Pump system controller (variable speed, differential pressure) · BACnet points list

Tigerflow Mark VI pump system controller BACnet points list

Updated 12 November 2026

Short answer

The Mark VI controls up to three VFD pumps on zone differential pressure. Over BACnet it reports pump run commands, VFD run and fault feedback, HOA positions, zone differential pressures, flow, pump speeds and supply/return temperatures. The BMS can write a system disable (BV 41) and a differential pressure setpoint for zones 1-3 (AV 41-43).

This page lists 49 BACnet objects for the Tigerflow Mark VI pump system controller — 4 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Tigerflow’s own free documentation, linked below.

Manufacturer
Tigerflow
Model
Mark VI pump system controller
Equipment
Pump system controller (variable speed, differential pressure)
Equipment type
VFDs & pumps
BACnet objects
49 (4 writable)
Transport
—
Firmware
Not stated
Also known as
Mark VI, Mark 6, Tigerflow Mark VI, Tigerflow differential pressure pump controller
Source document
MARK VI - BACNet POINT LIST · rev. 2018-04-19
Download CSV 49 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Tigerflow’s current documentation and the live device before use. Not official Tigerflow information. Terms of use.

BMS integration notes: Tigerflow Mark VI pump system controller

Integration in brief

Write BV 41 to disable or release the system and the zone differential pressure setpoints AV 41-43 if the BMS owns the setpoint. Read zone pressures, flow, pump run and fault flags and the general alarm.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 41Remote System Disable - BAS SignalSystem disable from the BMSWrite
AV 41Remote BAS Zone 1 SetpointZone 1 differential pressure setpoint, psiWrite
AV 60Zone 1 Differential PressureZone 1 differential pressure, psiRead
AV 64Flow RateSystem flow, gpmRead
BV 21Pump 1 Run CommandPump 1 called to run (repeat for pumps 2-3)Read
AV 65Pump 1 Speed Signal (%)Pump 1 speed signal, % (repeat for pumps 2-3)Read
BV 71Pump 1 FaultPump 1 fault (repeat for pumps 2-3)Read
BV 86General/Fatal AlarmAny general or fatal alarmRead

Enable & remote start

BV 41 Remote System Disable - BAS Signal is the only writable binary; the list gives 1 = ON but does not say how it combines with the hard-wired disable input.

Sensors & values from the BMS

AV 41-43 accept zone differential pressure setpoints from the BAS; the list does not say how the controller chooses between local and BAS setpoints.

Watch out for

Tigerflow Mark VI pump system controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

49 of 49 shown
Type
AnalogBinary
Access
Show
Tigerflow Mark VI pump system controller BACnet Points List
DescriptionStates
BV1VFD 1 Differential Pressure Switch InputDifferential pressure switch input, VFD 1Read1=On
BV2VFD 2 Differential Pressure Switch InputDifferential pressure switch input, VFD 2Read1=On
BV3VFD 3 Differential Pressure Switch InputDifferential pressure switch input, VFD 3Read1=On
BV4Remote System Disable InputHard-wired remote disable inputRead1=On
BV6VFD 1 Run Status InputRun status input from VFD 1Read1=On
BV7VFD 2 Run Status InputRun status input from VFD 2Read1=On
BV8VFD 3 Run Status InputRun status input from VFD 3Read1=On
BVmin21Pump 1 Run CommandController run output to pump 1Read1=On
BV22Pump 2 Run CommandController run output to pump 2Read1=On
BV23Pump 3 Run CommandController run output to pump 3Read1=On
BV25General/Fatal Alarm OutputGeneral or fatal alarm relay outputRead1=On
BV26Alarm Horn OutputAlarm horn outputRead1=On
BVmin41Remote System Disable - BAS SignalSystem disable written by the BASWrite1=On
BV61Pump 1 in AutoPump 1 HOA in AutoRead1=On
BV62Pump 1 in HandPump 1 HOA in HandRead1=On
BV63Pump 2 in AutoPump 2 HOA in AutoRead1=On
BV64Pump 2 in HandPump 2 HOA in HandRead1=On
BV65Pump 3 in AutoPump 3 HOA in AutoRead1=On
BV66Pump 3 in HandPump 3 HOA in HandRead1=On
BVmin71Pump 1 FaultPump 1 faultRead1=On
BV72Pump 2 FaultPump 2 faultRead1=On
BV73Pump 3 FaultPump 3 faultRead1=On
BV75VFD 1 FaultVFD 1 faultRead1=On
BV76VFD 2 FaultVFD 2 faultRead1=On
BV77VFD 3 FaultVFD 3 faultRead1=On
BV81Supply High Temperature AlarmHigh supply water temperature alarmRead1=On
BV82Return High Temperature AlarmHigh return water temperature alarmRead1=On
BV85Alarm AcknowledgedAlarm acknowledgedRead1=On
BVmin86General/Fatal AlarmGeneral or fatal alarm activeRead1=On
BV87Alarm SilencedAlarm horn silencedRead1=On
BV88Alarm ResetAlarm reset stateRead1=On
BV89Remote System Disable InputRemote system disable activeRead1=On
BV91Zone 1 Pressure Sensor FailureZone 1 pressure sensor failedRead1=On
BV92Zone 2 Pressure Sensor FailureZone 2 pressure sensor failedRead1=On
BV93Zone 3 Pressure Sensor FailureZone 3 pressure sensor failedRead1=On
BV94Zone 4 Pressure Sensor FailureZone 4 pressure sensor failedRead1=On
BV100Phase Loss Sensor InputPhase loss sensor inputRead1=On
AVmin41Remote BAS Zone 1 SetpointZone 1 differential pressure setpoint from BASpsiWrite
AV42Remote BAS Zone 2 SetpointZone 2 differential pressure setpoint from BASpsiWrite
AV43Remote BAS Zone 3 SetpointZone 3 differential pressure setpoint from BASpsiWrite
AVmin60Zone 1 Differential PressureZone 1 differential pressurepsiRead
AV61Zone 2 Differential PressureZone 2 differential pressurepsiRead
AV62Zone 3 Differential PressureZone 3 differential pressurepsiRead
AVmin64Flow RateSystem flow rategpmRead
AVmin65Pump 1 Speed Signal (%)Speed signal to pump 1 VFD%Read
AV66Pump 2 Speed Signal (%)Speed signal to pump 2 VFD%Read
AV67Pump 3 Speed Signal (%)Speed signal to pump 3 VFD%Read
AV78Supply Temperature (degF)Supply water temperature°FRead
AV79Return Temperature (degF)Return water temperature°FRead
Object ID lookup: Tigerflow Mark VI pump system controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Mark VI pump system controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Tigerflow Mark VI pump system controller

How many BACnet points does the Tigerflow Mark VI pump system controller have?

This list has 49 BACnet objects: 12 analog values, 37 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Tigerflow Mark VI pump system controller BACnet points are writable?

4 of the 49 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Tigerflow Mark VI pump system controller BACnet documentation?

The source is MARK VI - BACNet POINT LIST, revision 2018-04-19, published free by Tigerflow at https://tigerflow.com/demo/wp-content/uploads/2018/05/Mark-VI-BACNet-Point-List-20180419-1.pdf.

What are the minimum BACnet points to integrate the Tigerflow Mark VI pump system controller?

Start with BV 41 Remote System Disable - BAS Signal (System disable from the BMS); AV 41 Remote BAS Zone 1 Setpoint (Zone 1 differential pressure setpoint, psi); AV 60 Zone 1 Differential Pressure (Zone 1 differential pressure, psi); AV 64 Flow Rate (System flow, gpm); BV 21 Pump 1 Run Command (Pump 1 called to run (repeat for pumps 2-3)); AV 65 Pump 1 Speed Signal (%) (Pump 1 speed signal, % (repeat for pumps 2-3)); BV 71 Pump 1 Fault (Pump 1 fault (repeat for pumps 2-3)); BV 86 General/Fatal Alarm (Any general or fatal alarm).

How do I enable BMS control of the Tigerflow Mark VI pump system controller?

BV 41 Remote System Disable - BAS Signal is the only writable binary; the list gives 1 = ON but does not say how it combines with the hard-wired disable input.

Can the BMS supply sensor values to the Tigerflow Mark VI pump system controller?

AV 41-43 accept zone differential pressure setpoints from the BAS; the list does not say how the controller chooses between local and BAS setpoints.

How do I check these points on the real Mark VI pump system controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Tigerflow BACnet points lists

Source: MARK VI - BACNet POINT LIST · rev. 2018-04-19. Object names, instances and units are reproduced as published; descriptions are our own.