Vortex flow meter (volumetric and mass) · BACnet points list

Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) BACnet points list

Updated 6 November 2026

Short answer

The legacy InnovaMass 240/241 vortex meters expose a short BACnet MS/TP object list: 19 Analog Inputs (volume and mass flow, two temperatures, pressure, density, energy, two totalizers, status register, analog output channels and vortex diagnostics), four alarm Binary Inputs and a reset Binary Value.

This page lists 24 BACnet objects for the Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Sierra Instruments’s own free documentation, linked below.

Manufacturer
Sierra Instruments
Model
InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1)
Equipment
Vortex flow meter (volumetric and mass)
Equipment type
Thermostats, sensors & meters
BACnet objects
24 (1 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
240, 241, InnovaMass 240, InnovaMass 241
Source document
InnovaMass 240/241 BACnet Instruction Manual · IM240/241 BACnet · rev. Rev. V1
Download CSV 24 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Sierra Instruments’s current documentation and the live device before use. Not official Sierra Instruments information. Terms of use.

BMS integration notes: Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1)

Integration in brief

Read flow, temperature, pressure and the totalizers, and map the alarm BIs (Alarm1-Alarm3).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Volume FlowVolumetric flowRead
AI 2Mass FlowMass flowRead
AI 3Temperature 1Process temperatureRead
AI 5PressureProcess pressureRead
AI 8Totalizer 1Flow totalRead
BI 1Alarm1Alarm 1 stateRead

Watch out for

Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

24 of 24 shown
Type
Analog
Access
Show
Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) BACnet Points List
DescriptionStates
AImin1Volume FlowRead
AImin2Mass FlowRead
AImin3Temperature 1Read
AI4Temperature 2Read
AImin5PressureRead
AI6DensityRead
AI7Energy FlowRead
AImin8Totalizer 1Read
AI9Totalizer 2Read
AI10Status RegisterRead
AI11Channel 1(4-20mA)Read
AI12Channel 2 (4-20mA)Read
AI13Channel 3 (4-20mA)Read
AI14Scaled FreqRead
AI15Flow VelocityRead
AI16ViscosityRead
AI17FrequencyRead
AI18VorTex AmpRead
AI19Filter SettingRead
BImin1Alarm1Read
BI2Alarm2Read
BI3Alarm3Read
BI4ExternalRead
BV1ResetTotalizer resetWrite
Object ID lookup: Sierra Instruments InnovaMass 240/241 Vortex Flow Meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1)

How many BACnet points does the Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) have?

This list has 24 BACnet objects: 19 analog inputs, 4 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) BACnet points are writable?

1 of the 24 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) BACnet documentation?

The source is InnovaMass 240/241 BACnet Instruction Manual (IM240/241 BACnet), revision Rev. V1, published free by Sierra Instruments at https://sierrainstruments.com/userfiles/file/manuals/240-241-BACnet-Instruction-Manual_v1.pdf?x=2029.

What are the minimum BACnet points to integrate the Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1)?

Start with AI 1 Volume Flow (Volumetric flow); AI 2 Mass Flow (Mass flow); AI 3 Temperature 1 (Process temperature); AI 5 Pressure (Process pressure); AI 8 Totalizer 1 (Flow total); BI 1 Alarm1 (Alarm 1 state).

How do I check these points on the real InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Sierra Instruments BACnet points lists

Source: InnovaMass 240/241 BACnet Instruction Manual · IM240/241 BACnet · rev. Rev. V1. Object names, instances and units are reproduced as published; descriptions are our own.