Variable frequency drive · BACnet points list

TECO-Westinghouse F510 inverter (built-in BACnet MS/TP) BACnet points list

Updated 12 November 2026

Short answer

The F510 is a fan and pump inverter with BACnet MS/TP built into its RS-485 port; no option card is needed. The object list is fixed: analog inputs report terminals, frequency, current, fault code and motor data; analog outputs carry the frequency command, preset speeds, command sources, limits and ramps; binary objects give run, direction, fault, terminal and relay states and the run and direction commands.

This page lists 65 BACnet objects for the TECO-Westinghouse F510 inverter (built-in BACnet MS/TP) — 31 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from TECO-Westinghouse’s own free documentation, linked below.

Manufacturer
TECO-Westinghouse
Model
F510 inverter (built-in BACnet MS/TP)
Equipment
Variable frequency drive
Equipment type
VFDs & pumps
BACnet objects
65 (31 writable)
Transport
BACnet MS/TP
Firmware
0.14 (Firmware_Revision in the device object table)
Also known as
F510, TECO F510, TECO-Westinghouse F510, F510 BACnet, TECO-F510-AC001
Source document
F510 Communication Addendum (Modbus RTU/ASCII, BACnet, Metasys N2, Profibus) · TECO-F510-AC001 · rev. Ver01 2015-03
Download CSV 65 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against TECO-Westinghouse’s current documentation and the live device before use. Not official TECO-Westinghouse information. Terms of use.

BMS integration notes: TECO-Westinghouse F510 inverter (built-in BACnet MS/TP)

Integration in brief

Wire the drive's RS-485 port to the MS/TP trunk and select BACnet as the drive's communication mode. Set the run and frequency command sources to communication (AO 23 / AO 26 mirror those parameters), then write the speed to AO 0 and start/stop with BV 0. Read BI 0, AI 4, AI 5 and BI 2 / AI 2 for status and faults.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 0RUN/STOPRun/stop commandWrite
AO 0Set frequencyFrequency command, HzWrite
BI 0Run/StopRunning statusRead
AI 4FrequencyOutput frequency, HzRead
AI 5CurrentOutput current, ARead
BI 2statusDrive fault (OK / Fault)Read
AI 2Error codeLatest fault codeRead

Enable & remote start

Set the main run command source (parameter 00-02, also AO 23) and the main frequency command source (00-05, also AO 26) to communication. The addendum's Profibus section gives these as 00-02 = 2 and 00-05 = 3.

Network setup

Watch out for

TECO-Westinghouse F510 inverter (built-in BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

65 of 65 shown
Type
Access
Show
TECO-Westinghouse F510 inverter (built-in BACnet MS/TP) BACnet Points List
DescriptionStates
AI0TM2 AINAI1 input (0-10)VRead
AI1TM2 AIN2AI2 input (0-10)VRead
AImin2Error codeRecent fault message (0-45)Read
AI3Freq cmdFrequency command (0-60)HzRead
AImin4FrequencyOutput frequency (0-60)HzRead
AImin5CurrentOutput currentARead
AI6Control ModeControl mode (0-2)Read
AI7Motor R-VoltMotor rated voltageVRead
AI8Motor R-HPMotor rated powerhpRead
AI9Motor R-RPMMotor rated rotation speedRead
AI10Motor R-HzMotor rated frequencyHzRead
AI11CarrierFreqCarrier frequency (4-16)kHzRead
AI12Comm StationInverter communication station (1-254)Read
AI13BaudRateBaud rate setting (0-3)Read
AI14BacnetSelCommunication mode selection (0-1)Read
AI15DevInstanceInverter number (1-254)Read
AOmin0Set frequencyFrequency command (0-60)HzWrite
AO1TB2 AO1Output voltage 1 (0-10)VRead
AO2TB2 AO2Output voltage 2 (0-10)VRead
AO3Motor R-AmpMotor rated current (0-65535)AWrite
AO4PwrL SelMomentary stop and restart selection (0-2)Read
AO5RestartSelNumber of fault auto-restart attempts (0-10)Read
AO6RestartDelayFault auto-restart time (0-800)sRead
AO7FreqCommand1Preset speed frequency, stage 0 (0-400)HzWrite
AO8FreqCommand2Preset speed frequency, stage 1 (0-400)HzWrite
AO9FreqCommand3Preset speed frequency, stage 2 (0-400)HzWrite
AO10FreqCommand4Preset speed frequency, stage 3 (0-400)HzWrite
AO11FreqCommand5Preset speed frequency, stage 4 (0-400)HzWrite
AO12FreqCommand6Preset speed frequency, stage 5 (0-400)HzWrite
AO13FreqCommand7Preset speed frequency, stage 6 (0-400)HzWrite
AO14FreqCommand8Preset speed frequency, stage 7 (0-400)HzWrite
AO15FreqCommand9Preset speed frequency, stage 8 (0-400)HzWrite
AO16FreqCommand10Preset speed frequency, stage 9 (0-400)HzWrite
AO17FreqCommand11Preset speed frequency, stage 10 (0-400)HzWrite
AO18FreqCommand12Preset speed frequency, stage 11 (0-400)HzWrite
AO19FreqCommand13Preset speed frequency, stage 12 (0-400)HzWrite
AO20FreqCommand14Preset speed frequency, stage 13 (0-400)HzWrite
AO21FreqCommand15Preset speed frequency, stage 14 (0-400)HzWrite
AO22FreqCommand16Preset speed frequency, stage 15 (0-400)HzWrite
AO23RunModeMain run command source selection (0-2)Write
AO24ReverseOperDirection lock command (0-1)Write
AO25StoppingSelStop mode selection (0-1)Write
AO26FrequenceCommMain frequency command source selection (0-5)Write
AO27FreqUpperLimUpper limit frequency (0-400)HzWrite
AO28FreqLowerLimLower limit frequency (0-400)HzWrite
AO29Acc Time1Acceleration time 1 (0-3600)sWrite
AO30Dec Time1Deceleration time 1 (0-3600)sWrite
AV0PID – P GainPID proportional gain (0-10)Write
AV1PID – I TimePID integral time (0-100)Write
AV2PID – D TimePID derivative time (0-10)Write
BImin0Run/StopOperation statusReadStop / Run
BI1DirectionOperation directionReadFWD / REV
BImin2statusInverter statusReadOK / Fault
BI3AbnormalError occursReadClose / Open
BI4DI_1 statusTerminal S1 statusReadClose / Open
BI5DI_2 statusTerminal S2 statusReadClose / Open
BI6DI_3 statusTerminal S3 statusReadClose / Open
BI7DI_4 statusTerminal S4 statusReadClose / Open
BI8DI_5 statusTerminal S5 statusReadClose / Open
BI9DI_6 statusTerminal S6 statusReadClose / Open
BO0RY1 statusRelay output 1 statusReadClose / Open
BO1RY2 statusRelay output 2 statusReadClose / Open
BO2RY3 statusRelay output 3 statusReadClose / Open
BVmin0RUN/STOPRun/stop commandWriteStop / Run
BV1FWD/REVForward/reverse commandWriteFWD / REV
Object ID lookup: TECO-Westinghouse F510 inverter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the F510 inverter (built-in BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the TECO-Westinghouse F510 inverter (built-in BACnet MS/TP)

How many BACnet points does the TECO-Westinghouse F510 inverter (built-in BACnet MS/TP) have?

This list has 65 BACnet objects: 16 analog inputs, 31 analog outputs, 3 analog values, 10 binary inputs, 3 binary outputs, 2 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which TECO-Westinghouse F510 inverter (built-in BACnet MS/TP) BACnet points are writable?

31 of the 65 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official TECO-Westinghouse F510 inverter (built-in BACnet MS/TP) BACnet documentation?

The source is F510 Communication Addendum (Modbus RTU/ASCII, BACnet, Metasys N2, Profibus) (TECO-F510-AC001), revision Ver01 2015-03, published free by TECO-Westinghouse at https://www.tecowestinghouse.com/PDF/F510_comm_addendum.pdf.

What are the minimum BACnet points to integrate the TECO-Westinghouse F510 inverter (built-in BACnet MS/TP)?

Start with BV 0 RUN/STOP (Run/stop command); AO 0 Set frequency (Frequency command, Hz); BI 0 Run/Stop (Running status); AI 4 Frequency (Output frequency, Hz); AI 5 Current (Output current, A); BI 2 status (Drive fault (OK / Fault)); AI 2 Error code (Latest fault code).

How do I enable BMS control of the TECO-Westinghouse F510 inverter (built-in BACnet MS/TP)?

Set the main run command source (parameter 00-02, also AO 23) and the main frequency command source (00-05, also AO 26) to communication. The addendum's Profibus section gives these as 00-02 = 2 and 00-05 = 3.

How do I check these points on the real F510 inverter (built-in BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More TECO-Westinghouse BACnet points lists

Source: F510 Communication Addendum (Modbus RTU/ASCII, BACnet, Metasys N2, Profibus) · TECO-F510-AC001 · rev. Ver01 2015-03. Object names, instances and units are reproduced as published; descriptions are our own.