Toshiba RBC-BP2 Black Pear II BMS interface BACnet points list

Updated 6 November 2026

Short answer

The Black Pear II (RBC-BP2) is a BMS interface with a touch screen that connects to the Toshiba TCC-Link (U3/U4) network and serves up to 64 indoor unit addresses over BACnet IP, Modbus RTU/TCP or Trend. Each unit address gets the same block of setup (_w) and state (_r) objects named after the unit name set in the Black Pear, plus two system objects. BACnet is off by default and has to be enabled in the protocol settings.

This page lists 18 BACnet objects for the Toshiba RBC-BP2 Black Pear II BMS interface — 7 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Toshiba’s own free documentation, linked below.

Manufacturer
Toshiba
Model
RBC-BP2 Black Pear II BMS interface
Equipment
VRF / split AC BACnet IP gateway
Equipment type
VRF & split air conditioners
BACnet objects
18 (7 writable)
Transport
BACnet IP
Firmware
Black Pear II V1_00
Default device instance
200
Also known as
RBC-BP2, Black Pear 2, Black Pear II, BlackPear2, RBCBP2
Source document
Black Pear II Display Controller v1_00 Installation & Owners Manual (RBC-BP2) · rev. V1_00
Download CSV 18 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Toshiba’s current documentation and the live device before use. Not official Toshiba information. Terms of use.

BMS integration notes: Toshiba RBC-BP2 Black Pear II BMS interface

Integration in brief

Enable BACnet in the Black Pear protocol settings, set the device ID and unit names, group the units, then map each group master's _w (command) and _r (state) objects. Wait for Sys_HVAC_Network_Status = Ready before sending commands.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 100101nnn (ON_w)Start/stop the unitCommand
MO 100104nnn (MD_w)Command the operating modeCommand
AO 100109nnn (SP_w)Setpoint command, 18-29 °CCommand
MO 100106nnn (FS_w)Fan speed: 1 low, 2 medium, 3 high, 4 autoCommand
BI 100102nnn (ON_r)Confirm run statusRead
AI 100108nnn (RA)Room temperatureRead
MI 100023Sys_HVAC_Network_StatusGateway link status; commands work only when ReadyRead
AI 100103nnn (ECode)Error code (8000 = no error)Read

Enable & remote start

No enable point is needed per unit; only the group master address accepts commands. The digital input is a normally-closed volt-free Global Forced Off contact: opening it switches all fan coils off and inhibits their remotes (refreshed every 10 s). Sys_Force_Off (BV 100024) is the BACnet global off; Global-Off can be enabled or disabled per group.

Heartbeat & communication loss

No BMS heartbeat. Sys_HVAC_Network_Status reads Waiting/Searching after a restart; commands sent before it reads Ready are ignored.

Network setup

Watch out for

Toshiba RBC-BP2 Black Pear II BMS interface BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

18 of 18 shown
Type
Other
Access
Show
Toshiba RBC-BP2 Black Pear II BMS interface BACnet Points List
DescriptionStates
BOmin100101nnn (ON_w)On/off commandCommandInactive=Off, Active=On
BImin100102nnn (ON_r)On/off stateReadInactive=Off, Active=On
AImin100103nnn (ECode)4-digit error code (8000 = no error, 6999 = unit not present)Read
MOmin100104nnn (MD_w)Operation mode command (7-8 not settable, 9-11 VN units)Command1=Fan, 2=Cool, 3=Heat, 4=Dry, 5=Auto, 6=N/A, 7=Auto Cool, 8=Auto Heat, 9=Heat Exchange, 10=VN-Auto, 11=VN-Bypass
MI100105nnn (MD_r)Operation mode stateRead1=Fan, 2=Cool, 3=Heat, 4=Dry, 5=Auto, 6=N/A, 7=Auto Cool, 8=Auto Heat, 9=Heat Exchange, 10=VN-Auto, 11=VN-Bypass
MOmin100106nnn (FS_w)Fan speed commandCommand1=Low, 2=Medium, 3=High, 4=Auto
MI100107nnn (FS_r)Fan speed stateRead1=Low, 2=Medium, 3=High, 4=Auto
AImin100108nnn (RA)Room temperature, -35.0 to 92.0°CRead
AOmin100109nnn (SP_w)Setpoint command, 18.0 to 29.0°CCommand
AI100110nnn (SP_r)Setpoint state, 18.0 to 29.0°CRead
BO100111nnn (LI_wLocal remote controller inhibit commandCommandInactive=Off, Active=Inhibit
BI100112nnn (LI_r)Local remote controller inhibit stateReadInactive=Off, Active=Inhibited
MO100113nnn (AD_w)Air direction commandCommand1=Horizontal, 2=22.5 deg, 3=45 deg, 4=67.5 deg, 5=Vertical, 6=Swing, 7=Hold
MI100114nnn (AD_r)Air direction stateRead1=Horizontal, 2=22.5 deg, 3=45 deg, 4=67.5 deg, 5=Vertical, 6=Swing, 7=Hold
CSV100118nnn (Error Text)Manufacturer error code textRead
BI100119nnn (Error State)Unit error stateReadInactive=Ok, Active=In Error
MImin100023Sys_HVAC_Network_StatusLink status to the TCC-Link network; commands ignored until ReadyRead1=Waiting, 2=Searching, 3=Ready, 4=Unknown
BV100024Sys_Force_OffGlobal off commandWriteInactive=Off, Active=On
Object ID lookup: Toshiba RBC-BP2 Black Pear II point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the RBC-BP2 Black Pear II BMS interface and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Toshiba RBC-BP2 Black Pear II BMS interface

How many BACnet points does the Toshiba RBC-BP2 Black Pear II BMS interface have?

This list has 18 BACnet objects: 3 analog inputs, 1 analog output, 3 binary inputs, 2 binary outputs, 1 binary value, 4 multi-state inputs, 3 multi-state outputs, 1 characterstring value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Toshiba RBC-BP2 Black Pear II BMS interface BACnet points are writable?

7 of the 18 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Toshiba RBC-BP2 Black Pear II BMS interface BACnet documentation?

The source is Black Pear II Display Controller v1_00 Installation & Owners Manual (RBC-BP2), revision V1_00, published free by Toshiba at https://www.toshiba-aircon.co.uk/content/dam/public-toshiba/gb/documents/products/controls/central-controller/rbc-bp2-black-pear-bms-interface/RBC-BP2_BlackPear2_user_manual_v1_00.pdf/_jcr_content/renditions/original./RBC-BP2_BlackPear2_user_manual_v1_00.pdf.

What are the minimum BACnet points to integrate the Toshiba RBC-BP2 Black Pear II BMS interface?

Start with BO 100101 nnn (ON_w) (Start/stop the unit); MO 100104 nnn (MD_w) (Command the operating mode); AO 100109 nnn (SP_w) (Setpoint command, 18-29 °C); MO 100106 nnn (FS_w) (Fan speed: 1 low, 2 medium, 3 high, 4 auto); BI 100102 nnn (ON_r) (Confirm run status); AI 100108 nnn (RA) (Room temperature); MI 100023 Sys_HVAC_Network_Status (Gateway link status; commands work only when Ready); AI 100103 nnn (ECode) (Error code (8000 = no error)).

How do I enable BMS control of the Toshiba RBC-BP2 Black Pear II BMS interface?

No enable point is needed per unit; only the group master address accepts commands. The digital input is a normally-closed volt-free Global Forced Off contact: opening it switches all fan coils off and inhibits their remotes (refreshed every 10 s). Sys_Force_Off (BV 100024) is the BACnet global off; Global-Off can be enabled or disabled per group.

Does the Toshiba RBC-BP2 Black Pear II BMS interface need a BACnet heartbeat or have a communication timeout?

No BMS heartbeat. Sys_HVAC_Network_Status reads Waiting/Searching after a restart; commands sent before it reads Ready are ignored.