- Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)
Light level and occupancy sensor · BACnet points list
Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) BACnet points list
Updated 12 November 2026
The Aura Interior Sensor is a ceiling light-level and motion sensor that is its own BACnet MS/TP device. It reports the light level in lux, four lux-threshold flags and a motion flag; thresholds, hysteresis, delays and the occupancy mode are Analog Values the BMS can adjust.
This page lists 18 BACnet objects for the Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) — 12 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Touch-Plate’s own free documentation, linked below.
- Manufacturer
- Touch-Plate
- Model
- Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)
- Equipment
- Light level and occupancy sensor
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 18 (12 writable)
- Transport
- BACnet MS/TP
- Firmware
- 2.48 (application 1.5d)
- Default device instance
- 68301-68500
- Also known as
- AUR-IB-FX, Aura Interior Sensor, Touch-Plate Aura, AUR-EB-FX, Aura Exterior Sensor
- Source document
- PIC Statement - Aura Interior Sensor
Reference only, provided as-is: verify against Touch-Plate’s current documentation and the live device before use. Not official Touch-Plate information. Terms of use.
BMS integration notes: Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)
Read AV 1 for the light level and BI 5 for occupancy; the threshold flags BI 1-4 are ready-made daylight switches. Inputs support COV subscriptions, so subscribe rather than poll.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BI 5 | Motion Detected | Occupancy, 1 = room occupied | Read |
| AV 1 | Light Level | Measured light level, lux | Read |
| BI 1 | Light Threshold 1 | 1 = light above threshold 1 (AV 4) | Read |
Network setup
- MS/TP MAC address, baud rate and I/O configuration are set with DIP switches; AV 11 and AV 12 read or change them.
- MS/TP master at 9600, 19200, 38400 or 76800 baud.
- Device instance defaults to 68301-68500 and can be changed through AV 1003.
Watch out for
- Setting AV 10 Occupancy Sensor Mode to 0 makes the sensor ignore motion.
Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 1 | Light Threshold 1 | 1 when ambient light exceeds lux threshold 1 plus hysteresis | Read | 1=Room Lit | |
| BI | 2 | Light Threshold 2 | 1 when ambient light exceeds lux threshold 2 plus hysteresis | Read | 1=Room Lit | |
| BI | 3 | Light Threshold 3 | 1 when ambient light exceeds lux threshold 3 plus hysteresis | Read | 1=Room Lit | |
| BI | 4 | Light Threshold 4 | 1 when ambient light exceeds lux threshold 4 plus hysteresis | Read | 1=Room Lit | |
| BImin | 5 | Motion Detected | Occupancy from the motion sensor | Read | 1=Room Occupied | |
| AVmin | 1 | Light Level | Current light level, 0-65535 | lux | Read | |
| AV | 2 | Light Sensor Hysterisis | Threshold hysteresis 1-100 %, default 1 | % | Write | |
| AV | 3 | Light Sensor Delay | Light sensor delay 1-3600 s, default 1 | s | Write | |
| AV | 4 | Lux Threshold 1/2 | Lux threshold for BI 1, default 50 | lux | Write | |
| AV | 5 | Lux Threshold 3/4 | Lux threshold for BI 2, default 100 | lux | Write | |
| AV | 6 | Lux Threshold 5/6 | Lux threshold for BI 3, default 200 | lux | Write | |
| AV | 7 | Lux Threshold 7/8 | Lux threshold for BI 4, default 500 | lux | Write | |
| AV | 8 | Room Vacancy Delay | Vacancy delay 1-120 min, default 15 | min | Write | |
| AV | 9 | Motion Sensitivity Offset | Motion sensitivity 2-254, default 25 | Write | ||
| AV | 10 | Occupancy Sensor Mode | Occupancy sensor mode | Write | 0=Ignore Motion, 1=Motion Operation (default) | |
| AV | 11 | MS/TP MAC Address | MS/TP address, 1-127 | Write | ||
| AV | 12 | MS/TP Baud Rate | 9600, 19200, 38400 or 76800 | Write | ||
| AV | 1003 | Device Instance | Device instance, default 68301-68500 | Write |
No points match these filters.
Object ID lookup: Touch-Plate Aura AUR-IB-FX point IDs by name
BI1Light Threshold 1BI2Light Threshold 2BI3Light Threshold 3BI4Light Threshold 4BI5Motion DetectedAV1Light LevelAV2Light Sensor HysterisisAV3Light Sensor DelayAV4Lux Threshold 1/2AV5Lux Threshold 3/4AV6Lux Threshold 5/6AV7Lux Threshold 7/8AV8Room Vacancy DelayAV9Motion Sensitivity OffsetAV10Occupancy Sensor ModeAV11MS/TP MAC AddressAV12MS/TP Baud RateAV1003Device Instance
Integration notes
- Object list from the 2-page PIC statement "Table of Objects". There is no read/write column; the setting AVs are marked W and the inputs R.
- Object names are kept as printed, including "Hysterisis" and the paired threshold names ("Lux Threshold 1/2" sets the BI 1 threshold).
- The Aura Exterior Sensor AUR-EB-FX PIC sheet prints the same table minus BI 5 Motion Detected and AV 8-10.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)
How many BACnet points does the Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) have?
This list has 18 BACnet objects: 13 analog values, 5 binary inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) BACnet points are writable?
12 of the 18 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP) BACnet documentation?
The source is PIC Statement - Aura Interior Sensor, published free by Touch-Plate at https://touchplate.com/wp-content/uploads/product-documents/Components/Sensors/Aura-Interior-BACnet-PIC-Sheet.pdf.
What are the minimum BACnet points to integrate the Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)?
Start with BI 5 Motion Detected (Occupancy, 1 = room occupied); AV 1 Light Level (Measured light level, lux); BI 1 Light Threshold 1 (1 = light above threshold 1 (AV 4)).
How do I check these points on the real Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Touch-Plate BACnet points lists
- Lighting control station (wall keypad)
Touch-Plate Mystique BACnet smart control station MYS-B (BACnet MS/TP)
Touch-Plate Mystique MYS-B 8-button BACnet MS/TP control stations; the 6-button Ultra ULT-B uses the same objects for buttons 1-6.
Also known as: MYS-B, Mystique BACnet, Touch-Plate Mystique, ULT-B, Ultra BACnet, Touch-Plate Ultra - Lighting relay panel controller
Touch-Plate Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP)
Touch-Plate Supra Universal SPR-UB relay controller (firing card) for 8 lighting relays.
Also known as: SPR-UB, Supra Universal, Supra Universal Firing Card, Touch-Plate Supra
Source: PIC Statement - Aura Interior Sensor. Object names, instances and units are reproduced as published; descriptions are our own.