Easy BACnet
  1. Home
  2. BACnet points lists
  3. Strato Automation
  4. OPENSTAT OS537 thermostat, FCU firmware

Thermostat (BACnet MS/TP) · BACnet points list

Strato Automation OPENSTAT OS537 thermostat, FCU firmware BACnet points list

Updated 12 November 2026

Short answer

In its fan coil application the OS537 drives on/off, floating or 0-10 V valves, a three-speed or ECM fan and an auxiliary output (reheat, occupancy, fan or network-controlled) over BACnet MS/TP. The object list has setpoints, mode, fan and occupancy commands, door, window, filter and service inputs, changeover and fan status, demands and two PID loops.

This page lists 108 BACnet objects for the Strato Automation OPENSTAT OS537 thermostat, FCU firmware — 66 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Strato Automation’s own free documentation, linked below.

Manufacturer
Strato Automation
Model
OPENSTAT OS537 thermostat, FCU firmware
Equipment
Thermostat (BACnet MS/TP)
Equipment type
Thermostats, sensors & meters
BACnet objects
108 (66 writable)
Transport
BACnet MS/TP
Firmware
Universal firmware 1.2.6 and later
Also known as
OS537, OS537H, OS537MHC, OpenStat OS537, OS537-FCU, Strato OS537
Source document
OS537 (Universal Firmware) User Guide, Fan Coil Unit (FCU) - BACnet Objects · rev. July 2026 rev 0
Download CSV 108 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Strato Automation’s current documentation and the live device before use. Not official Strato Automation information. Terms of use.

BMS integration notes: Strato Automation OPENSTAT OS537 thermostat, FCU firmware

Integration in brief

Command system mode (MSV-16), fan mode (MSV-17) and occupancy (MSV-6) and write the room setpoint (AV-1). Read room temperature, demands, fan status and the door, window, filter and service status points.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 16MODESystem mode: Off, Auto, Cool, HeatWrite
MV 17FANFan mode: Lo, Med, Hi, AutoWrite
MV 6Occ_CmdOccupancy command: local, occupied, unoccupiedWrite
AV 1RoomTSPRoom temperature setpointWrite
AI 6RoomTRoom temperatureRead
MV 5Eff_OccEffective occupancyRead
AV 21HTG_DemHeating demand, %Read
AV 22CLG_DemCooling demand, %Read
BV 15FanStatFan running statusRead
MV 100HELP_messAlarm message: Service, Filter, WindowRead

Enable & remote start

MSV-6 Occ_Cmd (tagged Cmd) sets occupancy from the BMS; BV-14 Aux_Cmd switches the auxiliary output when MSV-54 = Network.

Network setup

Watch out for

Strato Automation OPENSTAT OS537 thermostat, FCU firmware BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

108 of 108 shown
Type
Multi-state
Access
Show
Strato Automation OPENSTAT OS537 thermostat, FCU firmware BACnet Points List
DescriptionStates
BO1BO_1Binary output 1Command
BO2BO_2Binary output 2Command
BO3BO_3Binary output 3Command
BO4BO_4Binary output 4Command
BO5BO_HighHigh-speed fan outputCommand
BO6BO_MedMedium-speed fan outputCommand
BO7BO_LowLow-speed fan outputCommand
AO1AO_ECMFan ECM output; dependent on MSV-58Command
AO2AO_2Analog output 2%Command
AO3AO_3Analog output 3%Command
AI1AI_1Analog input 1; dependent on MSV-46Read
AI3AI_3Analog input 3; dependent on MSV-48Read
AI4AI_4Remote room sensor°FRead
AI5AI_5UnusedRead
AImin6RoomTRoom temperature°FRead
AI7RoomRHRoom humidity%Read
AI8RoomCO2Room CO2ppmRead
BI1MotionMotion detectionReadOff / Active
AVmin1RoomTSPRoom Temperature setpoint (range 54-90°F (12-32°C))°FWrite
AV7Eff_TEffective temperature used for control (range -40-122°F (-40-50°C))°FRead
AV9OATempOutdoor air temperature (range -40-122°F (-40-50°C))°FRead
AV12SATempSupply air temperature (range -40-122°F (-40-50°C))°FRead
AV13CHOV_TChangeover temperature (range -40-122°F (-40-50°C))°FRead
AVmin21HTG_DemHeating demand (range 0-100%)%Read
AVmin22CLG_DemCooling demand (range 0-100%)%Read
AV23Fan_HT__DemandFan heating demand (range 0-100%)%Read
AV24Fan_CL__DemandFan cooling demand (range 0-100%)%Read
AV25ECM_MinECM minimum speed output (range 0-100%)%Write
AV27OvrTime_SetSet occupancy override time (range 15 – 480 min)minWrite
AV28MotionOvrTime_SetMotion Set occupancy override time (range 1 – 60 min)minWrite
AV30EffHTSPEffective heating setpointRead
AV31EffCLSPEffective cooling setpointRead
AV39OccHTSPOccupied heating setpointRead
AV40OccCLSPOccupied cooling setpointRead
AV41STBHTSPStandby heating setpoint°FWrite
AV42STBCLSPStandby cooling setpoint°FWrite
AV43Unoc_HT_SPUnoccupied heating setpoint°FWrite
AV44Unoc_CL_SPUnoccupied cooling setpoint°FWrite
AV50RT_CalRoom temperature calib (range -5 to 5)Write
AV58MaxHTSPMaximum heating setpoint (range 40-90°F (4.5-32°C))°FWrite
AV59MinCLSPMinimum cooling setpoint (range 54-100°F (12-37.5°C))°FWrite
AV63SP_DBSetpoint deadband (range 2 to 5)Write
BV2OVRSTATOccupancy override statusReadInactive = Normal, Active = Overrid
BV3Mot_DetMotion detectionReadInactive = None, Active = Moving
BV5OccSchSystem occupancy scheduleReadInactive = Off, Active = On
BV14Aux_CmdAuxiliary network commandWriteInactive = Off, Active = On
BVmin15FanStatFan statusReadInactive = Stopped, Active = Running
BV25AuxStatAuxiliary output statusReadInactive = Off, Active = On
BV29AI1StatAnalog input 1 binary contact statusReadInactive = Deactivated, Active = Activated
BV30AI2StatAnalog input 2 binary contact statusReadInactive = Deactivated, Active = Activated
BV31AI3StatAnalog input 3 binary contact statusReadInactive = Deactivated, Active = Activated
BV35WindowWindow detection statusReadInactive = Close, Active = Open
BV36FilterFilter sensor statusReadInactive = Normal, Active = Alarm
BV37ServALMService alarm statusReadInactive = Normal, Active = Alarm
BV38DoorDoor detection statusReadInactive = Close, Active = Open
BV40Ch_OverChange over statusReadInactive = Cool, Active = Heat
BV50AutoModAuto mode authorizedWriteInactive = No, Active = Yes
BV64Reh_OptReheat control optionWriteInactive = Pulse1S, Active = On-Off
BV66KeepFanFan auto modeWriteInactive = Fan Low, Active = Fan Off
BV75VALVCTLValve motor control typeWriteInactive = On-Off, Active = Floating
BV78AO2_DirAO2 actionWriteInactive = Direct, Active = Reverse
BV79AO3_DirAO3 actionWriteInactive = Direct, Active = Reverse
BV200LockStPointLock SetpointWriteInactive = Unlock, Active = Lock
BV201LockModeLock ModeWriteInactive = Unlock, Active = Lock
BV202LockFanLock FanWriteInactive = Unlock, Active = Lock
BV203WifiStatusWifi StatusReadInactive = Off, Active = On
MV2TsourceTemperature input locationWrite1 = AutoDet, 2 = Intern, 3 = AI-4
MVmin5Eff_OccEffective occupancy modeRead1 = Occupied, 2 = Unoccup, 3 = TempOcc, 4 = Standby
MVmin6Occ_CmdOccupancy commandWrite1 = Loc_Occ, 2 = Occupied, 3 = Unoccup
MV15SeqOperControl sequence of operationWrite1 = Cooling, 2 = Heating, 3 = Cool-Rt, 4 = Heat-Rt, 5 = Cl-Ht
MVmin16MODESystem modeWrite1 = Off, 2 = Auto, 3 = Cool, 4 = Heat
MVmin17FANFan modeWrite1 = Lo, 2 = Med, 3 = Hi, 4 = Auto
MV19KeyLockKeypad lock levelWrite1 = None, 2 = Fan, 3 = Mode, 4 = FanMode, 5 = All
MV26BO3_BO4BO3/BO4 statusRead1 = Stopped, 2 = Open, 3 = Close
MV27BO1_BO2BO1/BO2 statusRead1 = Stopped, 2 = Open, 3 = Close
MV28FanStatFan statusRead1 = Off, 2 = Low, 3 = Med, 4 = High
MV44Bi_PIRSelect PIR Motion sensor inputWrite1 = None, 2 = NO, AI1 (BI), 3 = NC, AI1 (BI), 4 = NO, AI2 (BI), 5 = NC, AI2 (BI), 6 = NO, AI3 (BI), 7 = NC, AI3 (BI), 8 = NO, AI4 (BI), 9 = NC, AI4 (BI), 10 = NO, AI5 (BI), 11 = NC, AI5 (BI), 12 = External, 13 = Intern
MV45BI_SCH_InputSelect schedule inputWrite1 = None (Off), 2 = None (On), 3 = Scheduler, 4 = AI-1, 5 = AI-2, 6 = AI-3, 7 = AI-4, 8 = AI-5, 9 = External
MV47AI2_CFGCFG Analog input 2Write1 = None, 2 = Overrid (remote override switch), 3 = Filter, 4 = Service
MV48AI3_CFGCFG Analog input 3Write1 = None, 2 = COC/NH (Normally Heat ChangeOver Contact), 3 = COC/NH (Normally Cool ChangeOver Contact), 4 = COS (ChangeOver Sensor), 5 = SS (Supply sensor remote monitoring 10K type 3 sensor)
MV49Door_LocDoor contact input locationWrite1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5
MV51Windows_LocWindow contact input locationWrite1 = None, 2 = AI-1, 3 = AI-2, 4 = AI-3, 5 = AI-4, 6 = AI-5
MV50AI5_CFGCFG Analog Input 5Write1 = None, 2 = Fan Lock
MV52PipeNumPipe numberWrite1 = 2 Pipes, 2 = 4 Pipes
MV54Aux_CFGAuxiliary output configurationWrite1 = Reheat, 2 = Occ-NO, 3 = Occ-NC, 4 = Fan-NO, 5 = Fan-NC, 6 = Network (Can be controlled by BACnet)
MV55ReheatReheat typeWrite1 = Basebrd, 2 = Coil
MV58Fan_SeqControl fan sequenceWrite1 = L-M-H, 2 = L-H, 3 = L-M-H-A, 4 = L-H-A, 5 = On-Auto (Single speed or 0-10Vdc)
MV65PBHeating/Cooling proportional bandWriteRange: 3 F (1.2 C) - 10 F (5.6 C)
MV70Display_SPSetpoint displayed for userWrite1 = Heating, 2 = Center, 3 = Cooling
MV75BO3TimeBO3/BO4 travel time for 3 states valveWriteRange: 0.5 min - 6 min
MV76BO1TimeBO1/BO2 travel time for 3 states valveWriteRange: 0.5 min - 6 min
MV77CL_CPHCooling output cycle per hourWriteRange: 3 - 8 CPH
MV78HT_CPHHeating output cycle per hourWriteRange: 3 - 8 CPH
MVmin100HELP_messHelp messageRead1 = Normal, 2 = Service, 3 = Filter, 4 = Window
MV200BrightnessBrightness ControlWrite1 = Low, 2 = Med-Low, 3 = Med
MV201BgColorBackground ColorWrite1 = White, 2 = Orange, 3 = Blue, 4 = Green, 5 = Red
MV202MainDisplayMain DisplayWrite1 = Temp, 2 = Setpoint, 3 = Nothing
MV203LanguageLanguage selectionWrite1 = English
MV204Display_UnitsTemperature displayed unitsWrite1 = C, 2 = F
MV205System_UnitSystem/Database UnitWrite1 = Metric, 2 = Imperial
MV221Radar_StatusRadar_statusWrite1 = Disable, 2 = Enable
MV223Detection_rangeDetection_rangeWriteRange: 1_m to 7_m
MV235Radar_Freqpll_frequency_wordWriteRange: Channel 1 to 8
MV244Sensitivityduty_cycle_repetition_rWrite1 = Low, 2 = Medium, 3 = High, 4 = very-high
LO1PIDZoneCoolPID Zone cooling%Read
LO2PIDZoneHeatPID Zone heating%Read
SCH1OccScheduleOccupancy scheduleWrite
AI2AI_2Analog input 2; dependent on MSV-47Read
Object ID lookup: Strato Automation OPENSTAT OS537 thermostat, FCU firmware point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OPENSTAT OS537 thermostat, FCU firmware and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Strato Automation OPENSTAT OS537 thermostat, FCU firmware

How many BACnet points does the Strato Automation OPENSTAT OS537 thermostat, FCU firmware have?

This list has 108 BACnet objects: 8 analog inputs, 3 analog outputs, 24 analog values, 1 binary input, 7 binary outputs, 24 binary values, 2 loops, 1 schedule, 38 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Strato Automation OPENSTAT OS537 thermostat, FCU firmware BACnet points are writable?

66 of the 108 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Strato Automation OPENSTAT OS537 thermostat, FCU firmware BACnet documentation?

The source is OS537 (Universal Firmware) User Guide, Fan Coil Unit (FCU) - BACnet Objects, revision July 2026 rev 0, published free by Strato Automation at https://stratoautomation.com/wp-content/uploads/2025/08/OS537-User-Guide-July-2026-rev-0.pdf.

What are the minimum BACnet points to integrate the Strato Automation OPENSTAT OS537 thermostat, FCU firmware?

Start with MV 16 MODE (System mode: Off, Auto, Cool, Heat); MV 17 FAN (Fan mode: Lo, Med, Hi, Auto); MV 6 Occ_Cmd (Occupancy command: local, occupied, unoccupied); AV 1 RoomTSP (Room temperature setpoint); AI 6 RoomT (Room temperature); MV 5 Eff_Occ (Effective occupancy); AV 21 HTG_Dem (Heating demand, %); AV 22 CLG_Dem (Cooling demand, %); BV 15 FanStat (Fan running status); MV 100 HELP_mess (Alarm message: Service, Filter, Window).

How do I enable BMS control of the Strato Automation OPENSTAT OS537 thermostat, FCU firmware?

MSV-6 Occ_Cmd (tagged Cmd) sets occupancy from the BMS; BV-14 Aux_Cmd switches the auxiliary output when MSV-54 = Network.

How do I check these points on the real OPENSTAT OS537 thermostat, FCU firmware?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Strato Automation BACnet points lists

Source: OS537 (Universal Firmware) User Guide, Fan Coil Unit (FCU) - BACnet Objects · rev. July 2026 rev 0. Object names, instances and units are reproduced as published; descriptions are our own.