Variable frequency drive (BACnet IP option module) · BACnet points list
Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module BACnet points list
Updated 11 November 2026Unofficial source
The 20-750-BNETIP option module serves a fixed object set from a PowerFlex 753 or 755 over BACnet IP: drive status and commands as Binary Values, references, measurements, fault history and eight parameter mailboxes as Analog Values, plus a few I/O terminal objects that exist on the 753 only.
This page lists 55 BACnet objects for the Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Rockwell Automation (Allen-Bradley)’s documentation hosted by archive.org, not by Rockwell Automation (Allen-Bradley) itself, so treat it as unofficial.
- Manufacturer
- Rockwell Automation (Allen-Bradley)
- Model
- PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module
- Equipment
- Variable frequency drive (BACnet IP option module)
- Equipment type
- VFDs & pumps
- BACnet objects
- 55 (34 writable)
- Transport
- BACnet IP
- Firmware
- FRN 1.xxx
- Default device instance
- 100
- Also known as
- 20-750-BNETIP, PowerFlex 753 BACnet, PowerFlex 755 BACnet, 750COM-UM005
- Source document
- PowerFlex 750-Series BACnet/IP Option Module 20-750-BNETIP User Manual · 750COM-UM005B-EN-P · rev. 2014-06 (unofficial copy, hosted by archive.org)
Reference only, provided as-is: verify against Rockwell Automation (Allen-Bradley)’s current documentation and the live device before use. Not official Rockwell Automation (Allen-Bradley) information. Terms of use.
BMS integration notes: Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module
Write a % speed reference to AV 0 (the manual's basic-control steps) and start/stop with BV 10; BV 12 picks reference 2. Read BV 1, AV 2, AV 3, BV 3 and the fault codes for monitoring; BV 13 clears faults.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 10 | Run/Stop | Run/stop command (1 = run) | Write |
| AV 0 | Speed Reference A | Speed reference (basic-control reference, %) | Write |
| BV 13 | Clear Faults | Fault reset (write 1) | Write |
| BV 1 | Active | Running status | Read |
| AV 2 | Output Frequency (Hz) | Output frequency, Hz | Read |
| AV 3 | Output Current (Amps) | Output current, A | Read |
| BV 3 | Fault | Drive fault | Read |
| AV 12 | Fault 1 | Latest fault code | Read |
Enable & remote start
The drive's speed reference and start sources must be assigned to the option module's port; BV 10 then starts and stops the drive.
Heartbeat & communication loss
Device parameter 17 [Comm Loss Time] (default 10 s, 0 disables) sets the network-loss timeout; host parameters 33 [Comm Flt Action] and 34 [Idle Flt Action] set the response (default: fault the drive).
Network setup
- An IP address jumper picks the address source: on pins 2-3 (default) with parameter 16 [DHCP] disabled it uses 192.168.0.1 / 255.255.255.0; on pins 1-2 it uses DHCP or the address parameters.
- Default device instance 100 (parameter 18 [Device Instnc]); reset the module after changing it.
- BACnet IP UDP port is parameter 19 [Device Port], default 47808.
- Read/WriteProperty(Multiple), Who-Is/I-Am and Who-Has/I-Have are supported.
Watch out for
- Commands written over BACnet are volatile; after a module reset or power cycle the BMS must write them again.
- The manual's basic-control steps use AV 0 'Speed Reference A' as the % reference, while AV 19/20 map to drive parameters 545/550; check which one the drive uses.
- AV 6, AV 7 and AV 11 accept only 0 (reset) when written.
Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 0 | Analog Input 1 (%) | Drive analog input 1 (753 only), par 260 | % | Read | |
| AO | 0 | Analog Output 1 (%) | Drive analog output (753 only), par 276 | % | Write | |
| AVmin | 0 | Speed Reference A | Speed reference A | Write | ||
| AV | 1 | Speed Reference B | Speed reference B | Write | ||
| AVmin | 2 | Output Frequency (Hz) | Output frequency, par 1 | Hz | Read | |
| AVmin | 3 | Output Current (Amps) | Output current, par 7 | A | Read | |
| AV | 4 | Output Voltage (VAC) | Output voltage, par 8 | V | Read | |
| AV | 5 | Output Power (kW) | Output power, par 9 | kW | Read | |
| AV | 6 | Output Energy (kWh) | Accumulated energy; write 0 to reset, par 14 | kWh | Write | |
| AV | 7 | Output Energy 2 (MWh) | Accumulated energy in MWh; write 0 to reset, par 13 | MWh | Write | |
| AV | 8 | DC Bus Voltage (VDC) | DC bus voltage, par 11 | V | Read | |
| AV | 9 | Drive Temp (°C) | Drive temperature, par 944 | °C | Read | |
| AV | 10 | Reserved | Reserved | Read | ||
| AV | 11 | Run Time (Hours) | Run time; write 0 to reset, par 15 | h | Write | |
| AVmin | 12 | Fault 1 | Most recent fault code | Read | ||
| AV | 13 | Fault 2 | Second most recent fault code | Read | ||
| AV | 14 | Fault 3 | Third most recent fault code | Read | ||
| AV | 15 | Accel Time 1 (Sec) | Accel time 1, par 535 | s | Write | |
| AV | 16 | Accel Time 2 (Sec) | Accel time 2, par 536 | s | Write | |
| AV | 17 | Decel Time 1 (Sec) | Decel time 1, par 537 | s | Write | |
| AV | 18 | Decel Time 2 (Sec) | Decel time 2, par 538 | s | Write | |
| AV | 19 | Reference 1 (%) | Reference 1, par 545 | % | Write | |
| AV | 20 | Reference 2 (%) | Reference 2, par 550 | % | Write | |
| AV | 21 | Mailbox1 Param | Parameter number for mailbox 1 | Write | ||
| AV | 22 | Mailbox1 Value | Value of mailbox 1 parameter | Write | ||
| AV | 23 | Mailbox2 Param | Parameter number for mailbox 2 | Write | ||
| AV | 24 | Mailbox2 Value | Value of mailbox 2 parameter | Write | ||
| AV | 25 | Mailbox3 Param | Parameter number for mailbox 3 | Write | ||
| AV | 26 | Mailbox3 Value | Value of mailbox 3 parameter | Write | ||
| AV | 27 | Mailbox4 Param | Parameter number for mailbox 4 | Write | ||
| AV | 28 | Mailbox4 Value | Value of mailbox 4 parameter | Write | ||
| AV | 29 | Mailbox5 Param | Parameter number for mailbox 5 | Write | ||
| AV | 30 | Mailbox5 Value | Value of mailbox 5 parameter | Write | ||
| AV | 31 | Mailbox6 Param | Parameter number for mailbox 6 | Write | ||
| AV | 32 | Mailbox6 Value | Value of mailbox 6 parameter | Write | ||
| AV | 33 | Mailbox7 Param | Parameter number for mailbox 7 | Write | ||
| AV | 34 | Mailbox7 Value | Value of mailbox 7 parameter | Write | ||
| AV | 35 | Mailbox8 Param | Parameter number for mailbox 8 | Write | ||
| AV | 36 | Mailbox8 Value | Value of mailbox 8 parameter | Write | ||
| BI | 0 | Digital Input 0 | Digital input 0, par 220 bit 0 | Read | ||
| BI | 1 | Digital Input 1 | Digital input 1 (753 only), par 220 bit 1 | Read | ||
| BI | 2 | Digital Input 2 | Digital input 2 (753 only), par 220 bit 2 | Read | ||
| BO | 0 | Output Relay 0 | Output relay 0 (753 only), par 227 | Write | ||
| BV | 0 | RUN Ready | Drive ready to run | Read | ||
| BVmin | 1 | Active | Drive running (active) | Read | ||
| BV | 2 | Forward/Reverse | Actual direction | Read | ||
| BVmin | 3 | Fault | Drive faulted | Read | ||
| BV | 4 | Alarm | Drive alarm active | Read | ||
| BV | 5 | At Setpt Spd | At setpoint speed | Read | ||
| BV | 6 | Manual Active | Manual mode active | Read | 0=Not active, 1=Manual mode active | |
| BVmin | 10 | Run/Stop | Run command (1 = run, 0 = stop) | Write | ||
| BV | 11 | Rev/Fwd | Direction command (1 = reverse) | Write | ||
| BV | 12 | Ref2/Ref1 | Reference select (1 = Reference 2) | Write | ||
| BVmin | 13 | Clear Faults | Write 1 to clear the drive fault | Write | ||
| BV | 14 | Auto/Manual | Auto/manual command | Write | 0=Not manual, 1=Manual |
No points match these filters.
Object ID lookup: Rockwell Automation (Allen-Bradley) PowerFlex 750 20-750-BNETIP point IDs by name
AI0Analog Input 1 (%)AO0Analog Output 1 (%)AV0Speed Reference AAV1Speed Reference BAV2Output Frequency (Hz)AV3Output Current (Amps)AV4Output Voltage (VAC)AV5Output Power (kW)AV6Output Energy (kWh)AV7Output Energy 2 (MWh)AV8DC Bus Voltage (VDC)AV9Drive Temp (°C)AV10ReservedAV11Run Time (Hours)AV12Fault 1AV13Fault 2AV14Fault 3AV15Accel Time 1 (Sec)AV16Accel Time 2 (Sec)AV17Decel Time 1 (Sec)AV18Decel Time 2 (Sec)AV19Reference 1 (%)AV20Reference 2 (%)AV21Mailbox1 ParamAV22Mailbox1 ValueAV23Mailbox2 ParamAV24Mailbox2 ValueAV25Mailbox3 ParamAV26Mailbox3 ValueAV27Mailbox4 ParamAV28Mailbox4 ValueAV29Mailbox5 ParamAV30Mailbox5 ValueAV31Mailbox6 ParamAV32Mailbox6 ValueAV33Mailbox7 ParamAV34Mailbox7 ValueAV35Mailbox8 ParamAV36Mailbox8 ValueBI0Digital Input 0BI1Digital Input 1BI2Digital Input 2BO0Output Relay 0BV0RUN ReadyBV1ActiveBV2Forward/ReverseBV3FaultBV4AlarmBV5At Setpt SpdBV6Manual ActiveBV10Run/StopBV11Rev/FwdBV12Ref2/Ref1BV13Clear FaultsBV14Auto/Manual
Integration notes
- Table 3 marks each object for the 753 and 755; 753-only objects are noted in the description. The drive parameter number is given where the table prints one.
- BI 1 is printed as 'B11' in the table; it sits between BI 0 and BI 2.
- AV 10 is reserved.
- Copy hosted on archive.org (manualzilla upload), not on rockwellautomation.com.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module
How many BACnet points does the Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module have?
This list has 55 BACnet objects: 1 analog input, 1 analog output, 37 analog values, 3 binary inputs, 1 binary output, 12 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module BACnet points are writable?
34 of the 55 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module BACnet documentation?
Rockwell Automation (Allen-Bradley) does not publish it on its own website. This list comes from PowerFlex 750-Series BACnet/IP Option Module 20-750-BNETIP User Manual (750COM-UM005B-EN-P), revision 2014-06, a copy hosted by archive.org at https://archive.org/download/manualzilla-id-5928861/5928861.pdf. Ask Rockwell Automation (Allen-Bradley) or its representative for the current revision.
What are the minimum BACnet points to integrate the Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module?
Start with BV 10 Run/Stop (Run/stop command (1 = run)); AV 0 Speed Reference A (Speed reference (basic-control reference, %)); BV 13 Clear Faults (Fault reset (write 1)); BV 1 Active (Running status); AV 2 Output Frequency (Hz) (Output frequency, Hz); AV 3 Output Current (Amps) (Output current, A); BV 3 Fault (Drive fault); AV 12 Fault 1 (Latest fault code).
How do I enable BMS control of the Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module?
The drive's speed reference and start sources must be assigned to the option module's port; BV 10 then starts and stops the drive.
Does the Rockwell Automation (Allen-Bradley) PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module need a BACnet heartbeat or have a communication timeout?
Device parameter 17 [Comm Loss Time] (default 10 s, 0 disables) sets the network-loss timeout; host parameters 33 [Comm Flt Action] and 34 [Idle Flt Action] set the response (default: fault the drive).
How do I check these points on the real PowerFlex 750-Series 20-750-BNETIP BACnet/IP option module?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.