- Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP)
Lighting relay panel controller · BACnet points list
Touch-Plate Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP) BACnet points list
Updated 12 November 2026
The SPR-UB is the controller card in a Touch-Plate Supra lighting relay panel. Each card is its own BACnet MS/TP device with 8 Binary Outputs, one per relay (relay 1 is listed; BO 2-8 follow the same pattern), plus an override status value. Relays can be switched by hand at the panel, which sets the BO's Override flag.
This page lists 4 BACnet objects for the Touch-Plate Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP) — 3 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Touch-Plate’s own free documentation, linked below.
- Manufacturer
- Touch-Plate
- Model
- Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP)
- Equipment
- Lighting relay panel controller
- Equipment type
- Other equipment
- BACnet objects
- 4 (3 writable)
- Transport
- BACnet MS/TP
- Firmware
- 2.49 (application 1.5b)
- Default device instance
- 68000
- Also known as
- SPR-UB, Supra Universal, Supra Universal Firing Card, Touch-Plate Supra
- Source document
- Supra Universal System Manual · rev. Manual revision 2.0a
Reference only, provided as-is: verify against Touch-Plate’s current documentation and the live device before use. Not official Touch-Plate information. Terms of use.
BMS integration notes: Touch-Plate Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP)
Command each relay through its BO. Write at priority 16 if local switches should still work; a higher priority locks out the switches until the BMS relinquishes. Watch AV 1002 and the BO Override flags for manual overrides at the panel.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 1 | Relay 001 | Relay 1 on/off; BO 2-8 for the other relays | Command |
| AV 1002 | Relay Override | Last relay overridden by hand, 0 = none | Read |
Enable & remote start
Relays are commanded directly through BO 1-8. Commands above priority 16 make the panel ignore its switch inputs for that relay until relinquished.
Network setup
- MS/TP MAC address by DIP switches; baud 9600, 19200, 38400 or 76800 by option DIP switches (power cycle after a change).
- Factory device instance is on a label (68002-68100 when ordered in a panel, DEV68000 default); change it through AV 1003.
- The manual recommends consecutive MAC addresses, Max Master set to the real device count and Max Info Frames 1.
Watch out for
- Panel inputs control relays at priority 16; a BMS write at a higher priority overrides the wall switches.
- A manual override at the panel sets the BO Override status flag; clear it with the RESET button.
- COV subscriptions expire by default; write 1 to AV 100 to allow lifetime 0.
Touch-Plate Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BOmin | 1 | Relay 001 | Relay 1 command and status (BO 1-8 = relays 1-8) | Command | 0=Off, 1=On | |
| AV | 100 | Device Options | 1 = allow infinite COV subscriptions | Write | 0=COVs expire (default), 1=infinite COVs | |
| AVmin | 1002 | Relay Override | Last manually overridden relay; 0 = none | Read | ||
| AV | 1003 | Device Instance | Device instance, factory 68002-68100 | Write |
No points match these filters.
Object ID lookup: Touch-Plate Supra SPR-UB point IDs by name
Integration notes
- The relays are printed as one range, BO 1-8, with the name pattern "Relay 00#" (# = relay 1-8). Only relay 1 is listed; add the relay number for the others.
- The AV 1003 property table prints Object_Name "Device Options", which looks like a copy error; the object table calls it Device Instance.
- There is no read/write column; access is inferred. BOs have a priority array.
- The panel's own inputs drive the relays at priority 16, fixed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Touch-Plate Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP)
How many BACnet points does the Touch-Plate Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP) have?
This list has 4 BACnet objects: 3 analog values, 1 binary output. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Touch-Plate Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP) BACnet points are writable?
3 of the 4 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Touch-Plate Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP) BACnet documentation?
The source is Supra Universal System Manual, revision Manual revision 2.0a, published free by Touch-Plate at https://touchplate.com/wp-content/uploads/product-documents/Panels/Supra/Supra-UB-Manual.pdf.
What are the minimum BACnet points to integrate the Touch-Plate Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP)?
Start with BO 1 Relay 001 (Relay 1 on/off; BO 2-8 for the other relays); AV 1002 Relay Override (Last relay overridden by hand, 0 = none).
How do I enable BMS control of the Touch-Plate Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP)?
Relays are commanded directly through BO 1-8. Commands above priority 16 make the panel ignore its switch inputs for that relay until relinquished.
How do I check these points on the real Supra Universal SPR-UB 8-relay lighting controller (BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Touch-Plate BACnet points lists
- Light level and occupancy sensor
Touch-Plate Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)
Touch-Plate Aura Interior Sensor AUR-IB-FX; the Aura Exterior Sensor AUR-EB-FX uses the same objects without motion and vacancy (no BI 5, AV 8-10).
Also known as: AUR-IB-FX, Aura Interior Sensor, Touch-Plate Aura, AUR-EB-FX, Aura Exterior Sensor - Lighting control station (wall keypad)
Touch-Plate Mystique BACnet smart control station MYS-B (BACnet MS/TP)
Touch-Plate Mystique MYS-B 8-button BACnet MS/TP control stations; the 6-button Ultra ULT-B uses the same objects for buttons 1-6.
Also known as: MYS-B, Mystique BACnet, Touch-Plate Mystique, ULT-B, Ultra BACnet, Touch-Plate Ultra
Source: Supra Universal System Manual · rev. Manual revision 2.0a. Object names, instances and units are reproduced as published; descriptions are our own.