Easy BACnet
  1. Home
  2. BACnet points lists
  3. Sierra Instruments
  4. InnovaSonic 207i Ultrasonic Liquid Flow Meter

Ultrasonic liquid flow and energy meter · BACnet points list

Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter BACnet points list

Updated 6 November 2026

Short answer

The InnovaSonic 207i is a clamp-on ultrasonic liquid flow meter that can also calculate thermal energy. With its BACnet MS/TP module it exposes 23 Analog Inputs (flow, velocity, flow and energy totals, temperatures, pressure, density, enthalpy, signal diagnostics and two error-flag words) and one Analog Value to reset the totalizers.

This page lists 24 BACnet objects for the Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Sierra Instruments’s own free documentation, linked below.

Manufacturer
Sierra Instruments
Model
InnovaSonic 207i Ultrasonic Liquid Flow Meter
Equipment
Ultrasonic liquid flow and energy meter
Equipment type
Thermostats, sensors & meters
BACnet objects
24 (1 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
207i, InnovaSonic 207i, Sierra 207i
Source document
InnovaSonic 207i BACnet Instruction Manual · IM-207i-BACnet · rev. V2.3/19
Download CSV 24 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Sierra Instruments’s current documentation and the live device before use. Not official Sierra Instruments information. Terms of use.

BMS integration notes: Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter

Integration in brief

Read flow, the net totalizer and, for energy metering, the energy flow rate and net energy total. Monitor the two error-flag AIs. Totalizers can be reset by writing AV-1.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1FlowFlow rateRead
AI 5NET TotalizerNet flow totalRead
AI 6Energy Flow RateThermal energy rateRead
AI 9Net Energy TotNet energy totalRead
AI 12QualitySignal quality, %Read
AI 22Error Flag 1Error flag word 1Read
AI 23Error Flag 2Error flag word 2Read

Network setup

Watch out for

Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

24 of 24 shown
Type
Access
Show
Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter BACnet Points List
DescriptionStates
AImin1FlowCurrent Flow Rateper meter setupRead
AI2VelocityCurrent Velocity of Fluidm/sRead
AI3POS TotalizerPOS Flow Totalper meter setupRead
AI4NEG TotalizerNEG Flow totalper meter setupRead
AImin5NET TotalizerNet Flow Total of Fluidper meter setupRead
AImin6Energy Flow RateEnergy Flow Rate of Fluidper meter setupRead
AI7+ Energy TotEnergy Positive Totalper meter setupRead
AI8-Energy TotEnergy Negative Totalper meter setupRead
AImin9Net Energy TotEnergy Net Totalper meter setupRead
AI10DtDelta TimensRead
AI11SignalSignal AmplitudedBRead
AImin12QualityQuality of Signal%Read
AI13NoiseNoise Portion in SignaldBRead
AI14GainGain at Amplifier%Read
AI15Fluid TempTemperature of the Fluid°C or °F (per meter setup)Read
AI16Inlet TempInlet Temperature°C or °F (per meter setup)Read
AI17Outlet TempOutlet Temperature°C or °F (per meter setup)Read
AI18Fluid Pressureper meter setupRead
AI19Fluid Densityper meter setupRead
AI20Inlet EnthalpykJ/kgRead
AI21Outlet EnthalpykJ/kgRead
AImin22Error Flag 1Read
AImin23Error Flag 2Read
AV1Reset TotalizersWrite 1-3 to reset, then write 0Write0=Do nothing, 1=Reset flow totalizers, 2=Reset energy totalizers, 3=Reset flow and energy totalizers
Object ID lookup: Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the InnovaSonic 207i Ultrasonic Liquid Flow Meter and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter

How many BACnet points does the Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter have?

This list has 24 BACnet objects: 23 analog inputs, 1 analog value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter BACnet points are writable?

1 of the 24 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter BACnet documentation?

The source is InnovaSonic 207i BACnet Instruction Manual (IM-207i-BACnet), revision V2.3/19, published free by Sierra Instruments at https://sierrainstruments.com/userfiles/file/manuals/207i-bacnet-manual.pdf.

What are the minimum BACnet points to integrate the Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter?

Start with AI 1 Flow (Flow rate); AI 5 NET Totalizer (Net flow total); AI 6 Energy Flow Rate (Thermal energy rate); AI 9 Net Energy Tot (Net energy total); AI 12 Quality (Signal quality, %); AI 22 Error Flag 1 (Error flag word 1); AI 23 Error Flag 2 (Error flag word 2).

How do I check these points on the real InnovaSonic 207i Ultrasonic Liquid Flow Meter?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Sierra Instruments BACnet points lists

Source: InnovaSonic 207i BACnet Instruction Manual · IM-207i-BACnet · rev. V2.3/19. Object names, instances and units are reproduced as published; descriptions are our own.