Light level and occupancy sensor · BACnet points list

Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The Aura Interior Sensor is a ceiling light-level and motion sensor that is its own BACnet MS/TP device. It reports the light level in lux, four lux-threshold flags and a motion flag; thresholds, hysteresis, delays and the occupancy mode are Analog Values the BMS can adjust.

This page lists 18 BACnet objects for the Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Touch-Plate’s own free documentation, linked below.

Manufacturer
Touch-Plate
Model
Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)
Equipment
Light level and occupancy sensor
Equipment type
Thermostats, sensors & meters
BACnet objects
18 (12 writable)
Transport
BACnet MS/TP
Firmware
2.48 (application 1.5d)
Default device instance
68301-68500
Also known as
AUR-IB-FX, Aura Interior Sensor, Touch-Plate Aura, AUR-EB-FX, Aura Exterior Sensor
Source document
PIC Statement - Aura Interior Sensor
Download CSV 18 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Touch-Plate’s current documentation and the live device before use. Not official Touch-Plate information. Terms of use.

BMS integration notes: Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)

Integration in brief

Read AV 1 for the light level and BI 5 for occupancy; the threshold flags BI 1-4 are ready-made daylight switches. Inputs support COV subscriptions, so subscribe rather than poll.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BI 5Motion DetectedOccupancy, 1 = room occupiedRead
AV 1Light LevelMeasured light level, luxRead
BI 1Light Threshold 11 = light above threshold 1 (AV 4)Read

Network setup

Watch out for

Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

18 of 18 shown
Type
AnalogBinary
Access
Show
Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) BACnet Points List
DescriptionStates
BImin1Light Threshold 11 when ambient light exceeds lux threshold 1 plus hysteresisRead1=Room Lit
BI2Light Threshold 21 when ambient light exceeds lux threshold 2 plus hysteresisRead1=Room Lit
BI3Light Threshold 31 when ambient light exceeds lux threshold 3 plus hysteresisRead1=Room Lit
BI4Light Threshold 41 when ambient light exceeds lux threshold 4 plus hysteresisRead1=Room Lit
BImin5Motion DetectedOccupancy from the motion sensorRead1=Room Occupied
AVmin1Light LevelCurrent light level, 0-65535luxRead
AV2Light Sensor HysterisisThreshold hysteresis 1-100 %, default 1%Write
AV3Light Sensor DelayLight sensor delay 1-3600 s, default 1sWrite
AV4Lux Threshold 1/2Lux threshold for BI 1, default 50luxWrite
AV5Lux Threshold 3/4Lux threshold for BI 2, default 100luxWrite
AV6Lux Threshold 5/6Lux threshold for BI 3, default 200luxWrite
AV7Lux Threshold 7/8Lux threshold for BI 4, default 500luxWrite
AV8Room Vacancy DelayVacancy delay 1-120 min, default 15minWrite
AV9Motion Sensitivity OffsetMotion sensitivity 2-254, default 25Write
AV10Occupancy Sensor ModeOccupancy sensor modeWrite0=Ignore Motion, 1=Motion Operation (default)
AV11MS/TP MAC AddressMS/TP address, 1-127Write
AV12MS/TP Baud Rate9600, 19200, 38400 or 76800Write
AV1003Device InstanceDevice instance, default 68301-68500Write
Object ID lookup: Touch-Plate Aura AUR-IB-FX point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)

How many BACnet points does the Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) have?

This list has 18 BACnet objects: 13 analog values, 5 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) BACnet points are writable?

12 of the 18 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) BACnet documentation?

The source is PIC Statement - Aura Interior Sensor, published free by Touch-Plate at https://touchplate.com/wp-content/uploads/product-documents/Components/Sensors/Aura-Interior-BACnet-PIC-Sheet.pdf.

What are the minimum BACnet points to integrate the Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)?

Start with BI 5 Motion Detected (Occupancy, 1 = room occupied); AV 1 Light Level (Measured light level, lux); BI 1 Light Threshold 1 (1 = light above threshold 1 (AV 4)).

How do I check these points on the real Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.