Variable frequency drive (BACnet MS/TP adapter) · BACnet points list

Rockwell Automation (Allen-Bradley) 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400 BACnet points list

Updated 11 November 2026Unofficial source

Short answer

The 22-COMM-B adapter puts a PowerFlex 4-class drive on BACnet MS/TP. It exposes a fixed set of objects: drive I/O terminals (AI, AO, BI, BO), drive status and commands as Binary Values, and references, measurements, fault history and a parameter mailbox as Analog Values. Which objects work depends on the drive (some are PowerFlex 40 / 400 only, noted in the descriptions).

This page lists 43 BACnet objects for the Rockwell Automation (Allen-Bradley) 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400 — 17 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Rockwell Automation (Allen-Bradley)’s documentation hosted by archive.org, not by Rockwell Automation (Allen-Bradley) itself, so treat it as unofficial.

Manufacturer
Rockwell Automation (Allen-Bradley)
Model
22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400
Equipment
Variable frequency drive (BACnet MS/TP adapter)
Equipment type
VFDs & pumps
BACnet objects
43 (17 writable)
Transport
BACnet MS/TP
Firmware
FRN 1.xxx
Default device instance
160000
Also known as
22-COMM-B, PowerFlex 4 BACnet, PowerFlex 40 BACnet, PowerFlex 400 BACnet, 22COMM-UM008
Source document
BACnet MS/TP Adapter 22-COMM-B FRN 1.xxx User Manual · 22COMM-UM008B-EN-P · rev. 2006-10 (unofficial copy, hosted by archive.org)
Download CSV 43 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Rockwell Automation (Allen-Bradley)’s current documentation and the live device before use. Not official Rockwell Automation (Allen-Bradley) information. Terms of use.

BMS integration notes: Rockwell Automation (Allen-Bradley) 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400

Integration in brief

Set the drive's speed reference source to the network (P038 = 5, Comm Port) and its start source as needed, then write a % speed reference to AV 0 and start/stop with BV 10. Read BV 1, AV 2, AV 3 and the fault objects for monitoring; BV 13 clears faults.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10Run/StopRun/stop command (1 = run)Write
AV 0Reference 1 (%)Speed reference, %Write
BV 13Clear FaultsFault reset (write 1)Write
BV 1RunningRunning statusRead
AV 2Output Frequency (Hz)Output frequency, HzRead
AV 3Output Current (Amps)Output current, ARead
BV 3FaultDrive faultRead
AV 12Fault 1Latest fault codeRead

Enable & remote start

Drive parameter P038 [Speed Reference] = 5 (Comm Port) lets the network reference work; BV 10 then starts and stops the drive.

Heartbeat & communication loss

Adapter parameter 03 [Comm Loss Time] (default 10 s) sets how long until a network loss is detected; parameter 02 [Comm Loss Action] decides what happens (default: fault the drive; also stop, zero data, hold last or send fault configuration).

Network setup

Watch out for

Rockwell Automation (Allen-Bradley) 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400 BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

43 of 43 shown
Type
Access
Show
Rockwell Automation (Allen-Bradley) 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400 BACnet Points List
DescriptionStates
AI0Analog Input 1 (%)Drive analog input 1%Read
AI1Analog Input 2 (%)Drive analog input 2%Read
AO0Analog Output 1 (%)Drive analog output 1, needs output set to network (PF 40/400 only)%Write
AO1Analog Output 2 (%)Drive analog output 2, needs output set to network (PF 400 only)%Write
AVmin0Reference 1 (%)Speed reference 1 (drive P038 = Comm Port)%Write
AV1Reference 2 (%)Speed reference 2, selected by BV 12%Write
AVmin2Output Frequency (Hz)Output frequencyHzRead
AVmin3Output Current (Amps)Output currentARead
AV4Output Voltage (VAC)Output voltageVRead
AV5Output Power (kW)Output power (PF 40/400 only)kWRead
AV6Output Energy (kWh)Accumulated energy; write 0 to reset (PF 400 only)kWhWrite
AV7DC Bus Voltage (VDC)DC bus voltageVRead
AV8Drive Temp (°C)Drive temperature°CRead
AV9ReservedReservedRead
AV10ReservedReservedRead
AV11Run Time (Hours)Accumulated run time; writable (0 only) on PF 400hWrite
AVmin12Fault 1Most recent fault codeRead
AV13Fault 2Second most recent fault codeRead
AV14Fault 3Third most recent fault codeRead
AV15Accel Time 1 (Sec)Accel time 1sWrite
AV16Decel Time 1 (Sec)Decel time 1sWrite
AV17Mailbox ParamParameter number for mailbox read/writeWrite
AV18Mailbox ValueValue of the mailbox parameterWrite
BI0Stop InputStop terminal stateRead
BI1Start InputStart terminal stateRead
BI2Dir InputDirection terminal stateRead
BI3Digital Input 1Digital input 1Read
BI4Digital Input 2Digital input 2Read
BI5Digital Input 3Digital input 3 (PF 40/400 only)Read
BI6Digital Input 4Digital input 4 (PF 40/400 only)Read
BO0Digital Output Cmd 1Relay output 1 (relay set to ParamControl)Write
BO1Digital Output Cmd 2Digital output 2 (PF 40/400 only)Write
BO2Digital Output Cmd 3Digital output 3 (PF 40/400 only)Write
BV0ReadyDrive ready to runRead
BVmin1RunningDrive runningRead
BV2Running ReverseRunning in reverseRead
BVmin3FaultDrive faultedRead
BV4AlarmDrive alarm activeRead
BV5At ReferenceAt speed referenceRead
BVmin10Run/StopRun command (1 = run, 0 = stop)Write
BV11Rev/FwdDirection command (1 = reverse)Write
BV12Ref2/Ref1Reference select (1 = Reference 2)Write
BVmin13Clear FaultsWrite 1 to clear the drive faultWrite
Object ID lookup: Rockwell Automation (Allen-Bradley) 22-COMM-B PowerFlex 4/40/400 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400 and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Rockwell Automation (Allen-Bradley) 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400

How many BACnet points does the Rockwell Automation (Allen-Bradley) 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400 have?

This list has 43 BACnet objects: 2 analog inputs, 2 analog outputs, 19 analog values, 7 binary inputs, 3 binary outputs, 10 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Rockwell Automation (Allen-Bradley) 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400 BACnet points are writable?

17 of the 43 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Rockwell Automation (Allen-Bradley) 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400 BACnet documentation?

Rockwell Automation (Allen-Bradley) does not publish it on its own website. This list comes from BACnet MS/TP Adapter 22-COMM-B FRN 1.xxx User Manual (22COMM-UM008B-EN-P), revision 2006-10, a copy hosted by archive.org at https://archive.org/download/manualzilla-id-5728490/5728490.pdf. Ask Rockwell Automation (Allen-Bradley) or its representative for the current revision.

What are the minimum BACnet points to integrate the Rockwell Automation (Allen-Bradley) 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400?

Start with BV 10 Run/Stop (Run/stop command (1 = run)); AV 0 Reference 1 (%) (Speed reference, %); BV 13 Clear Faults (Fault reset (write 1)); BV 1 Running (Running status); AV 2 Output Frequency (Hz) (Output frequency, Hz); AV 3 Output Current (Amps) (Output current, A); BV 3 Fault (Drive fault); AV 12 Fault 1 (Latest fault code).

How do I enable BMS control of the Rockwell Automation (Allen-Bradley) 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400?

Drive parameter P038 [Speed Reference] = 5 (Comm Port) lets the network reference work; BV 10 then starts and stops the drive.

Does the Rockwell Automation (Allen-Bradley) 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400 need a BACnet heartbeat or have a communication timeout?

Adapter parameter 03 [Comm Loss Time] (default 10 s) sets how long until a network loss is detected; parameter 02 [Comm Loss Action] decides what happens (default: fault the drive; also stop, zero data, hold last or send fault configuration).

How do I check these points on the real 22-COMM-B BACnet MS/TP adapter for PowerFlex 4 / 40 / 400?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.