 "manufacturer": "Touch-Plate",
 "manufacturer_slug": "touch-plate",
 "model": "Aura Interior Sensor AUR-IB-FX light level and occupancy sensor (BACnet MS/TP)",
 "model_slug": "aura-interior-sensor-aur-ib-fx",
 "short_model": "Aura AUR-IB-FX",
 "aliases": [
  "AUR-IB-FX",
  "Aura Interior Sensor",
  "Touch-Plate Aura",
  "AUR-EB-FX",
  "Aura Exterior Sensor"
 ],
 "equipment_type": "Light level and occupancy sensor",
 "applies_to": "Touch-Plate Aura Interior Sensor AUR-IB-FX; the Aura Exterior Sensor AUR-EB-FX uses the same objects without motion and vacancy (no BI 5, AV 8-10).",
 "summary": "The Aura Interior Sensor is a ceiling light-level and motion sensor that is its own BACnet MS/TP device. It reports the light level in lux, four lux-threshold flags and a motion flag; thresholds, hysteresis, delays and the occupancy mode are Analog Values the BMS can adjust.",
 "bacnet_transport": [
  "BACnet MS/TP"
 ],
 "firmware": "2.48 (application 1.5d)",
 "default_device_instance": "68301-68500",
 "access_inferred": true,
 "notes": [
  "Object list from the 2-page PIC statement \"Table of Objects\". There is no read/write column; the setting AVs are marked W and the inputs R.",
  "Object names are kept as printed, including \"Hysterisis\" and the paired threshold names (\"Lux Threshold 1/2\" sets the BI 1 threshold).",
  "The Aura Exterior Sensor AUR-EB-FX PIC sheet prints the same table minus BI 5 Motion Detected and AV 8-10."
 ],
 "source": {
  "title": "PIC Statement - Aura Interior Sensor",
  "doc_number": null,
  "revision_date": null,
  "url": "https://touchplate.com/wp-content/uploads/product-documents/Components/Sensors/Aura-Interior-BACnet-PIC-Sheet.pdf"
 },
 "integration": {
  "summary": "Read AV 1 for the light level and BI 5 for occupancy; the threshold flags BI 1-4 are ready-made daylight switches. Inputs support COV subscriptions, so subscribe rather than poll.",
  "minimum_points": [
   {
    "ref": "BI 5",
    "name": "Motion Detected",
    "why": "Occupancy, 1 = room occupied"
   },
   {
    "ref": "AV 1",
    "name": "Light Level",
    "why": "Measured light level, lux"
   },
   {
    "ref": "BI 1",
    "name": "Light Threshold 1",
    "why": "1 = light above threshold 1 (AV 4)"
   }
  ],
  "enable": null,
  "heartbeat": null,
  "remote_sensors": null,
  "setup": [
   "MS/TP MAC address, baud rate and I/O configuration are set with DIP switches; AV 11 and AV 12 read or change them.",
   "MS/TP master at 9600, 19200, 38400 or 76800 baud.",
   "Device instance defaults to 68301-68500 and can be changed through AV 1003."
  ],
  "gotchas": [
   "Setting AV 10 Occupancy Sensor Mode to 0 makes the sensor ignore motion."
  ]
 },
 "points": [
  {
   "type": "BI",
   "instance": 1,
   "name": "Light Threshold 1",
   "description": "1 when ambient light exceeds lux threshold 1 plus hysteresis",
   "units": "",
   "access": "R",
   "states": "1=Room Lit"
  },
  {
   "type": "BI",
   "instance": 2,
   "name": "Light Threshold 2",
   "description": "1 when ambient light exceeds lux threshold 2 plus hysteresis",
   "units": "",
   "access": "R",
   "states": "1=Room Lit"
  },
  {
   "type": "BI",
   "instance": 3,
   "name": "Light Threshold 3",
   "description": "1 when ambient light exceeds lux threshold 3 plus hysteresis",
   "units": "",
   "access": "R",
   "states": "1=Room Lit"
  },
  {
   "type": "BI",
   "instance": 4,
   "name": "Light Threshold 4",
   "description": "1 when ambient light exceeds lux threshold 4 plus hysteresis",
   "units": "",
   "access": "R",
   "states": "1=Room Lit"
  },
  {
   "type": "BI",
   "instance": 5,
   "name": "Motion Detected",
   "description": "Occupancy from the motion sensor",
   "units": "",
   "access": "R",
   "states": "1=Room Occupied"
  },
  {
   "type": "AV",
   "instance": 1,
   "name": "Light Level",
   "description": "Current light level, 0-65535",
   "units": "lux",
   "access": "R",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 2,
   "name": "Light Sensor Hysterisis",
   "description": "Threshold hysteresis 1-100 %, default 1",
   "units": "%",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 3,
   "name": "Light Sensor Delay",
   "description": "Light sensor delay 1-3600 s, default 1",
   "units": "s",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 4,
   "name": "Lux Threshold 1/2",
   "description": "Lux threshold for BI 1, default 50",
   "units": "lux",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 5,
   "name": "Lux Threshold 3/4",
   "description": "Lux threshold for BI 2, default 100",
   "units": "lux",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 6,
   "name": "Lux Threshold 5/6",
   "description": "Lux threshold for BI 3, default 200",
   "units": "lux",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 7,
   "name": "Lux Threshold 7/8",
   "description": "Lux threshold for BI 4, default 500",
   "units": "lux",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 8,
   "name": "Room Vacancy Delay",
   "description": "Vacancy delay 1-120 min, default 15",
   "units": "min",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 9,
   "name": "Motion Sensitivity Offset",
   "description": "Motion sensitivity 2-254, default 25",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 10,
   "name": "Occupancy Sensor Mode",
   "description": "Occupancy sensor mode",
   "units": "",
   "access": "W",
   "states": "0=Ignore Motion, 1=Motion Operation (default)"
  },
  {
   "type": "AV",
   "instance": 11,
   "name": "MS/TP MAC Address",
   "description": "MS/TP address, 1-127",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 12,
   "name": "MS/TP Baud Rate",
   "description": "9600, 19200, 38400 or 76800",
   "units": "",
   "access": "W",
   "states": ""
  },
  {
   "type": "AV",
   "instance": 1003,
   "name": "Device Instance",
   "description": "Device instance, default 68301-68500",
   "units": "",
   "access": "W",
   "states": ""
  }
 ],
 "page": "https://easybacnet.com/bacnet-points-lists/touch-plate/aura-interior-sensor-aur-ib-fx",
 "note": "Provided as-is. Point availability varies by firmware and options; verify against the live device.",
 "disclaimer": "DISCLAIMER: reference only, provided AS IS with no warranty. May contain errors or be out of date. You must verify every point against the manufacturer's current documentation and the live device before use. easybacnet.com accepts no liability for its use and is not affiliated with the manufacturer. Terms: https://easybacnet.com/terms#content"
}