Humidity and temperature sensor (wall transmitter) · BACnet points list

Vaisala HMW90 series humidity and temperature transmitter (BACnet MS/TP) BACnet points list

Updated 4 November 2026

Short answer

The digital HMW95 transmitter measures relative humidity and temperature and calculates dewpoint, wet bulb, absolute humidity, mixing ratio and enthalpy. On BACnet MS/TP each value is an Analog Input; two writable Analog Values set the operating pressure or altitude used in the humidity calculations.

This page lists 11 BACnet objects for the Vaisala HMW90 series humidity and temperature transmitter (BACnet MS/TP) — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vaisala’s own free documentation, linked below.

Manufacturer
Vaisala
Model
HMW90 series humidity and temperature transmitter (BACnet MS/TP)
Equipment
Humidity and temperature sensor (wall transmitter)
Equipment type
Thermostats, sensors & meters
BACnet objects
11 (2 writable)
Transport
BACnet MS/TP
Firmware
Application software 1.0.28 (firmware 1.0.0.0)
Default device instance
Unique value set at the factory
Also known as
HMW95, HMW90 BACnet, XMW90, Vaisala humidity transmitter BACnet, M211399EN
Source document
HMW90 Series Transmitters User's Guide · M211399EN-H · rev. 2016-04
Download CSV 11 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vaisala’s current documentation and the live device before use. Not official Vaisala information. Terms of use.

BMS integration notes: Vaisala HMW90 series humidity and temperature transmitter (BACnet MS/TP)

Integration in brief

Set the protocol, baud rate and MAC address on the DIP switches, give the transmitter a unique device instance, then read relative humidity (AI 2) and temperature (AI 3), plus dewpoint (AI 4) or enthalpy (AI 10) if the control sequence needs them. Write the site altitude (AV 2) once for accurate calculated values.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 2RHRelative humidity, %Read
AI 3TTemperatureRead
AI 4TdDewpointRead
AI 10hEnthalpyRead

Sensors & values from the BMS

AV 1 (operating pressure, hPa) or AV 2 (altitude) can be written by the BMS for the humidity calculations; the two are linked.

Network setup

Watch out for

Vaisala HMW90 series humidity and temperature transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

11 of 11 shown
Type
Access
Show
Vaisala HMW90 series humidity and temperature transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin2RHRelative humidity%RHRead
AImin3TTemperature°C or °FRead
AImin4TdDewpoint°C or °FRead
AI5TdfDewpoint°C or °FRead
AI6dTdDewpoint depressionK or °F (delta)Read
AI7TwWet bulb temperature°C or °FRead
AI8aAbsolute humidityg/m³ or gr/ft³Read
AI9xMixing ratiog/kg or gr/lbRead
AImin10hEnthalpykJ/kg or BTU/lbRead
AV1OPER POperating pressure for humidity calculations, default 1013.25hPaWrite
AV2OPER AltitudeOperating altitude; linked to OPER Pm or ftWrite
Object ID lookup: Vaisala HMW90 series humidity and temperature transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HMW90 series humidity and temperature transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vaisala HMW90 series humidity and temperature transmitter (BACnet MS/TP)

How many BACnet points does the Vaisala HMW90 series humidity and temperature transmitter (BACnet MS/TP) have?

This list has 11 BACnet objects: 9 analog inputs, 2 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vaisala HMW90 series humidity and temperature transmitter (BACnet MS/TP) BACnet points are writable?

2 of the 11 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vaisala HMW90 series humidity and temperature transmitter (BACnet MS/TP) BACnet documentation?

The source is HMW90 Series Transmitters User's Guide (M211399EN-H), revision 2016-04, published free by Vaisala at https://docs.vaisala.com/api/khub/documents/Nz9Rxwoq_FgzXgpFHM~8Yw/content.

What are the minimum BACnet points to integrate the Vaisala HMW90 series humidity and temperature transmitter (BACnet MS/TP)?

Start with AI 2 RH (Relative humidity, %); AI 3 T (Temperature); AI 4 Td (Dewpoint); AI 10 h (Enthalpy).

Can the BMS supply sensor values to the Vaisala HMW90 series humidity and temperature transmitter (BACnet MS/TP)?

AV 1 (operating pressure, hPa) or AV 2 (altitude) can be written by the BMS for the humidity calculations; the two are linked.

How do I check these points on the real HMW90 series humidity and temperature transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.