VRF BACnet gateway · BACnet points list

Toshiba BN interface BMS-IFBN1281U BACnet points list

Updated 28 October 2026

Short answer

The BN interface is a Toshiba Carrier gateway that converts the TU2C-LINK / TCC-LINK central control line to BACnet/IP, serving up to 128 indoor units (64 on TCC-LINK). Every indoor unit gets the same block of objects, with the instance built from the unit's central control address and a fixed per-function code. Objects only exist for units found during the gateway's air conditioner search mode.

This page lists 68 BACnet objects for the Toshiba BN interface BMS-IFBN1281U — 26 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Toshiba’s own free documentation, linked below.

Manufacturer
Toshiba
Model
BN interface BMS-IFBN1281U
Equipment
VRF BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
68 (26 writable)
Transport
BACnet IP
Firmware
Not stated
Default device instance
100
Also known as
BMS-IFBN1281U-E, BMS-IFBN1281U-TR, Toshiba BACnet interface, Toshiba Carrier BN interface, TU2C-LINK BACnet
Source document
BN interface Service Manual, BMS-IFBN1281U-E / BMS-IFBN1281U-TR · A10-2301-3 · rev. 2024-05 (Revision 3)
Download CSV 68 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Toshiba BN interface BMS-IFBN1281U

Integration in brief

Give every indoor unit a central control address, run the BN interface's air conditioner search mode, then map each unit's block of objects (instance = address x 256 + code). Command through the output objects (start/stop, mode, fan, setpoint) and read the matching input objects back for status. Watch Alarm/BI, Alarm_Code/MI and Indoor_Communication_Failure for faults.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 386State/BO_***Start/stop the indoor unitCommand
MO 387Mode/MO_***Sets heat/cool/fan/dry/autoCommand
AO 388Temp/AO_***Writes the setpointCommand
MO 389Fan/MO_***Sets fan speedCommand
BI 258State/BI_***Confirms the unit's on/off stateRead
AI 264Room_Temp/AI_***Room temperature at the unitRead
BI 320Alarm/BI_***Unit alarm flagRead
MI 257Alarm_Code/MI_***Check code: 1 = no alarm, other values encode the faultRead
BI 321Indoor_Communication_Failure_***Lost communication with the indoor unitRead

Enable & remote start

No enable point is described; units can be commanded once they have a central control address and were found by air conditioner search mode. Inhibit/MO can prohibit local remote-controller changes to start/stop, mode and setpoint.

Network setup

Watch out for

Toshiba BN interface BMS-IFBN1281U BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

68 of 68 shown
Type
Other
Access
Show
Toshiba BN interface BMS-IFBN1281U BACnet Points List
DescriptionStates
DEV100AC_CONTROLERBN interface device object (default instance = IP last byte)Read
BImin258State/BI_***Indoor unit on/off statusReadINACTIVE=Stop, ACTIVE=Start
BOmin386State/BO_***Indoor unit start/stop commandCommandINACTIVE=Stop, ACTIVE=Start
MI259Mode/MI_***Operation mode statusReadHeat / Cool / Fan / Dry / Auto
MOmin387Mode/MO_***Operation mode commandCommandHeat / Cool / Fan / Dry / Auto
MI261Fan/MI_***Fan speed statusReadAuto / HH / H / L / LL / H+ / L+
MOmin389Fan/MO_***Fan speed commandCommandAuto / HH / H / L / LL / H+ / L+
AI260Temp/AI_***Setpoint status°C/°FRead
AOmin388Temp/AO_***Setpoint command°C/°FCommand
AI366AutoCoolSetpoint/AI_***Auto-mode cooling setpoint status°C/°FRead
AO494AutoCoolSetpoint/AO_***Auto-mode cooling setpoint command°C/°FCommand
AI367AutoHeatSetpoint/AI_***Auto-mode heating setpoint status°C/°FRead
AO495AutoHeatSetpoint/AO_***Auto-mode heating setpoint command°C/°FCommand
AImin264Room_Temp/AI_***Room temperature (-39 to 150 °C range)°C/°FRead
MI265Inhibit/MI_***Local remote permit/prohibit statusReadPermit/prohibit of start/stop, operation mode, temperature setting
MO393Inhibit/MO_***Local remote permit/prohibit commandCommandPermit/prohibit of start/stop, operation mode, temperature setting
BI276Filter/BI_***Filter signReadNormal / Filter Sign
BO405Filter/BO_***Filter sign resetCommand- / Filter Sign Reset
BImin320Alarm/BI_***Alarm statusReadNo Alarm / Alarm
MImin257Alarm_Code/MI_***Check codeReadNo Check Code / Check Code
MI263Flap/MI_***Louver position statusReadSwing / F1 / F2 / F3 / F4 / F5 / Stop
MO391Flap/MO_***Louver position commandCommandSwing / F1 / F2 / F3 / F4 / F5 / Stop
BI296VentilationState/BI_***Ventilation on/off status (option)ReadINACTIVE=Stop, ACTIVE=Start
BO424VentilationState/BO_***Ventilation start/stop (option)CommandINACTIVE=Stop, ACTIVE=Start
MI297VentilationMode/MI_***Ventilation mode status (option)ReadBypass Mode / Heat Exchange Mode / Automatic Mode / 24-hours / Nighttime Heat purge
MO425VentilationMode/MO_***Ventilation mode command (option)CommandBypass Mode / Heat Exchange Mode / Automatic Mode
MI332VentilationFan/MI_***Ventilation fan speed status (option)ReadH / M / Unbalanced
MO460VentilationFan/MO_***Ventilation fan speed command (option)CommandH / M / Unbalanced
BI340IndoorThermoState/BI_***Indoor unit thermo on/off statusReadThermo ON / Thermo OFF
MI341IndoorSaveState/MI_***Save operation rate status (option)ReadNo Save (100%) / XX% Save (100-50%) / 50% Save / 100% Save (forced thermo off)
MO469IndoorSaveState/MO_***Save operation rate command (option)CommandNo Save (100%) / XX% Save (100-50%) / 50% Save / 100% Save (forced thermo off)
BImin321Indoor_Communication_Failure_***Indoor unit communication failureReadNormal / Alarm
MI266Facility_request /MI_***Facility request levelRead1 (Thermo off) to 16
MI355Notice_Code1/MI_***Notice code 1 (TU2C-LINK models)ReadNo Notice Code / Notice Code
MI356Notice_Code1/MI_***Notice code 2 (TU2C-LINK models)ReadNo Notice Code / Notice Code
MI357Notice_Code1/MI_***Notice code 3 (TU2C-LINK models)ReadNo Notice Code / Notice Code
MI358Notice_Code1/MI_***Notice code 4 (TU2C-LINK models)ReadNo Notice Code / Notice Code
MI359Notice_Code1/MI_***Notice code 5 (TU2C-LINK models)ReadNo Notice Code / Notice Code
BI342AtwZone_State/BI_***ATW Zone1/2 on/off statusReadINACTIVE=Stop, ACTIVE=Start
BO470AtwZone_State/BO_***ATW Zone1/2 start/stopCommandINACTIVE=Stop, ACTIVE=Start
BI343AtwHWS_State/BI_***ATW hot water on/off statusReadINACTIVE=Stop, ACTIVE=Start
BO471AtwHWS_State/BO_***ATW hot water start/stopCommandINACTIVE=Stop, ACTIVE=Start
BI350AtwAutoTemp/BI_***ATW auto temp setting statusReadINACTIVE=OFF, ACTIVE=ON
BO478AtwAutoTemp/BO_***ATW auto temp setting on/offCommandINACTIVE=OFF, ACTIVE=ON
BI351AtwNightSetback/BI_***ATW night setback statusReadINACTIVE=OFF, ACTIVE=ON
BO479AtwNightSetback/BO_***ATW night setback on/offCommandINACTIVE=OFF, ACTIVE=ON
BI353AtwFrostProtection/BI_***ATW frost protection statusReadINACTIVE=OFF, ACTIVE=ON
BO481AtwFrostProtection/BO_***ATW frost protection on/offCommandINACTIVE=OFF, ACTIVE=ON
BI354AtwAntiBacteria/BI_***ATW anti-bacteria statusReadINACTIVE=OFF, ACTIVE=ON
BO482AtwAntiBacteria/BO_***ATW anti-bacteria on/offCommandINACTIVE=OFF, ACTIVE=ON
AI344AtwZone1_Setpoint/AI_***ATW Zone1 setpoint status°C/°FRead
AO472AtwZone1_Setpoint/AO_***ATW Zone1 setpoint command°C/°FCommand
AI345AtwZone2_Setpoint/AI_***ATW Zone2 setpoint status°C/°FRead
AO473AtwZone2_Setpoint/AO_***ATW Zone2 setpoint command°C/°FCommand
AI346AtwHWS_Setpoint/AI_***ATW hot water setpoint status°C/°FRead
AO474AtwHWS_Setpoint/AO_***ATW hot water setpoint command°C/°FCommand
AI347AtwZone1_CtrlTemp/AI_***ATW Zone1 control temperature°C/°FRead
AI348AtwZone2_CtrlTemp/AI_***ATW Zone2 control temperature°C/°FRead
AI349AtwHWS_CtrlTemp/AI_***ATW hot water control temperature°C/°FRead
BI361RacPureFilter/BI_***RAC pure filter statusReadINACTIVE=OFF, ACTIVE=ON
BI362RacHiPower/BI_***RAC Hi-Power statusReadINACTIVE=OFF, ACTIVE=ON
BO490RacHiPower/BO_***RAC Hi-Power on/offCommandINACTIVE=OFF, ACTIVE=ON
BI363RacEco/BI_***RAC ECO statusReadINACTIVE=OFF, ACTIVE=ON
BO491RacEco/BO_***RAC ECO on/offCommandINACTIVE=OFF, ACTIVE=ON
BI364RacQuietFcu/BI_***RAC quiet indoor fan statusReadINACTIVE=OFF, ACTIVE=ON
BO492RacQuietFcu/BO_***RAC quiet indoor fan on/offCommandINACTIVE=OFF, ACTIVE=ON
BI365RacSilenceCdu/BI_***RAC silent outdoor unit statusReadINACTIVE=OFF, ACTIVE=ON
BO493RacSilenceCdu/BO_***RAC silent outdoor unit on/offCommandINACTIVE=OFF, ACTIVE=ON

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BN interface BMS-IFBN1281U and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Toshiba BN interface BMS-IFBN1281U

How many BACnet points does the Toshiba BN interface BMS-IFBN1281U have?

This list has 68 BACnet objects: 10 analog inputs, 6 analog outputs, 17 binary inputs, 13 binary outputs, 1 device, 14 multi-state inputs, 7 multi-state outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Toshiba BN interface BMS-IFBN1281U BACnet points are writable?

26 of the 68 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Toshiba BN interface BMS-IFBN1281U BACnet documentation?

The source is BN interface Service Manual, BMS-IFBN1281U-E / BMS-IFBN1281U-TR (A10-2301-3), revision 2024-05 (Revision 3), published free by Toshiba at https://www.toshiba-airconditioning.eu/@@download-proxy?uid=bfc26091451b41b1814e41f0d95432ab.

What are the minimum BACnet points to integrate the Toshiba BN interface BMS-IFBN1281U?

Start with BO 386 State/BO_*** (Start/stop the indoor unit); MO 387 Mode/MO_*** (Sets heat/cool/fan/dry/auto); AO 388 Temp/AO_*** (Writes the setpoint); MO 389 Fan/MO_*** (Sets fan speed); BI 258 State/BI_*** (Confirms the unit's on/off state); AI 264 Room_Temp/AI_*** (Room temperature at the unit); BI 320 Alarm/BI_*** (Unit alarm flag); MI 257 Alarm_Code/MI_*** (Check code: 1 = no alarm, other values encode the fault); BI 321 Indoor_Communication_Failure_*** (Lost communication with the indoor unit).

How do I enable BMS control of the Toshiba BN interface BMS-IFBN1281U?

No enable point is described; units can be commanded once they have a central control address and were found by air conditioner search mode. Inhibit/MO can prohibit local remote-controller changes to start/stop, mode and setpoint.

How do I check these points on the real BN interface BMS-IFBN1281U?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: BN interface Service Manual, BMS-IFBN1281U-E / BMS-IFBN1281U-TR · A10-2301-3 · rev. 2024-05 (Revision 3). Object names, instances and units are reproduced as published; descriptions are our own.