Vaisala GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP) BACnet points list

Updated 4 November 2026

Short answer

The digital GMW95 transmitters measure CO2 and temperature, and the R models add humidity. On BACnet MS/TP each value is an Analog Input; humidity models also give dewpoint, wet bulb, absolute humidity, mixing ratio and enthalpy. Two writable Analog Values set the operating pressure or altitude used for CO2 pressure compensation.

This page lists 12 BACnet objects for the Vaisala GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP) — 2 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vaisala’s own free documentation, linked below.

Manufacturer
Vaisala
Model
GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP)
Equipment
CO2, temperature and humidity sensor (wall transmitter)
Equipment type
Thermostats, sensors & meters
BACnet objects
12 (2 writable)
Transport
BACnet MS/TP
Firmware
Application software 1.1.28 and later (firmware 1.1.0.0 and later)
Default device instance
Unique value set at the factory
Also known as
GMW95, GMW95D, GMW95R, GMW95RD, GMW90 BACnet, XMW90, Vaisala CO2 transmitter BACnet, M211659EN
Source document
GMW90 Series Carbon Dioxide, Temperature, and Humidity Transmitters User's Guide · M211659EN-C · rev. 2016-04
Download CSV 12 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vaisala’s current documentation and the live device before use. Not official Vaisala information. Terms of use.

BMS integration notes: Vaisala GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP)

Integration in brief

Set the protocol, baud rate and MAC address on the DIP switches, give the transmitter a unique device instance, then read CO2 (AI 1), temperature (AI 3) and, on humidity models, relative humidity (AI 2). If the site is well above sea level, write the altitude (AV 2) or pressure (AV 1) once so the CO2 reading is compensated.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1CO2CO2 concentration, ppmRead
AI 3TTemperatureRead
AI 2RHRelative humidity, % (humidity models)Read

Sensors & values from the BMS

AV 1 (operating pressure, hPa) or AV 2 (altitude) can be written by the BMS to compensate the CO2 measurement; the two are linked.

Network setup

Watch out for

Vaisala GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

12 of 12 shown
Type
Access
Show
Vaisala GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1CO2Carbon dioxideppmRead
AImin2RHRelative humidity (humidity models)%RHRead
AImin3TTemperature°C or °FRead
AI4TdDewpoint (humidity models)°C or °FRead
AI5TdfDewpoint (humidity models)°C or °FRead
AI6dTdDewpoint depression (humidity models)K or °F (delta)Read
AI7TwWet bulb temperature (humidity models)°C or °FRead
AI8aAbsolute humidity (humidity models)g/m³ or gr/ft³Read
AI9xMixing ratio (humidity models)g/kg or gr/lbRead
AI10hEnthalpy (humidity models)kJ/kg or BTU/lbRead
AV1OPER POperating pressure for compensation, default 1013.25hPaWrite
AV2OPER AltitudeOperating altitude; linked to OPER Pm or ftWrite
Object ID lookup: Vaisala GMW90 series CO2, temperature and humidity transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vaisala GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP)

How many BACnet points does the Vaisala GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP) have?

This list has 12 BACnet objects: 10 analog inputs, 2 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vaisala GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP) BACnet points are writable?

2 of the 12 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vaisala GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP) BACnet documentation?

The source is GMW90 Series Carbon Dioxide, Temperature, and Humidity Transmitters User's Guide (M211659EN-C), revision 2016-04, published free by Vaisala at https://docs.vaisala.com/api/khub/documents/9qppJ_IBz5JrKtQAoZ~ioQ/content.

What are the minimum BACnet points to integrate the Vaisala GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP)?

Start with AI 1 CO2 (CO2 concentration, ppm); AI 3 T (Temperature); AI 2 RH (Relative humidity, % (humidity models)).

Can the BMS supply sensor values to the Vaisala GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP)?

AV 1 (operating pressure, hPa) or AV 2 (altitude) can be written by the BMS to compensate the CO2 measurement; the two are linked.

How do I check these points on the real GMW90 series CO2, temperature and humidity transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vaisala BACnet points lists

Source: GMW90 Series Carbon Dioxide, Temperature, and Humidity Transmitters User's Guide · M211659EN-C · rev. 2016-04. Object names, instances and units are reproduced as published; descriptions are our own.