Vortex flow meter (volumetric and mass) · BACnet points list
Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) BACnet points list
Updated 6 November 2026
The legacy InnovaMass 240/241 vortex meters expose a short BACnet MS/TP object list: 19 Analog Inputs (volume and mass flow, two temperatures, pressure, density, energy, two totalizers, status register, analog output channels and vortex diagnostics), four alarm Binary Inputs and a reset Binary Value.
This page lists 24 BACnet objects for the Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) — 1 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Sierra Instruments’s own free documentation, linked below.
- Manufacturer
- Sierra Instruments
- Model
- InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1)
- Equipment
- Vortex flow meter (volumetric and mass)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 24 (1 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Also known as
- 240, 241, InnovaMass 240, InnovaMass 241
Reference only, provided as-is: verify against Sierra Instruments’s current documentation and the live device before use. Not official Sierra Instruments information. Terms of use.
BMS integration notes: Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1)
Read flow, temperature, pressure and the totalizers, and map the alarm BIs (Alarm1-Alarm3).
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Volume Flow | Volumetric flow | Read |
| AI 2 | Mass Flow | Mass flow | Read |
| AI 3 | Temperature 1 | Process temperature | Read |
| AI 5 | Pressure | Process pressure | Read |
| AI 8 | Totalizer 1 | Flow total | Read |
| BI 1 | Alarm1 | Alarm 1 state | Read |
Watch out for
- Units follow the meter configuration.
Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Volume Flow | Read | |||
| AImin | 2 | Mass Flow | Read | |||
| AImin | 3 | Temperature 1 | Read | |||
| AI | 4 | Temperature 2 | Read | |||
| AImin | 5 | Pressure | Read | |||
| AI | 6 | Density | Read | |||
| AI | 7 | Energy Flow | Read | |||
| AImin | 8 | Totalizer 1 | Read | |||
| AI | 9 | Totalizer 2 | Read | |||
| AI | 10 | Status Register | Read | |||
| AI | 11 | Channel 1(4-20mA) | Read | |||
| AI | 12 | Channel 2 (4-20mA) | Read | |||
| AI | 13 | Channel 3 (4-20mA) | Read | |||
| AI | 14 | Scaled Freq | Read | |||
| AI | 15 | Flow Velocity | Read | |||
| AI | 16 | Viscosity | Read | |||
| AI | 17 | Frequency | Read | |||
| AI | 18 | VorTex Amp | Read | |||
| AI | 19 | Filter Setting | Read | |||
| BImin | 1 | Alarm1 | Read | |||
| BI | 2 | Alarm2 | Read | |||
| BI | 3 | Alarm3 | Read | |||
| BI | 4 | External | Read | |||
| BV | 1 | Reset | Totalizer reset | Write |
No points match these filters.
Object ID lookup: Sierra Instruments InnovaMass 240/241 Vortex Flow Meter point IDs by name
AI1Volume FlowAI2Mass FlowAI3Temperature 1AI4Temperature 2AI5PressureAI6DensityAI7Energy FlowAI8Totalizer 1AI9Totalizer 2AI10Status RegisterAI11Channel 1(4-20mA)AI12Channel 2 (4-20mA)AI13Channel 3 (4-20mA)AI14Scaled FreqAI15Flow VelocityAI16ViscosityAI17FrequencyAI18VorTex AmpAI19Filter SettingBI1Alarm1BI2Alarm2BI3Alarm3BI4ExternalBV1Reset
Integration notes
- From the object property summary tables (manual pages 16-17). The unit lists in the Analog Input description table depend on the meter setup and are not repeated here.
- The last AI row is printed as "A19"; it is read as AI 19.
- The guide gives a Device Communication Control password; no read/write column is printed and only BV 1 Reset is treated as writable.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1)
How many BACnet points does the Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) have?
This list has 24 BACnet objects: 19 analog inputs, 4 binary inputs, 1 binary value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) BACnet points are writable?
1 of the 24 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1) BACnet documentation?
The source is InnovaMass 240/241 BACnet Instruction Manual (IM240/241 BACnet), revision Rev. V1, published free by Sierra Instruments at https://sierrainstruments.com/userfiles/file/manuals/240-241-BACnet-Instruction-Manual_v1.pdf?x=2029.
What are the minimum BACnet points to integrate the Sierra Instruments InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1)?
Start with AI 1 Volume Flow (Volumetric flow); AI 2 Mass Flow (Mass flow); AI 3 Temperature 1 (Process temperature); AI 5 Pressure (Process pressure); AI 8 Totalizer 1 (Flow total); BI 1 Alarm1 (Alarm 1 state).
How do I check these points on the real InnovaMass 240/241 Vortex Flow Meter (legacy, BACnet v1)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Sierra Instruments BACnet points lists
- Vortex flow meter (volumetric and mass)
Sierra Instruments InnovaMass 240i/241i Vortex Flow Meter
Sierra InnovaMass 240i inline and 241i insertion vortex flow meters with BACnet MS/TP.
Also known as: 240i, 241i, InnovaMass 240i, InnovaMass 241i, Sierra 240i - Ultrasonic liquid flow and energy meter
Sierra Instruments InnovaSonic 207i Ultrasonic Liquid Flow Meter
Sierra InnovaSonic 207i ultrasonic (transit-time) liquid flow meters with the BACnet MS/TP option module.
Also known as: 207i, InnovaSonic 207i, Sierra 207i
Source: InnovaMass 240/241 BACnet Instruction Manual · IM240/241 BACnet · rev. Rev. V1. Object names, instances and units are reproduced as published; descriptions are our own.