Humidity and temperature sensor (duct transmitter) · BACnet points list

Vaisala HMD65 humidity and temperature duct transmitter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The HMD65 duct transmitter selects Modbus RTU or BACnet MS/TP by DIP switch. On BACnet it serves relative humidity, temperature and six calculated humidity values (dewpoint, dew/frost point, wet bulb, absolute humidity, mixing ratio, enthalpy) as Analog Inputs, plus a writable operating pressure value used in the calculations.

This page lists 9 BACnet objects for the Vaisala HMD65 humidity and temperature duct transmitter (BACnet MS/TP) — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Vaisala’s own free documentation, linked below.

Manufacturer
Vaisala
Model
HMD65 humidity and temperature duct transmitter (BACnet MS/TP)
Equipment
Humidity and temperature sensor (duct transmitter)
Equipment type
Thermostats, sensors & meters
BACnet objects
9 (1 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
HMD65, Vaisala HMD65, HMD65 BACnet, M212243EN
Source document
HMD65 User Guide, BACnet Reference · M212243EN-C
Download CSV 9 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Vaisala’s current documentation and the live device before use. Not official Vaisala information. Terms of use.

BMS integration notes: Vaisala HMD65 humidity and temperature duct transmitter (BACnet MS/TP)

Integration in brief

Set BACnet mode, MAC address and bit rate on the DIP switches, then read RH and temperature (and dewpoint or enthalpy if needed). If the site is far from sea level, write the operating pressure once.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1RHRelative humidity, %Read
AI 2TTemperatureRead
AI 3TdDewpoint temperatureRead

Sensors & values from the BMS

AV 1 OPER P (operating pressure, hPa, default 1013.25) can be written by the BMS for the humidity calculations.

Network setup

Watch out for

Vaisala HMD65 humidity and temperature duct transmitter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

9 of 9 shown
Type
Access
Show
Vaisala HMD65 humidity and temperature duct transmitter (BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1RHRelative humidity%RHRead
AImin2TTemperature°C (Units writable: °C/°F)Read
AImin3TdDewpoint°C or °FRead
AI4TdfDew/frost point°C or °FRead
AI5TwWet bulb temperature°C or °FRead
AI6aAbsolute humidityg/m3 or gr/ft3Read
AI7xMixing ratiog/kg or gr/lbRead
AI8hEnthalpykJ/kg or Btu/lbRead
AV1OPER POperating pressure for humidity calculations (default 1013.25)hPaWrite
Object ID lookup: Vaisala HMD65 humidity and temperature duct transmitter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the HMD65 humidity and temperature duct transmitter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Vaisala HMD65 humidity and temperature duct transmitter (BACnet MS/TP)

How many BACnet points does the Vaisala HMD65 humidity and temperature duct transmitter (BACnet MS/TP) have?

This list has 9 BACnet objects: 8 analog inputs, 1 analog value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Vaisala HMD65 humidity and temperature duct transmitter (BACnet MS/TP) BACnet points are writable?

1 of the 9 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Vaisala HMD65 humidity and temperature duct transmitter (BACnet MS/TP) BACnet documentation?

The source is HMD65 User Guide, BACnet Reference (M212243EN-C), published free by Vaisala at https://docs.vaisala.com/r/M212243EN-C/en-US.

What are the minimum BACnet points to integrate the Vaisala HMD65 humidity and temperature duct transmitter (BACnet MS/TP)?

Start with AI 1 RH (Relative humidity, %); AI 2 T (Temperature); AI 3 Td (Dewpoint temperature).

Can the BMS supply sensor values to the Vaisala HMD65 humidity and temperature duct transmitter (BACnet MS/TP)?

AV 1 OPER P (operating pressure, hPa, default 1013.25) can be written by the BMS for the humidity calculations.

How do I check these points on the real HMD65 humidity and temperature duct transmitter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Vaisala BACnet points lists

Source: HMD65 User Guide, BACnet Reference · M212243EN-C. Object names, instances and units are reproduced as published; descriptions are our own.