Vortex flow meter (volumetric and mass) · BACnet points list

Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter BACnet points list

Updated 6 November 2026

Short answer

The InnovaMass 240i (inline) and 241i (insertion) are multivariable vortex meters measuring flow, temperature and pressure for steam, gas and liquids. Over BACnet MS/TP they expose 21 Analog Inputs (flow, temperatures, pressure, energy, totalizer, alarm state and vortex diagnostics), 11 Binary Input fault flags and a Binary Output to reset the totalizer.

This page lists 33 BACnet objects for the Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Sierra Instruments’s own free documentation, linked below.

Manufacturer
Sierra Instruments
Model
InnovaMass 240i/241i Vortex Flow Meter
Equipment
Vortex flow meter (volumetric and mass)
Equipment type
Thermostats, sensors & meters
BACnet objects
33 (1 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
240i, 241i, InnovaMass 240i, InnovaMass 241i, Sierra 240i
Source document
InnovaMass 240i/241i Series BACnet Instruction Manual · IM240i/241i BACnet · rev. V3.4/19
Download CSV 33 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Sierra Instruments’s current documentation and the live device before use. Not official Sierra Instruments information. Terms of use.

BMS integration notes: Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter

Integration in brief

Read flow, temperature, pressure, the totalizer and energy flow, and watch the BI fault flags and alarm AIs. Write the Reset Totalizer BO to clear the total.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1FlowFlow rateRead
AI 6TotalizerFlow totalRead
AI 2Temperature1Process temperatureRead
AI 4PressureProcess pressureRead
AI 5Energy FlowEnergy flowRead
AI 7Alarm StatusAlarm relay stateRead

Network setup

Watch out for

Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

33 of 33 shown
Type
Analog
Access
Show
Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter BACnet Points List
DescriptionStates
AImin1FlowUsed for measurement of FlowcfmRead
AImin2Temperature1Int. Temperature°FRead
AI3Temperature2Ext. Temperature°FRead
AImin4PressureFluid PressurepsiRead
AImin5Energy FlowEnergy Flow in FluidBtuRead
AImin6TotalizerFlow Totalizerft³Read
AImin7Alarm StatusState of Alarm RelayRead
AI8Alarm ActiveSource of AlarmRead
AI9Alarm ModeSelected Alarm ModeRead
AI10VelocityPoint vol. Velocityft/sRead
AI11Flow-ProCorrection FactorRead
AI12DensityDensity for massRead
AI13ReynoldsReynolds numberRead
AI14ViscosityDynamic ViscosityRead
AI15FrequencyVortex shedder frequencyHzRead
AI16Ck factorFor dynamic freq.Read
AI17Dynamic FrequencyDynamic frequency valueHzRead
AI18Minimum noise levelSquelch noise lvlRead
AI19F/S cutoff% of full scaleRead
AI20GainSignal gainRead
AI21AmplitudeIn ADC countsRead
BI1Binary XDR faultRead0=good, 1=fault
BI2Pressure over rangeRead0=good, 1=fault
BI3Temperature faultRead0=good, 1=fault
BI4Temperature over rangeTemperature overrangeRead
BI5Flow sensor errorRead0=good, 1=fault
BI6SD card errorRead0=good, 1=fault
BI7Communication errorRead0=good, 1=fault
BI8MCU errorRead0=good, 1=fault
BI9Display button stuckRead0=good, 1=fault
BI10BACnet communication errorBACnet comm errorRead0=good, 1=fault
BI11Latched on bad signalRead0=good, 1=fault
BO1Reset TotalizerReset totalizerWrite0=run, 1=reset
Object ID lookup: Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the InnovaMass 240i/241i Vortex Flow Meter and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter

How many BACnet points does the Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter have?

This list has 33 BACnet objects: 21 analog inputs, 11 binary inputs, 1 binary output. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter BACnet points are writable?

1 of the 33 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter BACnet documentation?

The source is InnovaMass 240i/241i Series BACnet Instruction Manual (IM240i/241i BACnet), revision V3.4/19, published free by Sierra Instruments at https://sierrainstruments.com/userfiles/file/manuals/240i-241i-bacnet-instruction-manual.pdf?x=5806.

What are the minimum BACnet points to integrate the Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter?

Start with AI 1 Flow (Flow rate); AI 6 Totalizer (Flow total); AI 2 Temperature1 (Process temperature); AI 4 Pressure (Process pressure); AI 5 Energy Flow (Energy flow); AI 7 Alarm Status (Alarm relay state).

How do I check these points on the real InnovaMass 240i/241i Vortex Flow Meter?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Sierra Instruments BACnet points lists

Source: InnovaMass 240i/241i Series BACnet Instruction Manual · IM240i/241i BACnet · rev. V3.4/19. Object names, instances and units are reproduced as published; descriptions are our own.