Variable frequency drive · BACnet points list

TECO-Westinghouse L510 inverter (built-in BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The L510 is a compact inverter with BACnet MS/TP built into its RS-485 port. Its object list follows the F510 layout but is smaller: one analog output terminal, eight preset speeds (AO 7-14), five digital inputs and one relay. Analog inputs are scaled in percent and frequencies run to 599 Hz.

This page lists 53 BACnet objects for the TECO-Westinghouse L510 inverter (built-in BACnet MS/TP) — 23 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TECO-Westinghouse’s own free documentation, linked below.

Manufacturer
TECO-Westinghouse
Model
L510 inverter (built-in BACnet MS/TP)
Equipment
Variable frequency drive
Equipment type
VFDs & pumps
BACnet objects
53 (23 writable)
Transport
BACnet MS/TP
Firmware
0.14 (Firmware_Revision in the device object table)
Also known as
L510, TECO L510, TECO-Westinghouse L510, L510 BACnet, TECO-L510-AC001
Source document
L510 Communication Addendum (Modbus RTU/ASCII, BACnet, Metasys N2, Profibus) · TECO-L510-AC001 · rev. Ver01 2015-06
Download CSV 53 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TECO-Westinghouse’s current documentation and the live device before use. Not official TECO-Westinghouse information. Terms of use.

BMS integration notes: TECO-Westinghouse L510 inverter (built-in BACnet MS/TP)

Integration in brief

Wire the drive's RS-485 port to the MS/TP trunk and select BACnet as the drive's communication mode. Set the run and frequency command sources to communication (AO 23 / AO 26 mirror those parameters), then write the speed to AO 0 and start/stop with BV 0. Read BI 0, AI 4, AI 5 and BI 2 / AI 2 for status and faults.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0RUN/STOPRun/stop commandWrite
AO 0Set frequencyFrequency command, HzWrite
BI 0Run/StopRunning statusRead
AI 4FrequencyOutput frequency, HzRead
AI 5CurrentOutput current, ARead
BI 2statusDrive fault (OK / Fault)Read
AI 2Error codeLatest fault codeRead

Enable & remote start

Set the main run command source (AO 23) and main frequency command source (AO 26) to the communication option; the addendum does not print the setting values for the L510.

Network setup

Watch out for

TECO-Westinghouse L510 inverter (built-in BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

53 of 53 shown
Type
Access
Show
TECO-Westinghouse L510 inverter (built-in BACnet MS/TP) BACnet Points List
DescriptionStates
AI0TM2 AINAVI input (0-100)%Read
AI1TM2 AIN2ACI input (0-100)%Read
AImin2Error codeRecent fault message (0-43)Read
AI3Freq cmdFrequency command (0-599)HzRead
AImin4FrequencyOutput frequency (0-599)HzRead
AImin5CurrentOutput currentARead
AI6Control ModeControl mode (0-1)Read
AI7Motor R-VoltMotor rated voltageVRead
AI8Motor R-HPMotor rated powerhpRead
AI9Motor R-RPMMotor rated rotation speedrpmRead
AI10Motor R-HzMotor rated frequencyHzRead
AI11CarrierFreqCarrier frequency (1-16)kHzRead
AI12Comm StationInverter communication station (1-254)Read
AI13BaudRateBaud rate setting (0-3)Read
AI14BacnetSelCommunication mode selection (0-1)Read
AI15DevInstanceInverter number (1-254)Read
AOmin0Set frequencyFrequency command (0-599)HzWrite
AO1TB2 AO1Output voltage 1 (0-10)VRead
AO3Motor R-AmpMotor rated current (range not printed)AWrite
AO4PwrL SelMomentary stop and restart selection (0-1)Read
AO5RestartSelNumber of fault auto-restart attempts (0-10)Read
AO6RestartDelayFault auto-restart time (0-800)sRead
AO7FreqCommand1Preset speed frequency, stage 0 (0-599)HzWrite
AO8FreqCommand2Preset speed frequency, stage 1 (0-599)HzWrite
AO9FreqCommand3Preset speed frequency, stage 2 (0-599)HzWrite
AO10FreqCommand4Preset speed frequency, stage 3 (0-599)HzWrite
AO11FreqCommand5Preset speed frequency, stage 4 (0-599)HzWrite
AO12FreqCommand6Preset speed frequency, stage 5 (0-599)HzWrite
AO13FreqCommand7Preset speed frequency, stage 6 (0-599)HzWrite
AO14FreqCommand8Preset speed frequency, stage 7 (0-599)HzWrite
AO23RunModeMain run command source selection (0-2)Write
AO24ReverseOperDirection lock command (0-1)Write
AO25StoppingSelStop mode selection (0-1)Write
AO26FrequenceCommMain frequency command source selection (0-6)Write
AO27FreqUpperLimUpper limit frequency (0.01-599)HzWrite
AO28FreqLowerLimLower limit frequency (0-598.99)HzWrite
AO29Acc Time1Acceleration time 1 (range not printed)sWrite
AO30Dec Time1Deceleration time 1 (0.1-3600)sWrite
AV0PID – P GainPID proportional gain (0-10)Write
AV1PID – I TimePID integral time (0-100)Write
AV2PID – D TimePID derivative time (0-10)Write
BImin0Run/StopOperation statusReadStop / Run
BI1DirectionOperation directionReadFWD / REV
BImin2statusInverter statusReadOK / Fault
BI3AbnormalError occursReadClose / Open
BI4DI_1 statusTerminal S1 statusReadClose / Open
BI5DI_2 statusTerminal S2 statusReadClose / Open
BI6DI_3 statusTerminal S3 statusReadClose / Open
BI7DI_4 statusTerminal S4 statusReadClose / Open
BI8DI_5 statusTerminal S5 statusReadClose / Open
BO0RY1 statusRelay output 1 statusReadClose / Open
BVmin0RUN/STOPRun/stop commandWriteStop / Run
BV1FWD/REVForward/reverse commandWriteFWD / REV
Object ID lookup: TECO-Westinghouse L510 inverter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the L510 inverter (built-in BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TECO-Westinghouse L510 inverter (built-in BACnet MS/TP)

How many BACnet points does the TECO-Westinghouse L510 inverter (built-in BACnet MS/TP) have?

This list has 53 BACnet objects: 16 analog inputs, 22 analog outputs, 3 analog values, 9 binary inputs, 1 binary output, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TECO-Westinghouse L510 inverter (built-in BACnet MS/TP) BACnet points are writable?

23 of the 53 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official TECO-Westinghouse L510 inverter (built-in BACnet MS/TP) BACnet documentation?

The source is L510 Communication Addendum (Modbus RTU/ASCII, BACnet, Metasys N2, Profibus) (TECO-L510-AC001), revision Ver01 2015-06, published free by TECO-Westinghouse at https://www.tecowestinghouse.com/PDF/L510_comm_addendum.pdf.

What are the minimum BACnet points to integrate the TECO-Westinghouse L510 inverter (built-in BACnet MS/TP)?

Start with BV 0 RUN/STOP (Run/stop command); AO 0 Set frequency (Frequency command, Hz); BI 0 Run/Stop (Running status); AI 4 Frequency (Output frequency, Hz); AI 5 Current (Output current, A); BI 2 status (Drive fault (OK / Fault)); AI 2 Error code (Latest fault code).

How do I enable BMS control of the TECO-Westinghouse L510 inverter (built-in BACnet MS/TP)?

Set the main run command source (AO 23) and main frequency command source (AO 26) to the communication option; the addendum does not print the setting values for the L510.

How do I check these points on the real L510 inverter (built-in BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TECO-Westinghouse BACnet points lists

Source: L510 Communication Addendum (Modbus RTU/ASCII, BACnet, Metasys N2, Profibus) · TECO-L510-AC001 · rev. Ver01 2015-06. Object names, instances and units are reproduced as published; descriptions are our own.