- IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)
Energy recovery ventilator controller · BACnet points list
Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) BACnet points list
Updated 7 November 2026
This is the full Appendix E points list of the IVE microprocessor controller (program IVE v1.3). It adds detailed alarm, status and configuration objects to the shorter BACnet integration guide subset. Objects marked as the BACnet short list are flagged in the descriptions; the controller talks BACnet MS/TP or BACnet IP once BACnet is licensed.
This page lists 152 BACnet objects for the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) — 66 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Valent’s own free documentation, linked below.
- Manufacturer
- Valent
- Model
- IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)
- Equipment
- Energy recovery ventilator controller
- Equipment type
- Rooftop units, AHUs & DOAS
- BACnet objects
- 152 (66 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- IVE v1.3 (version date 5/26)
- Also known as
- IVE, IVE v1.3, 487416, Valent IVE, Greenheck IVE
Reference only, provided as-is: verify against Valent’s current documentation and the live device before use. Not official Valent information. Terms of use.
BMS integration notes: Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)
Enable the unit with BV 2 and command occupancy with BV 3, and write the temperature setpoint AV 1 if needed. Watch BV 23 Global Alarm and IV 5 LatestAlm. If the BMS replaces hardwired sensors or drives fans, it must toggle BV 1 BMS Watchdog within the timeout delay.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2 | System_Enable | Enables or disables the unit | Write |
| BV 3 | BMS_Occupancy_Command | Occupancy; Active = Unoccupied, Inactive = Occupied | Write |
| AV 1 | Temperature_Setpoint | Occupied temperature setpoint | Write |
| BV 1 | BMS_Watchdog | Heartbeat when BMS controls fans or sensors | Write |
| BV 4 | Reset_All_Alarms | Remote alarm reset | Write |
| AV 40 | Unit_Status_Mode | Current operating mode code | Read |
| AI 2 | Supply_Temp_Analog_Input | Supply (discharge) air temperature | Read |
| BV 23 | Global_Alarm | Any active alarm | Read |
| IV 5 | LatestAlm | Most recent alarm code | Read |
Enable & remote start
BV 2 System_Enable enables or disables the unit from the BMS; BV 3 BMS_Occupancy_Command sets occupancy (Active = Unoccupied).
Heartbeat & communication loss
BV 1 BMS_Watchdog is required when the BMS takes the place of a hardwired sensor: the BMS toggles it between true and false within the timeout delay. If the timer expires the controller falls back to hardwired sensors and raises the BMS watchdog alarm (alarm 79). BV 24 shows the watchdog status.
Sensors & values from the BMS
Set the sensor source-select binary (BV 7-16, e.g. BV 8 Outside_Temp_Source_BMS) to BMS, then write the matching *_from_BMS analog value (e.g. AV 27 Outside_Temp_from_BMS). Fan speed, energy recovery and economizer control can be handed to the BMS with BV 17, BV 18, BV 35 and BV 36.
Network setup
- BACnet must be licensed on the controller; alarm 82 means the BACnet license is not installed.
- BACnet MS/TP or BACnet IP is selected and configured from the controller network settings screens.
Watch out for
- Status words are packed integers (IV objects); see the manual tables to decode them.
Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Space_Temp_Analog_Input | Space Temperature [BACnet short list] | °F | Read | |
| AImin | 2 | Supply_Temp_Analog_Input | Supply Temperature [BACnet short list] | °F | Read | |
| AI | 3 | Outside_Air_Temp_Analog_Input | Outside Air Temperature [BACnet short list] | °F | Read | |
| AI | 4 | Mixed_Temp_Analog_Input | Mixed Temperature | °F | Read | |
| AI | 5 | Cold_Coil_1_Temp_Analog_Input | Cold Coil 1 Temperature | °F | Read | |
| AI | 7 | Return_Temp_Analog_Input | Return Temperature [BACnet short list] | °F | Read | |
| AI | 8 | Exhaust_Temp_Analog_Input | Exhaust Temperature [BACnet short list] | °F | Read | |
| AI | 9 | Space_RH_Analog_Input | Space % Relative Humidity [BACnet short list] | % | Read | |
| AI | 10 | Outside_RH_Analog_Input | Outside % Relative Humidity [BACnet short list] | % | Read | |
| AI | 11 | Return_RH_Analog_Input | Return % Relative Humidity [BACnet short list] | % | Read | |
| AI | 12 | Return_Duct_Static_Pressure_Analog_Input | Return Duct Static Pressure [BACnet short list] | inH2O | Read | |
| AI | 13 | Space_Static_Pressure_Analog_Input | Space Static Pressure [BACnet short list] | inH2O | Read | |
| AI | 14 | Supply_Duct_Static_Pressure_Analog_Input | Supply Duct Static Pressure [BACnet short list] | inH2O | Read | |
| AI | 15 | Space_CO2_1_Analog_Input | Space 1 CO2 ppm [BACnet short list] | ppm | Read | |
| AI | 16 | Space_CO2_2_Analog_Input | Space 2 CO2 ppm [BACnet short list] | ppm | Read | |
| AI | 17 | Return_CO2_Analog_Input | Return CO2 ppm [BACnet short list] | ppm | Read | |
| AI | 36 | Aux_In_Customer_1 | Customer defined auxiliary input [BACnet short list] | Read | ||
| AI | 37 | Aux_In_Customer_2 | Customer defined auxiliary input [BACnet short list] | Read | ||
| AI | 38 | Aux_In_Customer_3 | Customer defined auxiliary input [BACnet short list] | Read | ||
| AI | 39 | Aux_In_Customer_4 | Customer defined auxiliary input [BACnet short list] | Read | ||
| AI | 40 | Aux_In_Customer_5 | Customer defined auxiliary input [BACnet short list] | Read | ||
| AI | 41 | Aux_In_Customer_6 | Customer defined auxiliary input [BACnet short list] | Read | ||
| AI | 42 | Aux_In_Customer_7 | Customer defined auxiliary input [BACnet short list] | Read | ||
| AI | 43 | Aux_In_Customer_8 | Customer defined auxiliary input [BACnet short list] | Read | ||
| AI | 44 | Aux_In_Customer_9 | Customer defined auxiliary input [BACnet short list] | Read | ||
| AI | 45 | Aux_In_Customer_10 | Customer defined auxiliary input [BACnet short list] | Read | ||
| AVmin | 1 | Temperature_Setpoint | Temperature Setpoint used for Supply, Space, or Return temperature control [BACnet short list] | °F | Write | |
| AV | 2 | Temperature_Heat_Cool_Deadband | Heat/Cool Spt Deadband for Space or Return Reset [BACnet short list] | Δ°F | Write | |
| AV | 3 | Temperature_Setpoint_Unoccupied | Temperature Setpoint used for Supply, Space, or Return temperature control [BACnet short list] | °F | Write | |
| AV | 4 | Temperature_Heat_Cool_Deadband_Unoccupied | Heat/Cool Spt Deadband for Space or Return Reset [BACnet short list] | Δ°F | Write | |
| AV | 5 | Cooling_Coil_Setpoint_Min | Cooling Coil Leaving Air Setpoint | °F | Write | |
| AV | 6 | Cooling_Coil_Setpoint_Max | Maximum Coil Leaving Setpoint | °F | Write | |
| AV | 7 | Dehumidification_Setpoint | Dehumidification Setpoint %RH | % | Write | |
| AV | 8 | Outside_Dewpoint_Setpoint | Outside Dewpoint Dehumidification Trigger [BACnet short list] | °F | Write | |
| AV | 9 | Indoor_Dewpoint_Setpoint | Indoor Dewpoint Dehumidification Trigger [BACnet short list] | °F | Write | |
| AV | 10 | Unocc_Indoor_Dewpoint_Setpoint | Unoccupied Indoor Dewpoint Dehumidification | °F | Write | |
| AV | 11 | Unoccupied_Dehumidification_Setpoint | Unoccupied Dehumidification %RH Setpoint | % | Write | |
| AV | 12 | Economizer_Temp_Enable_Setpoint | Economizer Ambient Temp Enable Setpoint Allow Econ when OAT< Setpoint [BACnet short list] | °F | Write | |
| AV | 13 | Economizer_Enthalpy_Enable_Setpoint | Economizer Enthalpy Enable Setpoint Allow Econ when OA Enthalpy<Setpoint [BACnet short list] | BTU/lb | Write | |
| AV | 14 | Supply_Fan_CFM_Setpoint | Supply Fan CFM Setpoint | CFM | Write | |
| AV | 15 | Exhaust_Fan_CFM_Setpoint | Exhaust Fan CFM Setpoint | CFM | Write | |
| AV | 16 | OAD_CFM_Setpoint | OAD CFM Setpoint | CFM | Write | |
| AV | 17 | Cooling_Lockout_Setpoint | Cooling Ambient Lockout Setpoint [BACnet short list] | °F | Write | |
| AV | 18 | Heating_Lockout_Setpoint | Heating Ambient Lockout Setpoint [BACnet short list] | °F | Write | |
| AV | 19 | Preheat_Lockout_Setpoint | Preheat Ambient Lockout Setpoint [BACnet short list] | °F | Write | |
| AV | 20 | Economizer_Lockout_Setpoint | Economizer Ambient Lockout Setpoint [BACnet short list] | °F | Write | |
| AV | 21 | Return_Duct_Static_Pressure_Setpoint | Return Duct Static Pressure Setpoint [BACnet short list] | inH2O | Write | |
| AV | 22 | Space_Static_Pressure_Setpoint | Space Static Pressure Setpoint [BACnet short list] | inH2O | Write | |
| AV | 23 | Supply_Duct_Static_Pressure_Setpoint | Supply Duct Static Pressure Setpoint [BACnet short list] | inH2O | Write | |
| AV | 24 | Space_CO2_Setpoint | Space CO2 Setpoint [BACnet short list] | ppm | Write | |
| AV | 25 | Outside_Air_Damper_Minimum_Setpoint_Occ | Outside Air Damper Minimum Setpoint | % | Write | |
| AV | 26 | Outside_RH_from_BMS | Outside RH from BMS - source is BMS [BACnet short list] | % | Write | |
| AV | 27 | Outside_Temp_from_BMS | Outside Temp from BMS - source is BMS [BACnet short list] | °F | Write | |
| AV | 28 | Return_RH_from_BMS | Return RH from BMS - source is BMS [BACnet short list] | % | Write | |
| AV | 29 | Return_Temp_from_BMS | Return Temp from BMS - source is BMS [BACnet short list] | °F | Write | |
| AV | 30 | Space_1_CO2_from_BMS | Space 1 CO2 from BMS - source is BMS [BACnet short list] | ppm | Write | |
| AV | 31 | Space_2_CO2_from_BMS | Space 2 CO2 from BMS - source is BMS [BACnet short list] | ppm | Write | |
| AV | 32 | Return_CO2_from_BMS | Return CO2 from BMS - source is BMS [BACnet short list] | ppm | Write | |
| AV | 33 | Space_RH_from_BMS | Space RH from BMS - source is BMS [BACnet short list] | % | Write | |
| AV | 34 | Space_Static_from_BMS | Space Static from BMS - source is BMS [BACnet short list] | inH2O | Write | |
| AV | 35 | Space_Temp_from_BMS | Space Temp from BMS - source is BMS [BACnet short list] | °F | Write | |
| AV | 36 | SF_Control_Signal_BMS | BMS to control signal for supply fan speed [BACnet short list] | % | Write | |
| AV | 37 | EF_Control_Signal_BMS | BMS to control signal for exhaust fan speed [BACnet short list] | % | Write | |
| AV | 38 | OAD_Control_Signal_BMS | Allows the BMS to control OAD position | % | Write | |
| AV | 39 | Aux_BMS_Analog_Output_1 | BMS Commanded auxiliary analog output [BACnet short list] | Write | ||
| AVmin | 40 | Unit_Status_Mode | Unit Status Mode - See Table [BACnet short list] | Read | ||
| AV | 41 | Supply_Temperature_Calculated_Setpoint | Active Supply Temperature Setpoint [BACnet short list] | °F | Read | |
| AV | 42 | Cooling_1_Ramp_Capacity | Cooling Ramp 1 Status Value | % | Read | |
| AV | 44 | Defrost_Ramp | Defrost Ramp [BACnet short list] | % | Read | |
| AV | 45 | Economizer_Ramp | Economizer Ramp [BACnet short list] | % | Read | |
| AV | 46 | Head_Pressure_Control_Ramp_1_Ramp | Head Pressure Control Ramp 1 | % | Read | |
| AV | 47 | Head_Pressure_Control_Ramp_2_Ramp | Head Pressure Control Ramp 2 | % | Read | |
| AV | 50 | HP_Ramp_Capacity | Heat Pump Heating Ramp | % | Read | |
| AV | 51 | Heating_Capacity | Heating Ramp [BACnet short list] | % | Read | |
| AV | 52 | Case_Heat_Control_Ramp | Case Heat Ramp | % | Read | |
| AV | 53 | Hot_Gas_Reheat_Ramp | Hot Gas Reheat Ramp | % | Read | |
| AV | 54 | Outside_Dewpoint | Outside Dewpoint [BACnet short list] | °F | Read | |
| AV | 55 | Outside_Enthalpy | Outside Enthalpy [BACnet short list] | BTU/lb | Read | |
| AV | 56 | Return_Dewpoint | Return Dewpoint [BACnet short list] | °F | Read | |
| AV | 57 | Return_Enthalpy | Return Enthalpy [BACnet short list] | BTU/lb | Read | |
| AV | 58 | Space_Dewpoint | Space Dewpoint [BACnet short list] | °F | Read | |
| AV | 59 | Space_Enthalpy | Space Enthalpy [BACnet short list] | BTU/lb | Read | |
| AV | 64 | Total_Exhaust_Fan_CFM_BMS | Total Exhaust Fan CFM [BACnet short list] | CFM | Read | |
| AV | 65 | Total_Supply_Fan_CFM_BMS | Total Supply Fan CFM [BACnet short list] | CFM | Read | |
| AV | 66 | OAD_CFM_BMS | OAD CFM [BACnet short list] | CFM | Read | |
| AV | 67 | Active_Temperature_Setpoint | Active Temperature Setpoint [BACnet short list] | °F | Read | |
| AV | 68 | Chilled_Water_1_Valve_Analog_Output | Chilled Water 1 Valve Analog Output [BACnet short list] | % | Read | |
| AV | 70 | Electric_Heater_1_Analog_Output | Electric Heater 1 Analog Output [BACnet short list] | % | Read | |
| AV | 72 | Energy_Recovery_Analog_Output | Energy Recovery Analog Output [BACnet short list] | % | Read | |
| AV | 73 | Exhaust_Fan_Speed_Analog_Output | Exhaust Fan Speed Analog Output [BACnet short list] | % | Read | |
| AV | 74 | Hot_Water_Valve_1_Analog_Output | Hot Water Valve 1 Analog Output [BACnet short list] | % | Read | |
| AV | 78 | Outside_Air_Damper_Analog_Output | Outside Air Damper Analog Output | % | Read | |
| AV | 79 | Supply_Fan_Speed_Analog_Output | Supply Fan Speed Analog Output [BACnet short list] | % | Read | |
| AV | 90 | Coil_Temperature_Calculated_Setpoint | Calculated Coil Leaving Set point | °F | Read | |
| AV | 91 | Active_Cooling_Setpoint | Active Cooling Setpoint [BACnet short list] | °F | Read | |
| AV | 92 | Active_Heating_Setpoint | Active Heating Setpoint [BACnet short list] | °F | Read | |
| AV | 93 | LatestAlm_Real | Most recent alarm - See Alarm Table [BACnet short list] | Read | ||
| AV | 94 | Device_Enable_DO_Word_Real_1 | Device Enable DO Word - See Table [BACnet short list] (bit-packed) | Read | ||
| AV | 95 | Device_Enable_DO_Word_Real_2 | Device Enable DO Word - See Table [BACnet short list] (bit-packed) | Read | ||
| AV | 98 | Device_Offline_Word_Real_1 | Device Offline Word - See Table [BACnet short list] (bit-packed) | Read | ||
| AV | 99 | Device_Offline_Word_Real_2 | Device Offline Word - See Table [BACnet short list] (bit-packed) | Read | ||
| AV | 100 | Device_Alarm_Word_Real_1 | Device Alarm Word - See Table [BACnet short list] (bit-packed) | Read | ||
| AV | 101 | Device_Alarm_Word_Real_2 | Device Alarm Word - See Table [BACnet short list] (bit-packed) | Read | ||
| AV | 102 | System_Word_Real_1 | System Word - See Table [BACnet short list] (bit-packed) | Read | ||
| AV | 103 | System_Word_Real_2 | System Word - See Table [BACnet short list] (bit-packed) | Read | ||
| AV | 104 | Unit_Status_Word_Real_1 | Unit Status Word - See Table [BACnet short list] (bit-packed) | Read | ||
| AV | 105 | Unit_Status_Word_Real_2 | Unit Status Word - See Table [BACnet short list] (bit-packed) | Read | ||
| AV | 106 | ER_Control_Signal_BMS | BMS to control signal for Energy Recovery. [BACnet short list] | % | Write | |
| AV | 107 | Heating_Ramp | Heating Ramp [BACnet short list] | % | Read | |
| AV | 108 | Cooling_1_Ramp | Cooling 1 Ramp [BACnet short list] | % | Read | |
| BI | 1 | Exhaust_Fan_1_Status_Digital_Input | Exhaust Fan Status [BACnet short list] | Read | 0=Inactive, 1=Active | |
| BI | 2 | Supply_Fan_1_Status_Digital_Input | Supply Fan Status [BACnet short list] | Read | 0=Inactive, 1=Active | |
| BVmin | 1 | BMS_Watchdog | BMS Watchdog command Used to determine BMS comm status [BACnet short list] | Write | 0=Inactive, 1=Active | |
| BVmin | 2 | System_Enable | Master system enable/disable point [BACnet short list] | Write | 0=Disable, 1=Enable | |
| BVmin | 3 | BMS_Occupancy_Command | Occupancy Command [BACnet short list] | Write | 0=Occupied, 1=Unoccupied | |
| BVmin | 4 | Reset_All_Alarms | Alarm Reset Command [BACnet short list] | Write | 0=Normal, 1=Reset | |
| BV | 5 | Exhaust_Only_Mode_BMS_Cmd | Exhaust Mode Command [BACnet short list] | Write | 0=Disable, 1=Enable | |
| BV | 6 | Pressurization_Only_Mode_BMS_Cmd | Pressurization Mode Command | Write | 0=Disable, 1=Enable | |
| BV | 7 | Outside_RH_Source_BMS | Outside RH Source Selection [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 8 | Outside_Temp_Source_BMS | Outside Temp Source Selection [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 9 | Return_RH_Source_BMS | Return RH Source Selection [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 10 | Return_Temp_Source_BMS | Return Temp Source Selection [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 11 | Space_1_CO2_Source_BMS | Space 1 CO2 Source Selection [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 12 | Space_2_CO2_Source_BMS | Space 2 CO2 Source Selection [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 13 | Return_CO2_Source_BMS | Return CO2 Source Selection [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 14 | Space_RH_Source_BMS | Space RH Source Selection [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 15 | Space_Static_Source_BMS | Space Static Source Selection [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 16 | Space_Temp_Source_BMS | Space Temp Source Selection [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 17 | SF_Control_Source_BMS | Allows the BMS to control supply fan speed [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 18 | EF_Control_Source_BMS | Allows the BMS to control exhaust fan speed [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 19 | OAD_Control_Source_BMS | Allows the BMS to control OAD position | Write | 0=Local, 1=BMS | |
| BV | 20 | Aux_BMS_Digital_Output_1 | BMS Commanded auxiliary digital output [BACnet short list] | Write | 0=Inactive, 1=Active | |
| BV | 21 | Aux_BMS_Digital_Output_2 | BMS Commanded auxiliary digital output [BACnet short list] | Write | 0=Inactive, 1=Active | |
| BV | 22 | Occupied | Occupancy [BACnet short list] | Read | 0=Unoccupied, 1=Occupied | |
| BVmin | 23 | Global_Alarm | General alarm point Default set to indicate any alarm is active [BACnet short list] | Read | 0=Normal, 1=Alarm | |
| BV | 24 | BMS_Watchdog_Active | Status of the BMS watchdog heartbeat [BACnet short list] | Read | 0=Inactive, 1=Active | |
| BV | 29 | Supply_Fan_1_Alarm.Active | Supply Fan Alarm Active [BACnet short list] | Read | 0=Normal, 1=Alarm | |
| BV | 30 | Exhaust_Fan_1_Alarm.Active | Exhaust Fan Alarm Active [BACnet short list] | Read | 0=Normal, 1=Alarm | |
| BV | 31 | Drain_Pan_Alarm.Active | Condensate Drain Pan Alarm Active | Read | 0=Normal, 1=Alarm | |
| BV | 32 | Fire_Safety_Shutdown_Alarm.Active | Fire Safety Shutdown Alarm Active | Read | 0=Normal, 1=Alarm | |
| BV | 35 | ER_Control_Source_BMS | Allows the BMS to control energy recovery. [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 36 | Econ_Enable_Source_BMS | Allows the BMS to control ERV call for cooling. [BACnet short list] | Write | 0=Local, 1=BMS | |
| BV | 37 | Econ_Enable_from_BMS | Enable ERV call for cooling. [BACnet short list] | Write | 0=Disable, 1=Enable | |
| IV | 1 | Temperature_Reset_Mode | Occupied Reset Type Setpoint [BACnet short list] | Write | 1=Discharge, 2=Space, 3=Return, 4=Outside | |
| IV | 2 | Temperature_Reset_Mode_Unoccupied | Unoccupied Reset Type Setpoint [BACnet short list] | Write | 1=Discharge, 2=Space, 3=Return | |
| IV | 3 | Active_Temperature_Reset_Mode | Active Occupied Reset Type Setpoint [BACnet short list] | Read | 1=Discharge, 2=Space, 3=Return, 4=Outside | |
| IVmin | 5 | LatestAlm | Most recent alarm - See Alarm Table [BACnet short list] | Read | ||
| IV | 6 | Device_Enable_DO_Word | Device Enable DO Word - See Table [BACnet short list] (bit-packed) | Read | ||
| IV | 8 | Device_Offline_Word | Device Offline Word - See Table [BACnet short list] (bit-packed) | Read | ||
| IV | 9 | Device_Alarm_Word | Device Alarm Word - See Table [BACnet short list] (bit-packed) | Read | ||
| IV | 10 | System_Word | System Word - See Table [BACnet short list] (bit-packed) | Read | ||
| IV | 11 | Unit_Status_Word | Unit Status Word - See Table [BACnet short list] (bit-packed) | Read |
No points match these filters.
Object ID lookup: Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller point IDs by name
AI1Space_Temp_Analog_InputAI2Supply_Temp_Analog_InputAI3Outside_Air_Temp_Analog_InputAI4Mixed_Temp_Analog_InputAI5Cold_Coil_1_Temp_Analog_InputAI7Return_Temp_Analog_InputAI8Exhaust_Temp_Analog_InputAI9Space_RH_Analog_InputAI10Outside_RH_Analog_InputAI11Return_RH_Analog_InputAI12Return_Duct_Static_Pressure_Analog_InputAI13Space_Static_Pressure_Analog_InputAI14Supply_Duct_Static_Pressure_Analog_InputAI15Space_CO2_1_Analog_InputAI16Space_CO2_2_Analog_InputAI17Return_CO2_Analog_InputAI36Aux_In_Customer_1AI37Aux_In_Customer_2AI38Aux_In_Customer_3AI39Aux_In_Customer_4AI40Aux_In_Customer_5AI41Aux_In_Customer_6AI42Aux_In_Customer_7AI43Aux_In_Customer_8AI44Aux_In_Customer_9AI45Aux_In_Customer_10AV1Temperature_SetpointAV2Temperature_Heat_Cool_DeadbandAV3Temperature_Setpoint_UnoccupiedAV4Temperature_Heat_Cool_Deadband_UnoccupiedAV5Cooling_Coil_Setpoint_MinAV6Cooling_Coil_Setpoint_MaxAV7Dehumidification_SetpointAV8Outside_Dewpoint_SetpointAV9Indoor_Dewpoint_SetpointAV10Unocc_Indoor_Dewpoint_SetpointAV11Unoccupied_Dehumidification_SetpointAV12Economizer_Temp_Enable_SetpointAV13Economizer_Enthalpy_Enable_SetpointAV14Supply_Fan_CFM_SetpointAV15Exhaust_Fan_CFM_SetpointAV16OAD_CFM_SetpointAV17Cooling_Lockout_SetpointAV18Heating_Lockout_SetpointAV19Preheat_Lockout_SetpointAV20Economizer_Lockout_SetpointAV21Return_Duct_Static_Pressure_SetpointAV22Space_Static_Pressure_SetpointAV23Supply_Duct_Static_Pressure_SetpointAV24Space_CO2_SetpointAV25Outside_Air_Damper_Minimum_Setpoint_OccAV26Outside_RH_from_BMSAV27Outside_Temp_from_BMSAV28Return_RH_from_BMSAV29Return_Temp_from_BMSAV30Space_1_CO2_from_BMSAV31Space_2_CO2_from_BMSAV32Return_CO2_from_BMSAV33Space_RH_from_BMSAV34Space_Static_from_BMSAV35Space_Temp_from_BMSAV36SF_Control_Signal_BMSAV37EF_Control_Signal_BMSAV38OAD_Control_Signal_BMSAV39Aux_BMS_Analog_Output_1AV40Unit_Status_ModeAV41Supply_Temperature_Calculated_SetpointAV42Cooling_1_Ramp_CapacityAV44Defrost_RampAV45Economizer_RampAV46Head_Pressure_Control_Ramp_1_RampAV47Head_Pressure_Control_Ramp_2_RampAV50HP_Ramp_CapacityAV51Heating_CapacityAV52Case_Heat_Control_RampAV53Hot_Gas_Reheat_RampAV54Outside_DewpointAV55Outside_EnthalpyAV56Return_DewpointAV57Return_EnthalpyAV58Space_DewpointAV59Space_EnthalpyAV64Total_Exhaust_Fan_CFM_BMSAV65Total_Supply_Fan_CFM_BMSAV66OAD_CFM_BMSAV67Active_Temperature_SetpointAV68Chilled_Water_1_Valve_Analog_OutputAV70Electric_Heater_1_Analog_OutputAV72Energy_Recovery_Analog_OutputAV73Exhaust_Fan_Speed_Analog_OutputAV74Hot_Water_Valve_1_Analog_OutputAV78Outside_Air_Damper_Analog_OutputAV79Supply_Fan_Speed_Analog_OutputAV90Coil_Temperature_Calculated_SetpointAV91Active_Cooling_SetpointAV92Active_Heating_SetpointAV93LatestAlm_RealAV94Device_Enable_DO_Word_Real_1AV95Device_Enable_DO_Word_Real_2AV98Device_Offline_Word_Real_1AV99Device_Offline_Word_Real_2AV100Device_Alarm_Word_Real_1AV101Device_Alarm_Word_Real_2AV102System_Word_Real_1AV103System_Word_Real_2AV104Unit_Status_Word_Real_1AV105Unit_Status_Word_Real_2AV106ER_Control_Signal_BMSAV107Heating_RampAV108Cooling_1_RampBI1Exhaust_Fan_1_Status_Digital_InputBI2Supply_Fan_1_Status_Digital_InputBV1BMS_WatchdogBV2System_EnableBV3BMS_Occupancy_CommandBV4Reset_All_AlarmsBV5Exhaust_Only_Mode_BMS_CmdBV6Pressurization_Only_Mode_BMS_CmdBV7Outside_RH_Source_BMSBV8Outside_Temp_Source_BMSBV9Return_RH_Source_BMSBV10Return_Temp_Source_BMSBV11Space_1_CO2_Source_BMSBV12Space_2_CO2_Source_BMSBV13Return_CO2_Source_BMSBV14Space_RH_Source_BMSBV15Space_Static_Source_BMSBV16Space_Temp_Source_BMSBV17SF_Control_Source_BMSBV18EF_Control_Source_BMSBV19OAD_Control_Source_BMSBV20Aux_BMS_Digital_Output_1BV21Aux_BMS_Digital_Output_2BV22OccupiedBV23Global_AlarmBV24BMS_Watchdog_ActiveBV29Supply_Fan_1_Alarm.ActiveBV30Exhaust_Fan_1_Alarm.ActiveBV31Drain_Pan_Alarm.ActiveBV32Fire_Safety_Shutdown_Alarm.ActiveBV35ER_Control_Source_BMSBV36Econ_Enable_Source_BMSBV37Econ_Enable_from_BMSIV1Temperature_Reset_ModeIV2Temperature_Reset_Mode_UnoccupiedIV3Active_Temperature_Reset_ModeIV5LatestAlmIV6Device_Enable_DO_WordIV8Device_Offline_WordIV9Device_Alarm_WordIV10System_WordIV11Unit_Status_Word
Integration notes
- Appendix E prints a Modbus register beside each BACnet object; only the BACnet side is listed here. Access is from the Read/Write column (RW shown as W).
- Objects marked * in the manual are the BACnet short list; they carry "[BACnet short list]" in the description.
- The shorter Greenheck IVE BACnet integration guide (487690, also in this library) has 95 objects; all 95 instances are here (84 with the same name), plus 57 more setpoints, BMS commands, dewpoint/enthalpy values and ramps.
- Binary states are the printed active/inactive texts (1 = active text).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)
How many BACnet points does the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) have?
This list has 152 BACnet objects: 26 analog inputs, 84 analog values, 2 binary inputs, 31 binary values, 9 integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) BACnet points are writable?
66 of the 152 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) BACnet documentation?
The source is Microprocessor Controller for IVE - Reference Guide, Appendix E: Points List (487416 Rev. 2), revision 2026-05, published free by Valent at https://content.greenheck.com/public/DAMProd/Original/10025/487416-ive-microprocessor-controller-r2-may-2026_val.pdf.
What are the minimum BACnet points to integrate the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)?
Start with BV 2 System_Enable (Enables or disables the unit); BV 3 BMS_Occupancy_Command (Occupancy; Active = Unoccupied, Inactive = Occupied); AV 1 Temperature_Setpoint (Occupied temperature setpoint); BV 1 BMS_Watchdog (Heartbeat when BMS controls fans or sensors); BV 4 Reset_All_Alarms (Remote alarm reset); AV 40 Unit_Status_Mode (Current operating mode code); AI 2 Supply_Temp_Analog_Input (Supply (discharge) air temperature); BV 23 Global_Alarm (Any active alarm); IV 5 LatestAlm (Most recent alarm code).
How do I enable BMS control of the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)?
BV 2 System_Enable enables or disables the unit from the BMS; BV 3 BMS_Occupancy_Command sets occupancy (Active = Unoccupied).
Does the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3) need a BACnet heartbeat or have a communication timeout?
BV 1 BMS_Watchdog is required when the BMS takes the place of a hardwired sensor: the BMS toggles it between true and false within the timeout delay. If the timer expires the controller falls back to hardwired sensors and raises the BMS watchdog alarm (alarm 79). BV 24 shows the watchdog status.
Can the BMS supply sensor values to the Valent IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)?
Set the sensor source-select binary (BV 7-16, e.g. BV 8 Outside_Temp_Source_BMS) to BMS, then write the matching *_from_BMS analog value (e.g. AV 27 Outside_Temp_from_BMS). Fan speed, energy recovery and economizer control can be handed to the BMS with BV 17, BV 18, BV 35 and BV 36.
How do I check these points on the real IVE Indoor Energy Recovery Ventilator Microprocessor Controller (IVE v1.3)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Valent BACnet points lists
- Energy recovery ventilator (ERV) controller
Valent ERV Microprocessor Controller (ERV v3.10 / v3.11)
Valent energy recovery ventilators with the factory microprocessor controller, ERV program v3.10/v3.11.
Also known as: 486440, Document 486440, Valent ERV controller, ERV v3.10, ERV v3.11, c.pCO - Energy recovery / DOAS make-up air unit controller (legacy)
Valent JENEsys Controller (legacy) for VPR / VPRE / VPRC/P / VPRX
Valent VPR, VPRE, VPRC/P and VPRX series units with the JENEsys controller, software version 4 (legacy controller).
Also known as: JENEsys, IOM-C1-0616, 474626, VPR, VPRE, VPRC, VPRP, VPRX, Valent legacy controller - Dedicated outdoor air system (DOAS) unit controller
Valent VX Series DOAS Microprocessor Controller (DOAS v9.4)
Valent VX-series dedicated outdoor air units (VX, VXE, VXC) with the factory microprocessor controller, DOAS program v9.4.
Also known as: 485937, Document 485937, VX, VXE, VXC, Valent DOAS controller, DOAS v9.4, c.pCO
Source: Microprocessor Controller for IVE - Reference Guide, Appendix E: Points List · 487416 Rev. 2 · rev. 2026-05. Object names, instances and units are reproduced as published; descriptions are our own.