Booster pump system controller · BACnet points list

Tigerflow Mark V booster pump controller BACnet points list

Updated 12 November 2026

Short answer

The Mark V is the controller on Tigerflow multi-pump booster packages (up to four VFD pumps). Its BACnet list is monitoring only: every object is read-only. It reports pump run commands and VFD run feedback, HOA positions, pump faults, pressure alarms, suction and system pressure, the pressure setpoint, flow, per-pump speed and run hours.

This page lists 47 BACnet objects for the Tigerflow Mark V booster pump controller — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Tigerflow’s own free documentation, linked below.

Manufacturer
Tigerflow
Model
Mark V booster pump controller
Equipment
Booster pump system controller
Equipment type
VFDs & pumps
BACnet objects
47 (0 writable)
Transport
—
Firmware
Not stated
Also known as
Mark V, Mark 5, Tigerflow Mark V, Mark V booster, Tigerflow booster pump controller
Source document
MARK V - BACNET POINT LIST · rev. 2018-04-19
Download CSV 47 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Tigerflow’s current documentation and the live device before use. Not official Tigerflow information. Terms of use.

BMS integration notes: Tigerflow Mark V booster pump controller

Integration in brief

Monitoring only. Map system and suction pressure, the active setpoint and flow, the per-pump run commands and faults, and the general and fatal alarm flags.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 2System PressureSystem discharge pressure, psiRead
AV 3Pressure Set PointActive pressure setpoint, psi (read-only)Read
AV 1Suction PressureSuction pressure, psiRead
AV 4Flow RateSystem flow, gpmRead
BV 17Pump 1 Run CommandPump 1 called to run (repeat for pumps 2-4)Read
AV 5Pump 1 Speed Signal (%)Pump 1 speed signal, % (repeat for pumps 2-4)Read
BV 51Pump 1 FaultPump 1 fault (repeat for pumps 2-4)Read
BV 63General AlarmAny general alarmRead
BV 64Fatal AlarmFatal alarm activeRead

Watch out for

Tigerflow Mark V booster pump controller BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

47 of 47 shown
Type
AnalogBinary
Show
Tigerflow Mark V booster pump controller BACnet Points List
DescriptionStates
BV1VFD 1 Run Status InputRun status input from VFD 1Read1=On
BV2VFD 2 Run Status InputRun status input from VFD 2Read1=On
BV3VFD 3 Run Status InputRun status input from VFD 3Read1=On
BV4VFD 4 Run Status InputRun status input from VFD 4Read1=On
BV5Remote System Disable InputHard-wired remote disable inputRead1=On
BV6Phase Loss Sensor InputPhase loss sensor inputRead1=On
BV7Flow Switch InputFlow switch inputRead1=On
BV8Level Switch InputLevel switch inputRead1=On
BVmin17Pump 1 Run CommandController run output to pump 1Read1=On
BV18Pump 2 Run CommandController run output to pump 2Read1=On
BV19Pump 3 Run CommandController run output to pump 3Read1=On
BV20Pump 4 Run CommandController run output to pump 4Read1=On
BV21General/Fatal Alarm OutputGeneral or fatal alarm relay outputRead1=On
BV22Alarm Horn OutputAlarm horn outputRead1=On
BV33Pump 1 in AutoPump 1 HOA in AutoRead1=On
BV34Pump 1 in HandPump 1 HOA in HandRead1=On
BV35Pump 2 in AutoPump 2 HOA in AutoRead1=On
BV36Pump 2 in HandPump 2 HOA in HandRead1=On
BV37Pump 3 in AutoPump 3 HOA in AutoRead1=On
BV38Pump 3 in HandPump 3 HOA in HandRead1=On
BV39Pump 4 in AutoPump 4 HOA in AutoRead1=On
BV40Pump 4 in HandPump 4 HOA in HandRead1=On
BVmin51Pump 1 FaultPump 1 faultRead1=On
BV52Pump 2 FaultPump 2 faultRead1=On
BV53Pump 3 FaultPump 3 faultRead1=On
BV54Pump 4 FaultPump 4 faultRead1=On
BV55Phase Loss AlarmPhase loss alarmRead1=On
BV56Low Suction Pressure AlarmLow suction pressure alarmRead1=On
BV57Low System Pressure AlarmLow system pressure alarmRead1=On
BV58High System Pressure AlarmHigh system pressure alarmRead1=On
BV59System Pressure Sensor Failure AlarmSystem pressure transducer failureRead1=On
BV60Suction Pressure Sensor Failure AlarmSuction pressure transducer failureRead1=On
BV62Alarm SilencedAlarm horn silencedRead1=On
BVmin63General AlarmGeneral alarm activeRead1=On
BVmin64Fatal AlarmFatal alarm activeRead1=On
AVmin1Suction PressurePump suction pressurepsiRead
AVmin2System PressureSystem (discharge) pressurepsiRead
AVmin3Pressure Set PointActive system pressure setpointpsiRead
AVmin4Flow RateSystem flow rategpmRead
AVmin5Pump 1 Speed Signal (%)Speed signal to pump 1 VFD%Read
AV6Pump 2 Speed Signal (%)Speed signal to pump 2 VFD%Read
AV7Pump 3 Speed Signal (%)Speed signal to pump 3 VFD%Read
AV8Pump 4 Speed Signal (%)Speed signal to pump 4 VFD%Read
AV9Pump 1 Run Time (Hrs.)Pump 1 run hourshRead
AV10Pump 2 Run Time (Hrs.)Pump 2 run hourshRead
AV11Pump 3 Run Time (Hrs.)Pump 3 run hourshRead
AV12Pump 4 Run Time (Hrs.)Pump 4 run hourshRead
Object ID lookup: Tigerflow Mark V booster pump controller point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Mark V booster pump controller and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Tigerflow Mark V booster pump controller

How many BACnet points does the Tigerflow Mark V booster pump controller have?

This list has 47 BACnet objects: 12 analog values, 35 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Tigerflow Mark V booster pump controller BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Tigerflow Mark V booster pump controller BACnet documentation?

The source is MARK V - BACNET POINT LIST, revision 2018-04-19, published free by Tigerflow at https://tigerflow.com/demo/wp-content/uploads/2018/05/Mark-V-BACNet-Point-List-20180419-1.pdf.

What are the minimum BACnet points to integrate the Tigerflow Mark V booster pump controller?

Start with AV 2 System Pressure (System discharge pressure, psi); AV 3 Pressure Set Point (Active pressure setpoint, psi (read-only)); AV 1 Suction Pressure (Suction pressure, psi); AV 4 Flow Rate (System flow, gpm); BV 17 Pump 1 Run Command (Pump 1 called to run (repeat for pumps 2-4)); AV 5 Pump 1 Speed Signal (%) (Pump 1 speed signal, % (repeat for pumps 2-4)); BV 51 Pump 1 Fault (Pump 1 fault (repeat for pumps 2-4)); BV 63 General Alarm (Any general alarm); BV 64 Fatal Alarm (Fatal alarm active).

How do I check these points on the real Mark V booster pump controller?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Tigerflow BACnet points lists

Source: MARK V - BACNET POINT LIST · rev. 2018-04-19. Object names, instances and units are reproduced as published; descriptions are our own.