Thermostat (BACnet MS/TP) · BACnet points list

Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware BACnet points list

Updated 12 November 2026

Short answer

In its fan coil unit (FCU) application the OS214 drives a valve (BO-1 or AO-1) and a three-speed fan (BO-2 to BO-4) over BACnet MS/TP. The object list gives setpoints, mode, fan mode and occupancy commands, changeover and fan status, demands and two PID loops. It shares 38 object IDs with the RTU list but many objects differ.

This page lists 58 BACnet objects for the Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware — 39 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Strato Automation’s own free documentation, linked below.

Manufacturer
Strato Automation
Model
OPENSTAT OS214 / OS214x thermostat, FCU firmware
Equipment
Thermostat (BACnet MS/TP)
Equipment type
Thermostats, sensors & meters
BACnet objects
58 (39 writable)
Transport
BACnet MS/TP
Firmware
Universal firmware 1.0.4 and later
Also known as
OS214, OS214W, OS214x, OpenStat OS214, OS214-FCU, Strato OS214
Source document
OS214x (Universal Firmware) User Guide, Fan Coil Unit (FCU) - BACnet Objects · rev. Sept 2025 rev 5
Download CSV 58 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Strato Automation’s current documentation and the live device before use. Not official Strato Automation information. Terms of use.

BMS integration notes: Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware

Integration in brief

Command the fan coil with the system mode (MSV-16), fan mode (MSV-17) and occupancy command (MSV-18), and write the room setpoint (AV-1). Read room temperature, demands, fan status (MSV-28) and changeover status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 16MODESystem mode: Off, N/A, Cool, HeatWrite
MV 17FANFan mode: Lo, Med, Hi, AutoWrite
MV 18Occ_CmdOccupancy command: local, occupied, unoccupiedWrite
AV 1RoomTSPRoom temperature setpointWrite
AI 6RoomTRoom temperatureRead
MV 33Eff_OccEffective occupancyRead
AV 21HTG_DemHeating demand, %Read
AV 22CLG_DemCooling demand, %Read
MV 28FanStatFan speed statusRead
BV 40Ch_OverChangeover: cool / heatRead

Enable & remote start

MSV-18 Occ_Cmd (tagged Cmd) sets occupancy from the BMS: Loc_Occ, Occupied or Unoccup.

Network setup

Watch out for

Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

58 of 58 shown
Type
Multi-state
Access
Show
Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware BACnet Points List
DescriptionStates
BO1BO_1ValveCommand
BO2BO_HighHigh-speed fan outputCommand
BO3BO_MedMedium-speed fan outputCommand
BO4BO_LowLow-speed fan outputCommand
AO1AO_1Valve 0-10Vdc%Command
AI1AI_1Analog input 1; dependent on MSV-48Read
AImin6RoomTRoom temperature°FRead
AVmin1RoomTSPRoom Temperature setpoint (range 54-90°F (12-32°C))°FWrite
AV7Eff_TEffective temperature used for control (range -40-122°F (-40-50°C))°FRead
AV13Chov_TChangeover temperature (range -40-122°F (-40-50°C))°FRead
AVmin21HTG_DemHeating demand (range 0-100%)%Read
AVmin22CLG_DemCooling demand (range 0-100%)%Read
AV23Fan_HT__DemandFan heating demand (range 0-100%)%Read
AV24Fan_CL__DemandFan cooling demand (range 0-100%)%Read
AV30EffHTSPEffective heating setpoint°FRead
AV31EffCLSPEffective cooling setpoint°FRead
AV39OccHTSPOccupied heating setpoint°FWrite
AV40OccCLSPOccupied cooling setpoint°FWrite
AV43Unoc_HT_SPUnoccupied heating setpoint°FWrite
AV44Unoc_CL_SPUnoccupied cooling setpoint°FWrite
AV50RT_CalRoom temperature calib (range -5 to 5)Write
AV58MaxHTSPMaximum heating setpoint (range 40-90°F (4.5-32°C))°FWrite
AV59MinCLSPMinimum cooling setpoint (range 54-100°F (12-37.5°C))°FWrite
AV63SP_DBSetpoint deadband (range 2 to 5)Write
BV8OVRSTATOccupancy override statusReadInactive = Normal, Active = Overrid
BV29AI1StatAnalog input 1 binary contact statusReadInactive = Deactivated, Active = Activated
BVmin40Ch_OverChange over statusReadInactive = Cool, Active = Heat
BV50AutoModAuto mode authorizedWriteInactive = No, Active = Yes
BV66KeepFanFan auto modeWriteInactive = Fan Low, Active = Fan Off
BV78AO1_DirCFG AO1 actionWriteInactive = Direct, Active = Reverse
BV200LockStPointLock SetpointWriteInactive = Unlock, Active = Lock
BV201LockModeLock ModeWriteInactive = Unlock, Active = Lock
BV202LockFanLock FanWriteInactive = Unlock, Active = Lock
BV203WifiStatusWifi StatusReadInactive = Off, Active = On
MV1CFGSensRemote thermistor 10KWrite1 = Type 3, 2 = Type 2
MV2TsourceTemperature input locationWrite1 = AutoDet, 2 = Intern, 3 = AI-1, 4 = AI-2
MV14Valve_TypeChange operation of BO1 and AO1Write1 = N.C., 2 = N.O.
MV15SeqOperControl sequence of operationWrite1 = Cooling, 2 = Heating
MVmin16MODESystem modeWrite1 = Off, 2 = N/A, 3 = Cool, 4 = Heat
MVmin17FANFan modeWrite1 = Lo, 2 = Med, 3 = Hi, 4 = Auto
MVmin18Occ_CmdOccupancy commandWrite1 = Loc_Occ, 2 = Occupied, 3 = Unoccup
MVmin28FanStatFan statusRead1 = Off, 2 = Low, 3 = Med, 4 = High
MVmin33Eff_OccEffective occupancy modeRead1 = Occupied, 2 = Unoccup, 3 = TempOcc
MV48AI1_CFGAnalog input 1 configurationWrite1 = None, 2 = COC/NH (Normally Heat ChangeOver Contact), 3 = COC/NC (Normally Cool ChangeOver Contact), 4 = COS (ChangeOver Sensor), 5 = SS (Supply sensor remote monitoring 10K sensor)
MV58Fan_SeqControl fan sequenceWrite1 = L-M-H, 2 = L-H, 3 = L-M-H-A, 4 = L-H-A, 5 = On-Auto (use for single speed)
MV62OvrTimeOverride time delayWriteRange: 0 - 24 hours
MV65PBHeating/Cooling proportional bandWriteRange: 3 F (1.2 C) - 10 F (5.6 C)
MV70Display_SPSetpoint displayed for userWrite1 = Heating, 2 = Center, 3 = Cooling
MV77Valve_CPHValve output cycle per hourWriteRange: 3 - 8 CPH
MV200BrightnessBrightness controlWrite1 = Low, 2 = Med-Low, 3 = Med
MV201BgColorBackground colorWrite1 = White, 2 = Orange, 3 = Blue, 4 = Green, 5 = Red
MV202Display_MainMain displayed valueWrite1 = Temp, 2 = Setpoint, 3 = Nothing
MV203LanguageLanguage selectionWrite1 = English
MV204Display_UnitsTemperature displayed unitsWrite1 = C, 2 = F
LO1PIDZoneCoolPID Zone cooling%Read
LO2PIDZoneHeatPID Zone heating%Read
SCH1OccScheduleOccupancy scheduleWrite
AI2AI_2Analog input 2; dependent on MSV-2Read
Object ID lookup: Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OPENSTAT OS214 / OS214x thermostat, FCU firmware and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware

How many BACnet points does the Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware have?

This list has 58 BACnet objects: 3 analog inputs, 1 analog output, 17 analog values, 4 binary outputs, 10 binary values, 2 loops, 1 schedule, 20 multi-state values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware BACnet points are writable?

39 of the 58 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware BACnet documentation?

The source is OS214x (Universal Firmware) User Guide, Fan Coil Unit (FCU) - BACnet Objects, revision Sept 2025 rev 5, published free by Strato Automation at https://stratoautomation.com/wp-content/uploads/2026/01/OS214x-Universal-Firmware-User-Guide-Sept-2025-rev-5.pdf.

What are the minimum BACnet points to integrate the Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware?

Start with MV 16 MODE (System mode: Off, N/A, Cool, Heat); MV 17 FAN (Fan mode: Lo, Med, Hi, Auto); MV 18 Occ_Cmd (Occupancy command: local, occupied, unoccupied); AV 1 RoomTSP (Room temperature setpoint); AI 6 RoomT (Room temperature); MV 33 Eff_Occ (Effective occupancy); AV 21 HTG_Dem (Heating demand, %); AV 22 CLG_Dem (Cooling demand, %); MV 28 FanStat (Fan speed status); BV 40 Ch_Over (Changeover: cool / heat).

How do I enable BMS control of the Strato Automation OPENSTAT OS214 / OS214x thermostat, FCU firmware?

MSV-18 Occ_Cmd (tagged Cmd) sets occupancy from the BMS: Loc_Occ, Occupied or Unoccup.

How do I check these points on the real OPENSTAT OS214 / OS214x thermostat, FCU firmware?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Strato Automation BACnet points lists

Source: OS214x (Universal Firmware) User Guide, Fan Coil Unit (FCU) - BACnet Objects · rev. Sept 2025 rev 5. Object names, instances and units are reproduced as published; descriptions are our own.