Thermostat (BACnet MS/TP) · BACnet points list
Strato Automation OPENSTAT OS537 thermostat, RTU firmware BACnet points list
Updated 12 November 2026
The OS537 is a larger BACnet MS/TP thermostat with 5 universal inputs, 3 analog outputs and 7 binary outputs, plus humidity and (C models) CO2 sensing. Its RTU application covers up to four cooling and four heating stages, economizer with enthalpy and mixed air control, power exhaust, humidification and dehumidification, selected with the MSV-127 preset. The list also includes the radar presence sensor settings.
This page lists 123 BACnet objects for the Strato Automation OPENSTAT OS537 thermostat, RTU firmware — 84 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Strato Automation’s own free documentation, linked below.
- Manufacturer
- Strato Automation
- Model
- OPENSTAT OS537 thermostat, RTU firmware
- Equipment
- Thermostat (BACnet MS/TP)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 123 (84 writable)
- Transport
- BACnet MS/TP
- Firmware
- Universal firmware 1.2.6 and later
- Also known as
- OS537, OS537H, OS537MHC, OpenStat OS537, OS537-RTU, Strato OS537
Reference only, provided as-is: verify against Strato Automation’s current documentation and the live device before use. Not official Strato Automation information. Terms of use.
BMS integration notes: Strato Automation OPENSTAT OS537 thermostat, RTU firmware
Select the application with MSV-127, then command system mode (MSV-3), fan mode (MSV-4) and occupancy (BV-5 or MSV-6) and write the room setpoint (AV-1). Read room temperature and humidity, demands, supply and outdoor temperatures and the help message (MSV-100) for alarms.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 3 | MODE | System mode: Off, Auto, Cool, Heat | Write |
| MV 4 | FAN | Fan mode: On / Auto | Write |
| BV 5 | Occ_Sch | Occupancy schedule; BMS can write On/Off | Write |
| AV 1 | RoomTSP | Room temperature setpoint | Write |
| AI 6 | RoomT | Room temperature | Read |
| AI 7 | RoomRH | Room humidity | Read |
| AV 6 | HTG_Dem | Heating demand, % | Read |
| AV 7 | CLG_Dem | Cooling demand, % | Read |
| AV 16 | SATemp | Supply air temperature | Read |
| MV 100 | HELP_mess | Alarm / help message | Read |
Enable & remote start
Occupancy can be written to BV-5; MSV-45 selects the schedule source and MSV-6 forces local, occupied or unoccupied.
Sensors & values from the BMS
Sensor location MSVs (MSV-2, 27, 28, 52, 54, 57, 58) can be set to 'External' to take the value from the network.
Network setup
- MS/TP is the default network; address and baud are set in the MSTP Config menu. A Wi-Fi option is described in a separate Strato guide.
- Strato recommends writing MSVs and AVs at the default priority (16) and everything else at priority 8 down to 3.
Watch out for
- Most MSVs are commissioning settings; changing a custom output MSV switches MSV-127 to Custom.
Strato Automation OPENSTAT OS537 thermostat, RTU firmware BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BO | 1 | BO_1 | Output; function set by the MSV-127 preset | Command | ||
| BO | 2 | BO_2 | Output; function set by the MSV-127 preset | Command | ||
| BO | 3 | BO_3 | Output; function set by the MSV-127 preset | Command | ||
| BO | 4 | BO_4 | Output; function set by the MSV-127 preset | Command | ||
| BO | 5 | BO_5 | Output; function set by the MSV-127 preset | Command | ||
| BO | 6 | BO_6 | Output; function set by the MSV-127 preset | Command | ||
| BO | 7 | BO_7 | Output; function set by the MSV-127 preset | Command | ||
| AO | 1 | AO_1 | Output; function set by the MSV-127 preset | Command | ||
| AO | 2 | AO_2 | Output; function set by the MSV-127 preset | Command | ||
| AO | 3 | AO_3 | Output; function set by the MSV-127 preset | Command | ||
| AI | 1 | AI_1 | Input; function set by the configuration MSVs | Read | ||
| AI | 2 | AI_2 | Input; function set by the configuration MSVs | Read | ||
| AI | 3 | AI_3 | Input; function set by the configuration MSVs | Read | ||
| AI | 4 | AI_4 | Input; function set by the configuration MSVs | Read | ||
| AI | 5 | AI_5 | Input; function set by the configuration MSVs | Read | ||
| AImin | 6 | RoomT | Room temperature | °F | Read | |
| AImin | 7 | RoomRH | Room humidity | % | Read | |
| AI | 8 | RoomCO2 | Room CO2 | ppm | Read | |
| BI | 1 | Motion | Motion detection | Read | On / Off | |
| AVmin | 1 | RoomTSP | Room Temperature setpoint (range 54-90°F (12-32°C)) | °F | Write | |
| AVmin | 6 | HTG_Dem | Heating demand (range 0-100%) | % | Read | |
| AVmin | 7 | CLG_Dem | Cooling demand (range 0-100%) | % | Read | |
| AV | 9 | Eff_T | Effective temperature used for control (range -40-122°F (-40-50°C)) | °F | Read | |
| AVmin | 16 | SATemp | Supply air temperature (range -40-122°F (-40-50°C)) | °F | Read | |
| AV | 19 | SATFRSP_Set | Set supply freezing temperature (range -40-122°F (-40-50°C)) | °F | Write | |
| AV | 21 | ECM_min_Set | Fan analog min. output (range 0-100%) | % | Write | |
| AV | 24 | Fan_MinOn_Time | Fan minimum ON time (range 0-60 min) | min | Write | |
| AV | 27 | OvrTime_Set | Set occupancy override time (range 0-480 min) | min | Write | |
| AV | 29 | OATemp | Outdoor air temperature (range -40-122°F (-40-50°C)) | °F | Read | |
| AV | 31 | CO2_SP_Set | Set CO2 Setpoint (range 0-2000 PPM) | ppm | Write | |
| AV | 33 | MinCLSP | Set minimum cooling setpoint (range 54-100°F (12-37.5°C)) | °F | Write | |
| AV | 34 | MaxHTSP | Set maximum heating setpoint (range 40-90°F (4.5-32°C)) | °F | Write | |
| AV | 35 | OccCLSP | Set occupied cooling setpoint | °F | Read | |
| AV | 36 | OccHTSP | Set occupied heating setpoint | °F | Read | |
| AV | 37 | SP_DB_Set | Set deadband (range 2 to 5°) | Write | ||
| AV | 38 | Unoc_CL_Set | Set unoccupied cooling setpoint | °F | Write | |
| AV | 39 | Unoc_HT_Set | Set unoccupied heating setpoint | °F | Write | |
| AV | 40 | STBCoolOffset | Set standby cooling offset (+) (range 2 to 5°) | Write | ||
| AV | 41 | STBHeatOffset | Set standby heating offset (-) (range -2 to -5°) | Write | ||
| AV | 42 | EffCLSP | Effective cooling setpoint | Read | ||
| AV | 43 | EffHTSP | Effective heating setpoint | Read | ||
| AV | 50 | RT_Cal | Room temperature calib (range -5.0 to 5.0) | Write | ||
| AV | 51 | Eff_RH | Effective humidity used for control (range 0-100%) | % | Read | |
| AV | 52 | HUM_SP | Set humidity setpoint (range 0-100%) | % | Write | |
| AV | 53 | SAH | Supply humidity reading (range 0-100%) | % | Read | |
| AV | 54 | SAH_HL_Set | Supply humidity high limit setpoint (range 50-98%) | % | Write | |
| AV | 55 | DEH_SP | Set dehum setpoint (range 0-100%) | % | Write | |
| AV | 56 | SAT_HL_Set | Set supply air high limit setpoint (range 0.0-140°F (0.0-60°C)) | °F | Write | |
| AV | 57 | SAT_CTR_Set | Set supply air neutral setpoint (range 0.0-140°F (0.0-60°C)) | °F | Write | |
| AV | 58 | SAT_LL_Set | Set supply air low limit setpoint (range 0.0-140°F (0.0-60°C)) | °F | Write | |
| AV | 59 | Eff_SAT | Effective supply air calc. setpoint (range 0.0-140°F (0.0-60°C)) | °F | Read | |
| AV | 60 | ComprLockout | Compressor Lockout (range 0.0-140°F (0.0-60°C)) | °F | Write | |
| AV | 65 | EconoMin_Pos | Eco min position (range 0-100%) | % | Write | |
| AV | 66 | EconoMaxCO2Pos | Econo max position (for CO2) (range 0-100%) | % | Write | |
| AV | 67 | OATheatOutAuth | Heating authorization (from OAT) (range 0.0-140°F (0.0-60°C)) | °F | Write | |
| AV | 68 | OATeconOutAuth | Economizer authorization (from OAT) (range 0.0-140°F (0.0-60°C)) | °F | Write | |
| AV | 75 | OAH | Outside air humidity (range 0-100%) | % | Read | |
| AV | 76 | OAE | Outside air enthalpy (range 10-55 BTU/lbs) | BTU/lb | Read | |
| AV | 77 | EnthSP | Enthalpy setpoint (range 20-28 BTU/lbs) | BTU/lb | Write | |
| AV | 78 | MATSP | Mixed air temperature for economizer (range 0.0-140°F (0.0-60°C)) | °F | Write | |
| AV | 79 | MAT | Mixed air temperature (range 0.0-140°F (0.0-60°C)) | °F | Read | |
| BV | 2 | OVRSTAT | Occupancy override status | Read | Inactive = Normal, Active = Override | |
| BV | 3 | Mot_Det | Motion detection | Read | Inactive = None, Active = Moving | |
| BV | 4 | AutogenDesc | Autogenerate I/O descriptions | Write | Inactive = Off, Active = On | |
| BVmin | 5 | Occ_Sch | System occupancy schedule | Write | Inactive = Off, Active = On | |
| BV | 7 | Freeze_Status | Freeze condition status | Read | Inactive = Normal, Active = Active | |
| BV | 8 | Free_CL_Status | Free cooling authorization status | Read | Inactive = No, Active = Yes | |
| BV | 21 | EnthalpyAuth | Enthalpy Authorize | Read | Inactive = No, Active = Yes | |
| MV | 1 | CFGSens | Remote thermistor 10K | Write | 1 = Type 3, 2 = Type 2 | |
| MV | 2 | AI_RS | Select room temperature input | Write | 1 = Intern, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5 | |
| MVmin | 3 | MODE | System mode | Write | 1 = Off, 2 = Auto, 3 = Cool, 4 = Heat | |
| MVmin | 4 | FAN | Set fan mode | Write | 1 = On, 2 = Auto | |
| MV | 5 | Eff_Occ | Effective occupancy mode | Read | 1 = Occupied, 2 = Unoccup, 3 = TempOcc, 4 = Standby | |
| MV | 6 | Occ_Cmd | Occupancy command | Write | 1 = Loc-Occ, 2 = Occupied, 3 = Unoccup | |
| MV | 7 | CFG_Y1 | Set cooling output 1 operation | Write | 1 = None, 2 = Off-On, 3 = 0-10V DA (direct), 4 = 0-10V RA (reversed), 5 = 2-10V DA (direct), 6 = 2-10V RA (reversed), 7 = Pulsed DA (direct), 8 = Pulsed RA (reversed) | |
| MV | 8 | CFG_Y2 | Set cooling output 2 operation | Write | 1 = None, 2 = Off-On, 3 = 0-10V DA (direct), 4 = 0-10V RA (reversed), 5 = 2-10V DA (direct), 6 = 2-10V RA (reversed), 7 = Pulsed DA (direct), 8 = Pulsed RA (reversed) | |
| MV | 9 | CFG_Y3 | Set cooling output 3 operation | Write | 1 = None, 2 = Off-On | |
| MV | 10 | CFG_Y4 | Set cooling output 4 operation | Write | 1 = None, 2 = Off-On | |
| MV | 16 | CFG_W1 | Set heating output 1 operation | Write | 1 = None, 2 = Off-On, 3 = 0-10V DA (direct), 4 = 0-10V RA (reversed), 5 = 2-10V DA (direct), 6 = 2-10V RA (reversed), 7 = Pulsed DA (direct), 8 = Pulsed RA (reversed), 9 = O (O/B), 10 = B (O/B) | |
| MV | 17 | CFG_W2 | Set heating output 2 operation | Write | 1 = None, 2 = Off-On, 3 = 0-10V DA (direct), 4 = 0-10V RA (reversed), 5 = 2-10V DA (direct), 6 = 2-10V RA (reversed), 7 = Pulsed DA (direct), 8 = Pulsed RA (reversed), 9 = O (O/B), 10 = B (O/B) | |
| MV | 18 | CFG_W3 | Set heating output 3 operation | Write | 1 = None, 2 = Off-On | |
| MV | 19 | CFG_W4 | Set heating output 4 operation | Write | 1 = None, 2 = Off-On | |
| MV | 23 | CFG_FAN | Select fan output | Write | 1 = BO-1, 2 = BO-2, 3 = AO-1, 4 = AO-2, 5 = BO-1 & AO-1, 6 = BO-1 & AO-2 | |
| MV | 27 | AI_OAT | Select outside air temp. input | Write | 1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5, 7 = External | |
| MV | 28 | AI_SAT | Select supply air temp. input | Write | 1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5, 7 = External | |
| MV | 30 | AO_ECO | Select economizer output | Write | 1 = None, 2 = BO-5, 3 = BO-6, 4 = BO-7, 5 = AO-1, 6 = AO-2, 7 = AO-3 | |
| MV | 32 | CFG_EXH | Select power exhaust output | Write | 1 = None, 2 = BO-6, 3 = BO-7, 4 = AO-3, 5 = BO-6 & AO-3, 6 = BO-7 & AO-3 | |
| MV | 44 | BI_PIR | Select PIR Motion sensor input | Write | 1 = None, 2 = NO, AI1 (BI), 3 = NC, AI1 (BI), 4 = NO, AI2 (BI), 5 = NC, AI2 (BI), 6 = NO, AI3 (BI), 7 = NC, AI3 (BI), 8 = NO, AI4 (BI), 9 = NC, AI4 (BI), 10 = External, 11 = Intern | |
| MV | 45 | BI_SCH_Input | Select schedule input | Write | 1 = None (Off), 2 = None (On), 3 = Scheduler, 4 = AI-1, 5 = AI-2, 6 = AI-3, 7 = AI-4, 8 = AI-5, 9 = External | |
| MV | 48 | BO_HUM | Select humidifier BO output | Write | 1 = None, 2 = BO-2, 3 = BO-3, 4 = BO-4, 5 = BO-5, 6 = BO-6, 7 = BO-7, 8 = BO-5 & BO-6 (Two stages), 9 = BO-6 & BO-7 (Two stages) | |
| MV | 49 | AO_HUM | Select humidifier AO output | Write | 1 = None, 2 = AO-1, 3 = AO-2, 4 = AO-3 | |
| MV | 52 | AI_RH | Select room humidity input | Write | 1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5, 7 = External, 8 = Intern | |
| MV | 54 | AI_SRH | Select supply humidity input | Write | 1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5, 7 = External | |
| MV | 55 | AIC_SRH | Set supply humidity input signal | Write | 1 = 0-10V, 2 = 2-10V | |
| MV | 57 | OAH_Loc | Outside humidity physical input loc. | Write | 1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5, 7 = External, 8 = Intern | |
| MV | 58 | MAT_Loc | Mixed air temperature sensor loc. | Write | 1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5, 7 = External | |
| MV | 62 | CFGSetp | Room setpoint displayed | Write | 1 = Heat SP, 2 = Center, 3 = Cool SP | |
| MV | 65 | BO_OCC | Select occupied output | Write | 1 = None, 2 = BO-2, 3 = BO-3, 4 = BO-4, 5 = BO-5, 6 = BO-6, 7 = BO-7, 8 = AO-1, 9 = AO-2, 10 = AO-3 | |
| MV | 66 | AI1_CFG | Select predefined AI1 logic | Write | 1 = None, 2 = NSB, 3 = OVR, 4 = FILTER, 5 = SERVICE, 6 = FANSTATUS | |
| MV | 67 | AI2_CFG | Select predefined AI2 logic | Write | 1 = None, 2 = NSB, 3 = OVR, 4 = FILTER, 5 = SERVICE, 6 = FANSTATUS | |
| MV | 68 | BO_DEHU | Select dehumidification output | Write | 1 = None, 2 = BO-2, 3 = BO-3, 4 = BO-4, 5 = BO-5, 6 = BO-6, 7 = BO-7 | |
| MV | 70 | PB | CFG Heating/cooling proportional band | Write | 1 = 3F 1.2C, 2 = 4F 1.7C, 3 = 5F 2.2C, 4 = 6F 2.8C, 5 = 7F 3.3C, 6 = 8F 3.5C, 7 = 9F 5.0C, 8 = 10F 5.6C | |
| MVmin | 100 | HELP_mess | Help message | Read | 1 = Normal, 2 = FanLock, 3 = SupplyFrozen, 4 = Service, 5 = Filter, 6 = Rem NSB Ovr | |
| MV | 127 | Preset | Select application | Write | 1 = RT 2STG, 2 = RT ECON, 3 = HP 2STG, 4 = RT IAQ, 5 = RT MOD, 6 = HP DEH, 7 = HUM-DEH, 8 = RT 3STG, 9 = RT 4STG, 10 = HP 3STG | |
| MV | 200 | Brightness | Brightness Control | Write | 1 = Low, 2 = Med-Low, 3 = Med | |
| MV | 201 | BgColor | Background Color | Write | 1 = White, 2 = Orange, 3 = Blue, 4 = Green, 5 = Red | |
| MV | 202 | LockTemp | Main Display | Write | 1 = Temp, 2 = Setpoint, 3 = Nothing | |
| MV | 203 | Language | Language selection | Write | 1 = English | |
| MV | 204 | Display_Units | Temperature displayed units | Write | 1 = C, 2 = F | |
| MV | 205 | System_Unit | System/Database Unit | Write | 1 = Metric, 2 = Imperial | |
| MV | 221 | Radar_Status | Radar_status | Write | 1 = Disable, 2 = Enable | |
| MV | 223 | Detection_range | Detection_range | Write | Range: 1_m to 7_m | |
| MV | 235 | Radar_Freq | pll_frequency_word | Write | Range: Channel 1 to 8 | |
| MV | 244 | Sensitivity | duty_cycle_repetition_r | Write | 1 = Low, 2 = Medium, 3 = High, 4 = very-high | |
| LO | 1 | RoomT_Cool | Room temp cooling control loop | % | Read | |
| LO | 2 | RoomT_heat | Room temp heating control loop | % | Read | |
| LO | 6 | SupplyTemp | Supply temp control loop | % | Read | |
| LO | 7 | SupplyTempHL | Supply temp high limit control loop | % | Read | |
| LO | 8 | SupplyTempLL | Supply temp low limit control loop | % | Read | |
| LO | 10 | Room_RH | Room RH control loop | % | Read | |
| LO | 11 | Supply_RH_HL | Supply RH hi limit control loop | % | Read | |
| LO | 12 | PidMAT | Mix air T control for economizer | % | Read | |
| SCH | 1 | OccSchedule | Occupancy schedule | Write |
No points match these filters.
Object ID lookup: Strato Automation OPENSTAT OS537 thermostat, RTU firmware point IDs by name
BO1BO_1BO2BO_2BO3BO_3BO4BO_4BO5BO_5BO6BO_6BO7BO_7AO1AO_1AO2AO_2AO3AO_3AI1AI_1AI2AI_2AI3AI_3AI4AI_4AI5AI_5AI6RoomTAI7RoomRHAI8RoomCO2BI1MotionAV1RoomTSPAV6HTG_DemAV7CLG_DemAV9Eff_TAV16SATempAV19SATFRSP_SetAV21ECM_min_SetAV24Fan_MinOn_TimeAV27OvrTime_SetAV29OATempAV31CO2_SP_SetAV33MinCLSPAV34MaxHTSPAV35OccCLSPAV36OccHTSPAV37SP_DB_SetAV38Unoc_CL_SetAV39Unoc_HT_SetAV40STBCoolOffsetAV41STBHeatOffsetAV42EffCLSPAV43EffHTSPAV50RT_CalAV51Eff_RHAV52HUM_SPAV53SAHAV54SAH_HL_SetAV55DEH_SPAV56SAT_HL_SetAV57SAT_CTR_SetAV58SAT_LL_SetAV59Eff_SATAV60ComprLockoutAV65EconoMin_PosAV66EconoMaxCO2PosAV67OATheatOutAuthAV68OATeconOutAuthAV75OAHAV76OAEAV77EnthSPAV78MATSPAV79MATBV2OVRSTATBV3Mot_DetBV4AutogenDescBV5Occ_SchBV7Freeze_StatusBV8Free_CL_StatusBV21EnthalpyAuthMV1CFGSensMV2AI_RSMV3MODEMV4FANMV5Eff_OccMV6Occ_CmdMV7CFG_Y1MV8CFG_Y2MV9CFG_Y3MV10CFG_Y4MV16CFG_W1MV17CFG_W2MV18CFG_W3MV19CFG_W4MV23CFG_FANMV27AI_OATMV28AI_SATMV30AO_ECOMV32CFG_EXHMV44BI_PIRMV45BI_SCH_InputMV48BO_HUMMV49AO_HUMMV52AI_RHMV54AI_SRHMV55AIC_SRHMV57OAH_LocMV58MAT_LocMV62CFGSetpMV65BO_OCCMV66AI1_CFGMV67AI2_CFGMV68BO_DEHUMV70PBMV100HELP_messMV127PresetMV200BrightnessMV201BgColorMV202LockTempMV203LanguageMV204Display_UnitsMV205System_UnitMV221Radar_StatusMV223Detection_rangeMV235Radar_FreqMV244SensitivityLO1RoomT_CoolLO2RoomT_heatLO6SupplyTempLO7SupplyTempHLLO8SupplyTempLLLO10Room_RHLO11Supply_RH_HLLO12PidMATSCH1OccSchedule
Integration notes
- The guide has no read/write column. Access here follows its tags: Cfg, User and Cmd objects are shown writable, Status objects read-only, and BO/AO objects commandable (the guide lists them for output overrides). BV-5 (Occ_Sch) is tagged Status but shown writable because the guide says it can be written for occupancy.
- AI-8 RoomCO2 exists only on C models such as the OS537MHC.
- BO and AO descriptions are generated from the MSV-127 preset when BV-4 is On.
- Multistate state numbers follow the order the states are printed, starting at 1; MSV-223 and MSV-235 print a range.
- AV-35 and AV-36 (occupied setpoints) are tagged Status in this guide.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OPENSTAT OS537 thermostat, RTU firmware and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Strato Automation OPENSTAT OS537 thermostat, RTU firmware
How many BACnet points does the Strato Automation OPENSTAT OS537 thermostat, RTU firmware have?
This list has 123 BACnet objects: 8 analog inputs, 3 analog outputs, 42 analog values, 1 binary input, 7 binary outputs, 7 binary values, 8 loops, 1 schedule, 46 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Strato Automation OPENSTAT OS537 thermostat, RTU firmware BACnet points are writable?
84 of the 123 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Strato Automation OPENSTAT OS537 thermostat, RTU firmware BACnet documentation?
The source is OS537 (Universal Firmware) User Guide, Rooftop Unit (RTU) - BACnet Objects, revision July 2026 rev 0, published free by Strato Automation at https://stratoautomation.com/wp-content/uploads/2025/08/OS537-User-Guide-July-2026-rev-0.pdf.
What are the minimum BACnet points to integrate the Strato Automation OPENSTAT OS537 thermostat, RTU firmware?
Start with MV 3 MODE (System mode: Off, Auto, Cool, Heat); MV 4 FAN (Fan mode: On / Auto); BV 5 Occ_Sch (Occupancy schedule; BMS can write On/Off); AV 1 RoomTSP (Room temperature setpoint); AI 6 RoomT (Room temperature); AI 7 RoomRH (Room humidity); AV 6 HTG_Dem (Heating demand, %); AV 7 CLG_Dem (Cooling demand, %); AV 16 SATemp (Supply air temperature); MV 100 HELP_mess (Alarm / help message).
How do I enable BMS control of the Strato Automation OPENSTAT OS537 thermostat, RTU firmware?
Occupancy can be written to BV-5; MSV-45 selects the schedule source and MSV-6 forces local, occupied or unoccupied.
Can the BMS supply sensor values to the Strato Automation OPENSTAT OS537 thermostat, RTU firmware?
Sensor location MSVs (MSV-2, 27, 28, 52, 54, 57, 58) can be set to 'External' to take the value from the network.
How do I check these points on the real OPENSTAT OS537 thermostat, RTU firmware?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Strato Automation BACnet points lists
- Thermostat (BACnet MS/TP)
Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware
Strato OS214 / OS214W room thermostats running the fan coil (2-pipe / 4-pipe) application of the universal firmware.
Also known as: OS214, OS214W, OS214x, OpenStat OS214, OS214-FCU, Strato OS214 - Thermostat (BACnet MS/TP)
Strato Automation OPENSTAT OS214 / OS214x thermostat, RTU firmware
Strato OS214 / OS214W (Wi-Fi) room thermostats running the rooftop-unit / heat-pump application of the universal firmware.
Also known as: OS214, OS214W, OS214x, OpenStat OS214, OS214-RTU, Strato OS214 - Thermostat (BACnet MS/TP)
Strato Automation OPENSTAT OS214-EH electric heat thermostat
Strato OS214-EH thermostats controlling electric heat (baseboard, duct heater) from room and/or supply temperature.
Also known as: OS214-EH, OS214EH, OpenStat OS214-EH, Strato OS214-EH - Thermostat (BACnet MS/TP)
Strato Automation OPENSTAT OS537 thermostat, FCU firmware
Strato OS537 thermostats running the 2-pipe / 4-pipe fan coil application of the universal firmware.
Also known as: OS537, OS537H, OS537MHC, OpenStat OS537, OS537-FCU, Strato OS537 - Thermostat (BACnet MS/TP)
Strato Automation OPENSTAT OS537H-EH electric heat staging thermostat
Strato OS537H-EH thermostats controlling electric heat with up to six stages plus an SSR/SCR vernier stage.
Also known as: OS537H-EH, OS537HEH, OpenStat OS537H-EH, Strato OS537H-EH
Source: OS537 (Universal Firmware) User Guide, Rooftop Unit (RTU) - BACnet Objects · rev. July 2026 rev 0. Object names, instances and units are reproduced as published; descriptions are our own.