]Write0=Local, 1=BMS
BV11Space_1_CO2_Source_BMSSpace 1 CO2 Source Selection [BACnet short list]Write0=Local, 1=BMS
BV12Space_2_CO2_Source_BMSSpace 2 CO2 Source Selection [BACnet short list]Write0=Local, 1=BMS
BV13Return_CO2_Source_BMSReturn CO2 Source Selection [BACnet short list]Write0=Local, 1=BMS
BV14Space_RH_Source_BMSSpace RH Source Selection [BACnet short list]Write0=Local, 1=BMS
BV15Space_Static_Source_BMSSpace Static Source Selection [BACnet short list]Write0=Local, 1=BMS
BV16Space_Temp_Source_BMSSpace Temp Source Selection [BACnet short list]Write0=Local, 1=BMS
BV17SF_Control_Source_BMSAllows the BMS to control supply fan speed [BACnet short list]Write0=Local, 1=BMS
BV18EF_Control_Source_BMSAllows the BMS to control exhaust fan speed [BACnet short list]Write0=Local, 1=BMS
BV19OAD_Control_Source_BMSAllows the BMS to control OAD positionWrite0=Local, 1=BMS
BV20Aux_BMS_Digital_Output_1BMS Commanded auxiliary digital output [BACnet short list]Write0=Inactive, 1=Active
BV21Aux_BMS_Digital_Output_2BMS Commanded auxiliary digital output [BACnet short list]Write0=Inactive, 1=Active
BV22OccupiedOccupancy [BACnet short list]Read0=Unoccupied, 1=Occupied
BVmin23Global_AlarmGeneral alarm point Default set to indicate any alarm is active [BACnet short list]Read0=Normal, 1=Alarm
BV24BMS_Watchdog_ActiveStatus of the BMS watchdog heartbeat [BACnet short list]Read0=Inactive, 1=Active
BV29Supply_Fan_1_Alarm.ActiveSupply Fan Alarm Active [BACnet short list]Read0=Normal, 1=Alarm
BV30Exhaust_Fan_1_Alarm.ActiveExhaust Fan Alarm Active [BACnet short list]Read0=Normal, 1=Alarm
BV31Drain_Pan_Alarm.ActiveCondensate Drain Pan Alarm ActiveRead0=Normal, 1=Alarm
BV32Fire_Safety_Shutdown_Alarm.ActiveFire Safety Shutdown Alarm ActiveRead0=Normal, 1=Alarm
BV35ER_Control_Source_BMSAllows the BMS to control energy recovery. [BACnet short list]Write0=Local, 1=BMS
BV36Econ_Enable_Source_BMSAllows the BMS to control ERV call for cooling. [BACnet short list]Write0=Local, 1=BMS
BV37Econ_Enable_from_BMSEnable ERV call for cooling. [BACnet short list]Write0=Disable, 1=Enable
IV1Temperature_Reset_ModeOccupied Reset Type Setpoint [BACnet short list]Write1=Discharge, 2=Space, 3=Return, 4=Outside
IV2Temperature_Reset_Mode_UnoccupiedUnoccupied Reset Type Setpoint [BACnet short list]Write1=Discharge, 2=Space, 3=Return
IV3Active_Temperature_Reset_ModeActive Occupied Reset Type Setpoint [BACnet short list]Read1=Discharge, 2=Space, 3=Return, 4=Outside
IVmin5LatestAlmMost recent alarm - See Alarm Table [BACnet short list]Read
IV6Device_Enable_DO_WordDevice Enable DO Word - See Table [BACnet short list] (bit-packed)Read
IV8Device_Offline_WordDevice Offline Word - See Table [BACnet short list] (bit-packed)Read
IV9Device_Alarm_WordDevice Alarm Word - See Table [BACnet short list] (bit-packed)Read
IV10System_WordSystem Word - See Table [BACnet short list] (bit-packed)Read
IV11Unit_Status_WordUnit Status Word - See Table [BACnet short list] (bit-packed)Read
Object ID lookup: Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)

How many BACnet points does the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) have?

This list has 152 BACnet objects: 26 analog inputs, 84 analog values, 2 binary inputs, 31 binary values, 9 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) BACnet points are writable?

66 of the 152 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) BACnet documentation?

The source is Microprocessor Controller for IVE - Reference Guide, Appendix E: Points List (487416 Rev. 2), revision 2026-05, published free by Valent at https://content.greenheck.com/public/DAMProd/Original/10025/487416-ive-microprocessor-controller-r2-may-2026_val.pdf.

What are the minimum BACnet points to integrate the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)?

Start with BV 2 System_Enable (Enables or disables the unit); BV 3 BMS_Occupancy_Command (Occupancy; Active = Unoccupied, Inactive = Occupied); AV 1 Temperature_Setpoint (Occupied temperature setpoint); BV 1 BMS_Watchdog (Heartbeat when BMS controls fans or sensors); BV 4 Reset_All_Alarms (Remote alarm reset); AV 40 Unit_Status_Mode (Current operating mode code); AI 2 Supply_Temp_Analog_Input (Supply (discharge) air temperature); BV 23 Global_Alarm (Any active alarm); IV 5 LatestAlm (Most recent alarm code).

How do I enable BMS control of the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)?

BV 2 System_Enable enables or disables the unit from the BMS; BV 3 BMS_Occupancy_Command sets occupancy (Active = Unoccupied).

Does the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) need a BACnet heartbeat or have a communication timeout?

BV 1 BMS_Watchdog is required when the BMS takes the place of a hardwired sensor: the BMS toggles it between true and false within the timeout delay. If the timer expires the controller falls back to hardwired sensors and raises the BMS watchdog alarm (alarm 79). BV 24 shows the watchdog status.

Can the BMS supply sensor values to the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)?

Set the sensor source-select binary (BV 7-16, e.g. BV 8 Outside_Temp_Source_BMS) to BMS, then write the matching *_from_BMS analog value (e.g. AV 27 Outside_Temp_from_BMS). Fan speed, energy recovery and economizer control can be handed to the BMS with BV 17, BV 18, BV 35 and BV 36.

How do I check these points on the real IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Valent BACnet points lists

Source: Microprocessor Controller for IVE - Reference Guide, Appendix E: Points List · 487416 Rev. 2 · rev. 2026-05. Object names, instances and units are reproduced as published; descriptions are our own.