Thermostat (BACnet MS/TP) · BACnet points list

Strato Automation OPENSTAT OS537 thermostat, RTU firmware BACnet points list

Updated 12 November 2026

Short answer

The OS537 is a larger BACnet MS/TP thermostat with 5 universal inputs, 3 analog outputs and 7 binary outputs, plus humidity and (C models) CO2 sensing. Its RTU application covers up to four cooling and four heating stages, economizer with enthalpy and mixed air control, power exhaust, humidification and dehumidification, selected with the MSV-127 preset. The list also includes the radar presence sensor settings.

This page lists 123 BACnet objects for the Strato Automation OPENSTAT OS537 thermostat, RTU firmware — 84 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Strato Automation’s own free documentation, linked below.

Manufacturer
Strato Automation
Model
OPENSTAT OS537 thermostat, RTU firmware
Equipment
Thermostat (BACnet MS/TP)
Equipment type
Thermostats, sensors & meters
BACnet objects
123 (84 writable)
Transport
BACnet MS/TP
Firmware
Universal firmware 1.2.6 and later
Also known as
OS537, OS537H, OS537MHC, OpenStat OS537, OS537-RTU, Strato OS537
Source document
OS537 (Universal Firmware) User Guide, Rooftop Unit (RTU) - BACnet Objects · rev. July 2026 rev 0
Download CSV 123 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Strato Automation’s current documentation and the live device before use. Not official Strato Automation information. Terms of use.

BMS integration notes: Strato Automation OPENSTAT OS537 thermostat, RTU firmware

Integration in brief

Select the application with MSV-127, then command system mode (MSV-3), fan mode (MSV-4) and occupancy (BV-5 or MSV-6) and write the room setpoint (AV-1). Read room temperature and humidity, demands, supply and outdoor temperatures and the help message (MSV-100) for alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 3MODESystem mode: Off, Auto, Cool, HeatWrite
MV 4FANFan mode: On / AutoWrite
BV 5Occ_SchOccupancy schedule; BMS can write On/OffWrite
AV 1RoomTSPRoom temperature setpointWrite
AI 6RoomTRoom temperatureRead
AI 7RoomRHRoom humidityRead
AV 6HTG_DemHeating demand, %Read
AV 7CLG_DemCooling demand, %Read
AV 16SATempSupply air temperatureRead
MV 100HELP_messAlarm / help messageRead

Enable & remote start

Occupancy can be written to BV-5; MSV-45 selects the schedule source and MSV-6 forces local, occupied or unoccupied.

Sensors & values from the BMS

Sensor location MSVs (MSV-2, 27, 28, 52, 54, 57, 58) can be set to 'External' to take the value from the network.

Network setup

Watch out for

Strato Automation OPENSTAT OS537 thermostat, RTU firmware BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

123 of 123 shown
Type
Multi-state
Access
Show
Strato Automation OPENSTAT OS537 thermostat, RTU firmware BACnet Points List
DescriptionStates
BO1BO_1Output; function set by the MSV-127 presetCommand
BO2BO_2Output; function set by the MSV-127 presetCommand
BO3BO_3Output; function set by the MSV-127 presetCommand
BO4BO_4Output; function set by the MSV-127 presetCommand
BO5BO_5Output; function set by the MSV-127 presetCommand
BO6BO_6Output; function set by the MSV-127 presetCommand
BO7BO_7Output; function set by the MSV-127 presetCommand
AO1AO_1Output; function set by the MSV-127 presetCommand
AO2AO_2Output; function set by the MSV-127 presetCommand
AO3AO_3Output; function set by the MSV-127 presetCommand
AI1AI_1Input; function set by the configuration MSVsRead
AI2AI_2Input; function set by the configuration MSVsRead
AI3AI_3Input; function set by the configuration MSVsRead
AI4AI_4Input; function set by the configuration MSVsRead
AI5AI_5Input; function set by the configuration MSVsRead
AImin6RoomTRoom temperature°FRead
AImin7RoomRHRoom humidity%Read
AI8RoomCO2Room CO2ppmRead
BI1MotionMotion detectionReadOn / Off
AVmin1RoomTSPRoom Temperature setpoint (range 54-90°F (12-32°C))°FWrite
AVmin6HTG_DemHeating demand (range 0-100%)%Read
AVmin7CLG_DemCooling demand (range 0-100%)%Read
AV9Eff_TEffective temperature used for control (range -40-122°F (-40-50°C))°FRead
AVmin16SATempSupply air temperature (range -40-122°F (-40-50°C))°FRead
AV19SATFRSP_SetSet supply freezing temperature (range -40-122°F (-40-50°C))°FWrite
AV21ECM_min_SetFan analog min. output (range 0-100%)%Write
AV24Fan_MinOn_TimeFan minimum ON time (range 0-60 min)minWrite
AV27OvrTime_SetSet occupancy override time (range 0-480 min)minWrite
AV29OATempOutdoor air temperature (range -40-122°F (-40-50°C))°FRead
AV31CO2_SP_SetSet CO2 Setpoint (range 0-2000 PPM)ppmWrite
AV33MinCLSPSet minimum cooling setpoint (range 54-100°F (12-37.5°C))°FWrite
AV34MaxHTSPSet maximum heating setpoint (range 40-90°F (4.5-32°C))°FWrite
AV35OccCLSPSet occupied cooling setpoint°FRead
AV36OccHTSPSet occupied heating setpoint°FRead
AV37SP_DB_SetSet deadband (range 2 to 5°)Write
AV38Unoc_CL_SetSet unoccupied cooling setpoint°FWrite
AV39Unoc_HT_SetSet unoccupied heating setpoint°FWrite
AV40STBCoolOffsetSet standby cooling offset (+) (range 2 to 5°)Write
AV41STBHeatOffsetSet standby heating offset (-) (range -2 to -5°)Write
AV42EffCLSPEffective cooling setpointRead
AV43EffHTSPEffective heating setpointRead
AV50RT_CalRoom temperature calib (range -5.0 to 5.0)Write
AV51Eff_RHEffective humidity used for control (range 0-100%)%Read
AV52HUM_SPSet humidity setpoint (range 0-100%)%Write
AV53SAHSupply humidity reading (range 0-100%)%Read
AV54SAH_HL_SetSupply humidity high limit setpoint (range 50-98%)%Write
AV55DEH_SPSet dehum setpoint (range 0-100%)%Write
AV56SAT_HL_SetSet supply air high limit setpoint (range 0.0-140°F (0.0-60°C))°FWrite
AV57SAT_CTR_SetSet supply air neutral setpoint (range 0.0-140°F (0.0-60°C))°FWrite
AV58SAT_LL_SetSet supply air low limit setpoint (range 0.0-140°F (0.0-60°C))°FWrite
AV59Eff_SATEffective supply air calc. setpoint (range 0.0-140°F (0.0-60°C))°FRead
AV60ComprLockoutCompressor Lockout (range 0.0-140°F (0.0-60°C))°FWrite
AV65EconoMin_PosEco min position (range 0-100%)%Write
AV66EconoMaxCO2PosEcono max position (for CO2) (range 0-100%)%Write
AV67OATheatOutAuthHeating authorization (from OAT) (range 0.0-140°F (0.0-60°C))°FWrite
AV68OATeconOutAuthEconomizer authorization (from OAT) (range 0.0-140°F (0.0-60°C))°FWrite
AV75OAHOutside air humidity (range 0-100%)%Read
AV76OAEOutside air enthalpy (range 10-55 BTU/lbs)BTU/lbRead
AV77EnthSPEnthalpy setpoint (range 20-28 BTU/lbs)BTU/lbWrite
AV78MATSPMixed air temperature for economizer (range 0.0-140°F (0.0-60°C))°FWrite
AV79MATMixed air temperature (range 0.0-140°F (0.0-60°C))°FRead
BV2OVRSTATOccupancy override statusReadInactive = Normal, Active = Override
BV3Mot_DetMotion detectionReadInactive = None, Active = Moving
BV4AutogenDescAutogenerate I/O descriptionsWriteInactive = Off, Active = On
BVmin5Occ_SchSystem occupancy scheduleWriteInactive = Off, Active = On
BV7Freeze_StatusFreeze condition statusReadInactive = Normal, Active = Active
BV8Free_CL_StatusFree cooling authorization statusReadInactive = No, Active = Yes
BV21EnthalpyAuthEnthalpy AuthorizeReadInactive = No, Active = Yes
MV1CFGSensRemote thermistor 10KWrite1 = Type 3, 2 = Type 2
MV2AI_RSSelect room temperature inputWrite1 = Intern, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5
MVmin3MODESystem modeWrite1 = Off, 2 = Auto, 3 = Cool, 4 = Heat
MVmin4FANSet fan modeWrite1 = On, 2 = Auto
MV5Eff_OccEffective occupancy modeRead1 = Occupied, 2 = Unoccup, 3 = TempOcc, 4 = Standby
MV6Occ_CmdOccupancy commandWrite1 = Loc-Occ, 2 = Occupied, 3 = Unoccup
MV7CFG_Y1Set cooling output 1 operationWrite1 = None, 2 = Off-On, 3 = 0-10V DA (direct), 4 = 0-10V RA (reversed), 5 = 2-10V DA (direct), 6 = 2-10V RA (reversed), 7 = Pulsed DA (direct), 8 = Pulsed RA (reversed)
MV8CFG_Y2Set cooling output 2 operationWrite1 = None, 2 = Off-On, 3 = 0-10V DA (direct), 4 = 0-10V RA (reversed), 5 = 2-10V DA (direct), 6 = 2-10V RA (reversed), 7 = Pulsed DA (direct), 8 = Pulsed RA (reversed)
MV9CFG_Y3Set cooling output 3 operationWrite1 = None, 2 = Off-On
MV10CFG_Y4Set cooling output 4 operationWrite1 = None, 2 = Off-On
MV16CFG_W1Set heating output 1 operationWrite1 = None, 2 = Off-On, 3 = 0-10V DA (direct), 4 = 0-10V RA (reversed), 5 = 2-10V DA (direct), 6 = 2-10V RA (reversed), 7 = Pulsed DA (direct), 8 = Pulsed RA (reversed), 9 = O (O/B), 10 = B (O/B)
MV17CFG_W2Set heating output 2 operationWrite1 = None, 2 = Off-On, 3 = 0-10V DA (direct), 4 = 0-10V RA (reversed), 5 = 2-10V DA (direct), 6 = 2-10V RA (reversed), 7 = Pulsed DA (direct), 8 = Pulsed RA (reversed), 9 = O (O/B), 10 = B (O/B)
MV18CFG_W3Set heating output 3 operationWrite1 = None, 2 = Off-On
MV19CFG_W4Set heating output 4 operationWrite1 = None, 2 = Off-On
MV23CFG_FANSelect fan outputWrite1 = BO-1, 2 = BO-2, 3 = AO-1, 4 = AO-2, 5 = BO-1 & AO-1, 6 = BO-1 & AO-2
MV27AI_OATSelect outside air temp. inputWrite1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5, 7 = External
MV28AI_SATSelect supply air temp. inputWrite1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5, 7 = External
MV30AO_ECOSelect economizer outputWrite1 = None, 2 = BO-5, 3 = BO-6, 4 = BO-7, 5 = AO-1, 6 = AO-2, 7 = AO-3
MV32CFG_EXHSelect power exhaust outputWrite1 = None, 2 = BO-6, 3 = BO-7, 4 = AO-3, 5 = BO-6 & AO-3, 6 = BO-7 & AO-3
MV44BI_PIRSelect PIR Motion sensor inputWrite1 = None, 2 = NO, AI1 (BI), 3 = NC, AI1 (BI), 4 = NO, AI2 (BI), 5 = NC, AI2 (BI), 6 = NO, AI3 (BI), 7 = NC, AI3 (BI), 8 = NO, AI4 (BI), 9 = NC, AI4 (BI), 10 = External, 11 = Intern
MV45BI_SCH_InputSelect schedule inputWrite1 = None (Off), 2 = None (On), 3 = Scheduler, 4 = AI-1, 5 = AI-2, 6 = AI-3, 7 = AI-4, 8 = AI-5, 9 = External
MV48BO_HUMSelect humidifier BO outputWrite1 = None, 2 = BO-2, 3 = BO-3, 4 = BO-4, 5 = BO-5, 6 = BO-6, 7 = BO-7, 8 = BO-5 & BO-6 (Two stages), 9 = BO-6 & BO-7 (Two stages)
MV49AO_HUMSelect humidifier AO outputWrite1 = None, 2 = AO-1, 3 = AO-2, 4 = AO-3
MV52AI_RHSelect room humidity inputWrite1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5, 7 = External, 8 = Intern
MV54AI_SRHSelect supply humidity inputWrite1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5, 7 = External
MV55AIC_SRHSet supply humidity input signalWrite1 = 0-10V, 2 = 2-10V
MV57OAH_LocOutside humidity physical input loc.Write1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5, 7 = External, 8 = Intern
MV58MAT_LocMixed air temperature sensor loc.Write1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5, 7 = External
MV62CFGSetpRoom setpoint displayedWrite1 = Heat SP, 2 = Center, 3 = Cool SP
MV65BO_OCCSelect occupied outputWrite1 = None, 2 = BO-2, 3 = BO-3, 4 = BO-4, 5 = BO-5, 6 = BO-6, 7 = BO-7, 8 = AO-1, 9 = AO-2, 10 = AO-3
MV66AI1_CFGSelect predefined AI1 logicWrite1 = None, 2 = NSB, 3 = OVR, 4 = FILTER, 5 = SERVICE, 6 = FANSTATUS
MV67AI2_CFGSelect predefined AI2 logicWrite1 = None, 2 = NSB, 3 = OVR, 4 = FILTER, 5 = SERVICE, 6 = FANSTATUS
MV68BO_DEHUSelect dehumidification outputWrite1 = None, 2 = BO-2, 3 = BO-3, 4 = BO-4, 5 = BO-5, 6 = BO-6, 7 = BO-7
MV70PBCFG Heating/cooling proportional bandWrite1 = 3F 1.2C, 2 = 4F 1.7C, 3 = 5F 2.2C, 4 = 6F 2.8C, 5 = 7F 3.3C, 6 = 8F 3.5C, 7 = 9F 5.0C, 8 = 10F 5.6C
MVmin100HELP_messHelp messageRead1 = Normal, 2 = FanLock, 3 = SupplyFrozen, 4 = Service, 5 = Filter, 6 = Rem NSB Ovr
MV127PresetSelect applicationWrite1 = RT 2STG, 2 = RT ECON, 3 = HP 2STG, 4 = RT IAQ, 5 = RT MOD, 6 = HP DEH, 7 = HUM-DEH, 8 = RT 3STG, 9 = RT 4STG, 10 = HP 3STG
MV200BrightnessBrightness ControlWrite1 = Low, 2 = Med-Low, 3 = Med
MV201BgColorBackground ColorWrite1 = White, 2 = Orange, 3 = Blue, 4 = Green, 5 = Red
MV202LockTempMain DisplayWrite1 = Temp, 2 = Setpoint, 3 = Nothing
MV203LanguageLanguage selectionWrite1 = English
MV204Display_UnitsTemperature displayed unitsWrite1 = C, 2 = F
MV205System_UnitSystem/Database UnitWrite1 = Metric, 2 = Imperial
MV221Radar_StatusRadar_statusWrite1 = Disable, 2 = Enable
MV223Detection_rangeDetection_rangeWriteRange: 1_m to 7_m
MV235Radar_Freqpll_frequency_wordWriteRange: Channel 1 to 8
MV244Sensitivityduty_cycle_repetition_rWrite1 = Low, 2 = Medium, 3 = High, 4 = very-high
LO1RoomT_CoolRoom temp cooling control loop%Read
LO2RoomT_heatRoom temp heating control loop%Read
LO6SupplyTempSupply temp control loop%Read
LO7SupplyTempHLSupply temp high limit control loop%Read
LO8SupplyTempLLSupply temp low limit control loop%Read
LO10Room_RHRoom RH control loop%Read
LO11Supply_RH_HLSupply RH hi limit control loop%Read
LO12PidMATMix air T control for economizer%Read
SCH1OccScheduleOccupancy scheduleWrite
Object ID lookup: Strato Automation OPENSTAT OS537 thermostat, RTU firmware point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OPENSTAT OS537 thermostat, RTU firmware and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Strato Automation OPENSTAT OS537 thermostat, RTU firmware

How many BACnet points does the Strato Automation OPENSTAT OS537 thermostat, RTU firmware have?

This list has 123 BACnet objects: 8 analog inputs, 3 analog outputs, 42 analog values, 1 binary input, 7 binary outputs, 7 binary values, 8 loops, 1 schedule, 46 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Strato Automation OPENSTAT OS537 thermostat, RTU firmware BACnet points are writable?

84 of the 123 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Strato Automation OPENSTAT OS537 thermostat, RTU firmware BACnet documentation?

The source is OS537 (Universal Firmware) User Guide, Rooftop Unit (RTU) - BACnet Objects, revision July 2026 rev 0, published free by Strato Automation at https://stratoautomation.com/wp-content/uploads/2025/08/OS537-User-Guide-July-2026-rev-0.pdf.

What are the minimum BACnet points to integrate the Strato Automation OPENSTAT OS537 thermostat, RTU firmware?

Start with MV 3 MODE (System mode: Off, Auto, Cool, Heat); MV 4 FAN (Fan mode: On / Auto); BV 5 Occ_Sch (Occupancy schedule; BMS can write On/Off); AV 1 RoomTSP (Room temperature setpoint); AI 6 RoomT (Room temperature); AI 7 RoomRH (Room humidity); AV 6 HTG_Dem (Heating demand, %); AV 7 CLG_Dem (Cooling demand, %); AV 16 SATemp (Supply air temperature); MV 100 HELP_mess (Alarm / help message).

How do I enable BMS control of the Strato Automation OPENSTAT OS537 thermostat, RTU firmware?

Occupancy can be written to BV-5; MSV-45 selects the schedule source and MSV-6 forces local, occupied or unoccupied.

Can the BMS supply sensor values to the Strato Automation OPENSTAT OS537 thermostat, RTU firmware?

Sensor location MSVs (MSV-2, 27, 28, 52, 54, 57, 58) can be set to 'External' to take the value from the network.

How do I check these points on the real OPENSTAT OS537 thermostat, RTU firmware?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Strato Automation BACnet points lists

Source: OS537 (Universal Firmware) User Guide, Rooftop Unit (RTU) - BACnet Objects · rev. July 2026 rev 0. Object names, instances and units are reproduced as published; descriptions are our own.