Vortex flow meter (volumetric and mass) · BACnet points list
Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter BACnet points list
Updated 6 November 2026
The InnovaMass 240i (inline) and 241i (insertion) are multivariable vortex meters measuring flow, temperature and pressure for steam, gas and liquids. Over BACnet MS/TP they expose 21 Analog Inputs (flow, temperatures, pressure, energy, totalizer, alarm state and vortex diagnostics), 11 Binary Input fault flags and a Binary Output to reset the totalizer.
This page lists 33 BACnet objects for the Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Sierra Instruments’s own free documentation, linked below.
- Manufacturer
- Sierra Instruments
- Model
- InnovaMass 240i/241i Vortex Flow Meter
- Equipment
- Vortex flow meter (volumetric and mass)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 33 (1 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- 240i, 241i, InnovaMass 240i, InnovaMass 241i, Sierra 240i
Reference only, provided as-is: verify against Sierra Instruments’s current documentation and the live device before use. Not official Sierra Instruments information. Terms of use.
BMS integration notes: Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter
Read flow, temperature, pressure, the totalizer and energy flow, and watch the BI fault flags and alarm AIs. Write the Reset Totalizer BO to clear the total.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Flow | Flow rate | Read |
| AI 6 | Totalizer | Flow total | Read |
| AI 2 | Temperature1 | Process temperature | Read |
| AI 4 | Pressure | Process pressure | Read |
| AI 5 | Energy Flow | Energy flow | Read |
| AI 7 | Alarm Status | Alarm relay state | Read |
Network setup
- BACnet MS/TP at 9600, 19200 or 38400 baud; baud and MAC address are set with the Smart Interface Portal (SIP) software.
Watch out for
- Units follow the meter configuration; the units in the table are sample defaults.
Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Flow | Used for measurement of Flow | cfm | Read | |
| AImin | 2 | Temperature1 | Int. Temperature | °F | Read | |
| AI | 3 | Temperature2 | Ext. Temperature | °F | Read | |
| AImin | 4 | Pressure | Fluid Pressure | psi | Read | |
| AImin | 5 | Energy Flow | Energy Flow in Fluid | Btu | Read | |
| AImin | 6 | Totalizer | Flow Totalizer | ft³ | Read | |
| AImin | 7 | Alarm Status | State of Alarm Relay | Read | ||
| AI | 8 | Alarm Active | Source of Alarm | Read | ||
| AI | 9 | Alarm Mode | Selected Alarm Mode | Read | ||
| AI | 10 | Velocity | Point vol. Velocity | ft/s | Read | |
| AI | 11 | Flow-Pro | Correction Factor | Read | ||
| AI | 12 | Density | Density for mass | Read | ||
| AI | 13 | Reynolds | Reynolds number | Read | ||
| AI | 14 | Viscosity | Dynamic Viscosity | Read | ||
| AI | 15 | Frequency | Vortex shedder frequency | Hz | Read | |
| AI | 16 | Ck factor | For dynamic freq. | Read | ||
| AI | 17 | Dynamic Frequency | Dynamic frequency value | Hz | Read | |
| AI | 18 | Minimum noise level | Squelch noise lvl | Read | ||
| AI | 19 | F/S cutoff | % of full scale | Read | ||
| AI | 20 | Gain | Signal gain | Read | ||
| AI | 21 | Amplitude | In ADC counts | Read | ||
| BI | 1 | Binary XDR fault | Read | 0=good, 1=fault | ||
| BI | 2 | Pressure over range | Read | 0=good, 1=fault | ||
| BI | 3 | Temperature fault | Read | 0=good, 1=fault | ||
| BI | 4 | Temperature over range | Temperature overrange | Read | ||
| BI | 5 | Flow sensor error | Read | 0=good, 1=fault | ||
| BI | 6 | SD card error | Read | 0=good, 1=fault | ||
| BI | 7 | Communication error | Read | 0=good, 1=fault | ||
| BI | 8 | MCU error | Read | 0=good, 1=fault | ||
| BI | 9 | Display button stuck | Read | 0=good, 1=fault | ||
| BI | 10 | BACnet communication error | BACnet comm error | Read | 0=good, 1=fault | |
| BI | 11 | Latched on bad signal | Read | 0=good, 1=fault | ||
| BO | 1 | Reset Totalizer | Reset totalizer | Write | 0=run, 1=reset |
No points match these filters.
Object ID lookup: Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter point IDs by name
AI1FlowAI2Temperature1AI3Temperature2AI4PressureAI5Energy FlowAI6TotalizerAI7Alarm StatusAI8Alarm ActiveAI9Alarm ModeAI10VelocityAI11Flow-ProAI12DensityAI13ReynoldsAI14ViscosityAI15FrequencyAI16Ck factorAI17Dynamic FrequencyAI18Minimum noise levelAI19F/S cutoffAI20GainAI21AmplitudeBI1Binary XDR faultBI2Pressure over rangeBI3Temperature faultBI4Temperature over rangeBI5Flow sensor errorBI6SD card errorBI7Communication errorBI8MCU errorBI9Display button stuckBI10BACnet communication errorBI11Latched on bad signalBO1Reset Totalizer
Integration notes
- From the BACnet Supported Device, Object and Property tables (manual pages 17-23). Object names are the Object Name property values; units are the sample defaults shown and follow the meter configuration.
- AI-14 Viscosity shows the unit enumeration "423" in the table; it is left blank here.
- No read/write column is printed; only the Reset Totalizer BO is treated as writable.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the InnovaMass 240i/241i Vortex Flow Meter and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter
How many BACnet points does the Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter have?
This list has 33 BACnet objects: 21 analog inputs, 11 binary inputs, 1 binary output. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter BACnet points are writable?
1 of the 33 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter BACnet documentation?
The source is InnovaMass 240i/241i Series BACnet Instruction Manual (IM240i/241i BACnet), revision V3.4/19, published free by Sierra Instruments at https://sierrainstruments.com/userfiles/file/manuals/240i-241i-bacnet-instruction-manual.pdf?x=5806.
What are the minimum BACnet points to integrate the Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter?
Start with AI 1 Flow (Flow rate); AI 6 Totalizer (Flow total); AI 2 Temperature1 (Process temperature); AI 4 Pressure (Process pressure); AI 5 Energy Flow (Energy flow); AI 7 Alarm Status (Alarm relay state).
How do I check these points on the real InnovaMass 240i/241i Vortex Flow Meter?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Sierra Instruments BACnet points lists
- Vortex flow meter (volumetric and mass)
Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1)
Older Sierra InnovaMass 240 inline and 241 insertion vortex flow meters with BACnet MS/TP (manual Rev. V1), before the 240i/241i series.
Also known as: 240, 241, InnovaMass 240, InnovaMass 241 - Ultrasonic liquid flow and energy meter
Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter
Sierra InnovaSonic 207i ultrasonic (transit-time) liquid flow meters with the BACnet MS/TP option module.
Also known as: 207i, InnovaSonic 207i, Sierra 207i
Source: InnovaMass 240i/241i Series BACnet Instruction Manual · IM240i/241i BACnet · rev. V3.4/19. Object names, instances and units are reproduced as published; descriptions are our own.