Variable frequency drive (BACnet IP option module) · BACnet points list

Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module BACnet points list

Updated 11 November 2026Unofficial source

Short answer

The 20-750-BNETIP option module serves a fixed object set from a PowerFlex 753 or 755 over BACnet IP: drive status and commands as Binary Values, references, measurements, fault history and eight parameter mailboxes as Analog Values, plus a few I/O terminal objects that exist on the 753 only.

This page lists 55 BACnet objects for the Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Rockwell Automation (Allen-Bradley)’s documentation hosted by archive.org, not by Rockwell Automation (Allen-Bradley) itself, so treat it as unofficial.

Manufacturer
Rockwell Automation (Allen-Bradley)
Model
PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module
Equipment
Variable frequency drive (BACnet IP option module)
Equipment type
VFDs & pumps
BACnet objects
55 (34 writable)
Transport
BACnet IP
Firmware
FRN 1.xxx
Default device instance
100
Also known as
20-750-BNETIP, PowerFlex 753 BACnet, PowerFlex 755 BACnet, 750COM-UM005
Source document
PowerFlex 750-Series BACnet/IP Option Module 20-750-BNETIP User Manual · 750COM-UM005B-EN-P · rev. 2014-06 (unofficial copy, hosted by archive.org)
Download CSV 55 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Rockwell Automation (Allen-Bradley)’s current documentation and the live device before use. Not official Rockwell Automation (Allen-Bradley) information. Terms of use.

BMS integration notes: Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module

Integration in brief

Write a % speed reference to AV 0 (the manual's basic-control steps) and start/stop with BV 10; BV 12 picks reference 2. Read BV 1, AV 2, AV 3, BV 3 and the fault codes for monitoring; BV 13 clears faults.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10Run/StopRun/stop command (1 = run)Write
AV 0Speed Reference ASpeed reference (basic-control reference, %)Write
BV 13Clear FaultsFault reset (write 1)Write
BV 1ActiveRunning statusRead
AV 2Output Frequency (Hz)Output frequency, HzRead
AV 3Output Current (Amps)Output current, ARead
BV 3FaultDrive faultRead
AV 12Fault 1Latest fault codeRead

Enable & remote start

The drive's speed reference and start sources must be assigned to the option module's port; BV 10 then starts and stops the drive.

Heartbeat & communication loss

Device parameter 17 [Comm Loss Time] (default 10 s, 0 disables) sets the network-loss timeout; host parameters 33 [Comm Flt Action] and 34 [Idle Flt Action] set the response (default: fault the drive).

Network setup

Watch out for

Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

55 of 55 shown
Type
Access
Show
Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module BACnet Points List
DescriptionStates
AI0Analog Input 1 (%)Drive analog input 1 (753 only), par 260%Read
AO0Analog Output 1 (%)Drive analog output (753 only), par 276%Write
AVmin0Speed Reference ASpeed reference AWrite
AV1Speed Reference BSpeed reference BWrite
AVmin2Output Frequency (Hz)Output frequency, par 1HzRead
AVmin3Output Current (Amps)Output current, par 7ARead
AV4Output Voltage (VAC)Output voltage, par 8VRead
AV5Output Power (kW)Output power, par 9kWRead
AV6Output Energy (kWh)Accumulated energy; write 0 to reset, par 14kWhWrite
AV7Output Energy 2 (MWh)Accumulated energy in MWh; write 0 to reset, par 13MWhWrite
AV8DC Bus Voltage (VDC)DC bus voltage, par 11VRead
AV9Drive Temp (°C)Drive temperature, par 944°CRead
AV10ReservedReservedRead
AV11Run Time (Hours)Run time; write 0 to reset, par 15hWrite
AVmin12Fault 1Most recent fault codeRead
AV13Fault 2Second most recent fault codeRead
AV14Fault 3Third most recent fault codeRead
AV15Accel Time 1 (Sec)Accel time 1, par 535sWrite
AV16Accel Time 2 (Sec)Accel time 2, par 536sWrite
AV17Decel Time 1 (Sec)Decel time 1, par 537sWrite
AV18Decel Time 2 (Sec)Decel time 2, par 538sWrite
AV19Reference 1 (%)Reference 1, par 545%Write
AV20Reference 2 (%)Reference 2, par 550%Write
AV21Mailbox1 ParamParameter number for mailbox 1Write
AV22Mailbox1 ValueValue of mailbox 1 parameterWrite
AV23Mailbox2 ParamParameter number for mailbox 2Write
AV24Mailbox2 ValueValue of mailbox 2 parameterWrite
AV25Mailbox3 ParamParameter number for mailbox 3Write
AV26Mailbox3 ValueValue of mailbox 3 parameterWrite
AV27Mailbox4 ParamParameter number for mailbox 4Write
AV28Mailbox4 ValueValue of mailbox 4 parameterWrite
AV29Mailbox5 ParamParameter number for mailbox 5Write
AV30Mailbox5 ValueValue of mailbox 5 parameterWrite
AV31Mailbox6 ParamParameter number for mailbox 6Write
AV32Mailbox6 ValueValue of mailbox 6 parameterWrite
AV33Mailbox7 ParamParameter number for mailbox 7Write
AV34Mailbox7 ValueValue of mailbox 7 parameterWrite
AV35Mailbox8 ParamParameter number for mailbox 8Write
AV36Mailbox8 ValueValue of mailbox 8 parameterWrite
BI0Digital Input 0Digital input 0, par 220 bit 0Read
BI1Digital Input 1Digital input 1 (753 only), par 220 bit 1Read
BI2Digital Input 2Digital input 2 (753 only), par 220 bit 2Read
BO0Output Relay 0Output relay 0 (753 only), par 227Write
BV0RUN ReadyDrive ready to runRead
BVmin1ActiveDrive running (active)Read
BV2Forward/ReverseActual directionRead
BVmin3FaultDrive faultedRead
BV4AlarmDrive alarm activeRead
BV5At Setpt SpdAt setpoint speedRead
BV6Manual ActiveManual mode activeRead0=Not active, 1=Manual mode active
BVmin10Run/StopRun command (1 = run, 0 = stop)Write
BV11Rev/FwdDirection command (1 = reverse)Write
BV12Ref2/Ref1Reference select (1 = Reference 2)Write
BVmin13Clear FaultsWrite 1 to clear the drive faultWrite
BV14Auto/ManualAuto/manual commandWrite0=Not manual, 1=Manual
Object ID lookup: Rockwell Automation (Allen-Bradley) PowerFlex 750 20-750-BNETIP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module

How many BACnet points does the Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module have?

This list has 55 BACnet objects: 1 analog input, 1 analog output, 37 analog values, 3 binary inputs, 1 binary output, 12 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module BACnet points are writable?

34 of the 55 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module BACnet documentation?

Rockwell Automation (Allen-Bradley) does not publish it on its own website. This list comes from PowerFlex 750-Series BACnet/IP Option Module 20-750-BNETIP User Manual (750COM-UM005B-EN-P), revision 2014-06, a copy hosted by archive.org at https://archive.org/download/manualzilla-id-5928861/5928861.pdf. Ask Rockwell Automation (Allen-Bradley) or its representative for the current revision.

What are the minimum BACnet points to integrate the Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module?

Start with BV 10 Run/Stop (Run/stop command (1 = run)); AV 0 Speed Reference A (Speed reference (basic-control reference, %)); BV 13 Clear Faults (Fault reset (write 1)); BV 1 Active (Running status); AV 2 Output Frequency (Hz) (Output frequency, Hz); AV 3 Output Current (Amps) (Output current, A); BV 3 Fault (Drive fault); AV 12 Fault 1 (Latest fault code).

How do I enable BMS control of the Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module?

The drive's speed reference and start sources must be assigned to the option module's port; BV 10 then starts and stops the drive.

Does the Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module need a BACnet heartbeat or have a communication timeout?

Device parameter 17 [Comm Loss Time] (default 10 s, 0 disables) sets the network-loss timeout; host parameters 33 [Comm Flt Action] and 34 [Idle Flt Action] set the response (default: fault the drive).

How do I check these points on the real PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Rockwell Automation (Allen-Bradley) BACnet points lists

Source: PowerFlex 750-Series BACnet/IP Option Module 20-750-BNETIP User Manual · 750COM-UM005B-EN-P · rev. 2014-06. Object names, instances and units are reproduced as published; descriptions are our own.