Energy recovery ventilator (ERV) / DOAS controller (Carel c.pCO) · BACnet points list

RenewAire Premium Commercial Controls (ERV & DOAS) BACnet points list

Updated 28 October 2026

Short answer

RenewAire's Premium Commercial Controls run on a Carel c.pCO Mini with a c.pCOe expansion module and talk BACnet IP or BACnet MS/TP once a BACnet license is installed. The fixed object map covers sensors, fan, heating, cooling, economizer, dehumidification and frost-control settings, and about 60 alarm flags. Many points only mean something with the matching options and control types; writes go straight to Present_Value (no priority array).

This page lists 184 BACnet objects for the RenewAire Premium Commercial Controls (ERV & DOAS) — 66 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from RenewAire’s own free documentation, linked below.

Manufacturer
RenewAire
Model
Premium Commercial Controls (ERV & DOAS)
Equipment
Energy recovery ventilator (ERV) / DOAS controller (Carel c.pCO)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
184 (66 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Premium controls v4.xx
Also known as
RenewAire Premium Controls, Premium Commercial Controls, RenewAire DOAS controls, Carel c.pCO Mini, c.pCOe, 147641
Source document
Premium Commercial Controls Installation, Operation and Maintenance Manual (ERV & DOAS) · 147641_010_MAY26 · rev. 2026-05
Download CSV 184 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: RenewAire Premium Commercial Controls (ERV & DOAS)

Integration in brief

Install the BACnet license, pick BACnet IP or MS/TP as the BMS type and cycle power. Turn on BMS control at the keypad, then start and stop the unit with BV 10 and switch it to unoccupied with BV 63. Read BI 21 and MI 7 for status and BI 72 / BI 17 for alarms. Writes land directly on Present_Value with no priority array, and setpoints marked retained should not be written in a loop.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 10OnOffUnitMng.BmsOnOffRun/stop command (1 = on)Write
BV 63BmsUnoccUnoccupied mode command (1 = yes, unit stays on)Write
AV 55Occ_HTG_Setp.ValOccupied heating setpoint, °F (retained)Write
AV 56Occ_CLG_Setp.ValOccupied cooling setpoint, °F (retained)Write
AV 80BMS_SupplyFanCommandSupply fan speed, 0-100 % (BMS direct mode)Write
AV 81BMS_ExhaustFanCommandExhaust fan speed, 0-100 % (BMS direct mode)Write
BV 12AlarmMng.AlrmResByBmsAlarm reset (1 = reset; the unit clears it)Write
BI 21UnitOnUnit running status (1 = on)Read
MI 7UnitStatus_BNOperating state, or why the unit is offRead
BI 72Any_Alarm_Out.ValAny active alarmRead

Enable & remote start

BMS control of on/off is switched on at the keypad (first BMS screen). Once on, the unit will not start until the BMS writes BV 10 = On, so enable it only when the BMS is ready. The unit also needs the start/stop digital input closed, the keypad set On, the scheduler (if used) in an ON period and no serious alarm; any of these can stop it. BI 76 shows whether BMS control is enabled.

Heartbeat & communication loss

No BACnet timeout setting is documented. BI 503 Al_BMS_Offline flags that the BMS is offline and clears itself (auto reset); the manual does not say what the unit does then and documents no keep-alive write.

Sensors & values from the BMS

AV 53 BMS_CO2_Reading takes a CO2 value from the BMS in place of a wired sensor. AV 54 is named BMS_Space_Press_Reading but the table describes it as a coil leaving-air setpoint for dehumidification, so check it on site. The BMS can also force heat or cool: set BV 60 to Allow, then write BV 61 (0 = heat, 1 = cool).

Network setup

Watch out for

RenewAire Premium Commercial Controls (ERV & DOAS) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

184 of 184 shown
Type
Multi-state
Access
Show
RenewAire Premium Commercial Controls (ERV & DOAS) BACnet Points List
DescriptionStates
AI0OA_Temp.ValOA Temperature°FRead
AI1OA_Hum.ValOA Relative Humidity%Read
AI2RA_Temp.ValRA Temperature°FRead
AI3RA_Hum.ValRA Relative Humidity%Read
AI4EA_Temp.ValEA Temperature°FRead
AI5SA_Temp.ValSA Temperature (before tempering)°FRead
AI6OA_Flow_Rate.ValOA Flow RateCFMRead
AI7EA_Flow_Rate.ValEA Flow RateCFMRead
AI8Heating.HTG_SetP_AdjustedActing heating setpoint°FRead
AI9SA_Hum.ValSA Relative Humidity%Read
AI10EA_Hum.ValEA Relative Humidity%Read
AI11RA_DewpointReturn air dewpoint°FRead
AI12OA_DewpointOutdoor air dewpoint°FRead
AI24RA_Flt_Press.ValRA Filter Pressurein. w.c.Read
AI25OA_Flt_Press.ValOA Filter Pressurein. w.c.Read
AI26SF_Command.ValSupply Fan Command (actual)%Read
AI27EF_Command.ValExhaust Fan Command (actual)%Read
AI28CO2_Level.ValCO2 LevelppmRead
AI29VOC_Level.ValVOC LevelppmRead
AI30Exhaust_DuctRoom_Press.ValExhaust Duct Space Pressurein. w.c.Read
AI31Supply_DuctRoom_Press.ValSupply Duct Space Pressurein. w.c.Read
AI32CA_Temp.ValCA Temperature (after tempering)°FRead
AI33Cooling_Command.ValCooling Command%Read
AI34Cooling_LAT.ValCooling coil leaving air temp, used for dehumidification°FRead
AI36CO2_Level_2nd.ValCO2 Level , 2nd sensorppmRead
AI37Preheat_Command.ValPreheater command, 0-100 %%Read
AI38CO2_Level_3rd.ValCO2 Level , 3rd sensorppmRead
AI39CO2_Level_4th.ValCO2 Level , 4th sensorppmRead
AI59Bypass_Command.ValModulating bypass command, 0-100 %%Read
AI62HGRH_Command.ValHot gas reheat valve command; units printed as F°FRead
AV32HGRH_Coil_LAT_Setp.ValHot Gas Reheat Setpoint for conditioned air°FWrite
AV34Heating_Command.ValHeating output command, 0-100 % (0-10 V); needs BV 74%Write
AV35RA_Flt_AlarmHighRA Filter Alarm Level (retained)in. w.c.Write
AV36OA_Flt_AlarmHighOA Filter Alarm Level (retained)in. w.c.Write
AV37SF_ConstSpeedSetP.ValSF Const Speed Setpoint (retained)%Write
AV38SF_FlowControlSetP.ValSF Flow Control Setpoint (retained)CFMWrite
AV39SF_DuctStaticSetP.ValSF Duct Static Pressure Setpoint (retained)in. w.c.Write
AV40SF_RoomStaticSetP.ValSF Room Static Pressure Setpoint (retained)in. w.c.Write
AV41SF_CO2SetP.ValSF CO2 Setpoint (retained)ppmWrite
AV42SF_VOCSetP.ValSF VOC Setpoint (retained)ppmWrite
AV43EF_ConstSpeedSetP.ValEF Constant Speed Setpoint (retained)%Write
AV44EF_FlowControlSetP.ValEF Flow Control Setpoint (retained)CFMWrite
AV45EF_SF_TrackingSetP.ValEF SF Tracking Setpoint (retained)%Write
AV46EF_ReturnStaticSetP.ValEF Return Static Setpoint (retained)in. w.c.Write
AV47CoolLockoutTempOA Cooling Lockout Temperature (retained)°FWrite
AV48HeatLockoutTempOA Heating Lockout Temperature (retained)°FWrite
AV50Econ_Temp_DiffEconomizer Temperature Differential (retained)°FWrite
AV51Economizer.Econ_Low_OA_Temp_LimitEconomizer Low OA Temp Limit (retained)°FWrite
AV52Economizer.Econ_HysteresisEconomizer Hysteresis (retained)Btu/lbWrite
AV53BMS_CO2_ReadingCO2 value written by the BMS instead of a wired sensorppmWrite
AV54BMS_Space_Press_ReadingDoc labels it coil LAT setpoint for dehumidification (retained)°FWrite
AVmin55Occ_HTG_Setp.ValOccupied Heating Setpoint (retained)°FWrite
AVmin56Occ_CLG_Setp.ValOccupied Cooling Setpoint (retained)°FWrite
AV57HGRH_Unit_LAT_Setp.ValReheated supply air setpoint during dehumidification°FWrite
AV58Economizer.Econ_Low_RA_Temp_LimitEconomizer low RA temp limit (retained)°FWrite
AV59SF_CO2FlowMinCO2.ValSF Flow: MinCO2 (retained)ppmWrite
AV60SF_CO2FlowMaxCO2.ValSF Flow: Max CO2 (retained)ppmWrite
AV61SF_CO2FlowMinFlow.ValSF Flow: Min Flow (retained)CFMWrite
AV62SF_CO2FlowMaxFlow.ValSF Flow: Max Flow (retained)CFMWrite
AV64SF_UnoccFlowSetP.ValUnoccupied supply flow setpoint; set high enough for current switchCFMWrite
AV66Unocc_CLG_Setp.ValUnoccupied cooling setpoint°FWrite
AV71Unocc_HTG_Setp.ValUnoccupied heating setpoint°FWrite
AV73Dehumid_Changeover_SetP.ValDewpoint at which dehumidification starts°FWrite
AV77Defrost_OA_SetP.ValFrost control OA Setpoint Low Limit (retained)°FWrite
AV78Defrost_EA_Low_SetP.ValFrost control EA Setpoint Low Limit (retained)°FWrite
AV79Defrost_EA_High_SetP.ValFrost control EA High Limit Setpoint (retained)°FWrite
AVmin80BMS_SupplyFanCommandBMS direct supply fan command, 0-100 %, for cyclic writes%Write
AVmin81BMS_ExhaustFanCommandBMS direct exhaust fan command, 0-100 %, for cyclic writes%Write
AV82EF_Tracking_SFModeExhaust fan speed in EF-only mode when tracking supply fan%Write
AV90SF_ConstSpeedSetP_Boost.valSF Constant Speed Setpoint in Boost Mode%Write
AV91EF_ConstSpeedSetP_Boost.valEF Constant Speed Setpoint in Boost Mode%Write
AV92SF_FlowControlSetP_BoostSF flow control setpoint in boost modeCFMWrite
AV93EF_FlowControlSetP_BoostEF Flow Control Setpoint in Boost ModeCFMWrite
AV94PreheatLowLimitPreheater low limit setpoint for outdoor air (retained)°FWrite
AV500OA_Flt_AlarmHighOA Filter Alarm Levelin. w.c.Write
AV501RA_Flt_AlarmHighRA Filter Alarm Levelin. w.c.Write
AV502CO2_AlarmHighAlarm level for CO2ppmWrite
AV503VOC_AlarmHighAlarm level for VOCppmWrite
AV504SF_FlowControlTolSupply Fan Flow Control Tolerance; over 100 % disables%Write
AV505EF_FlowControlTolExhaust Fan Flow Control Tolerance; over 100 % disables%Write
AV506SF_DuctStaticTolSupply Fan Duct Static Pressure Tolerance; over 100 % disables%Write
AV507SF_RoomStaticTolSupply Fan Room Static Pressure Tolerance; over 100 % disables%Write
AV508EF_RoomStaticTolExhaust Fan Room Static Pressure Tolerance; over 100 % disables%Write
AV509Low_SupAir_Temp_Warn_SetP.ValLow temperature level for Supply Temp Warning°FWrite
AV510Low_SupAir_Temp_Alm_SetP.ValLow supply temp alarm level; alarm shuts unit down°FWrite
AV511High_SupAir_Temp_Warn_SetP.ValHigh temperature level for Supply Temp Warning (retained)°FWrite
AV512High_SupAir_Temp_Alm_SetP.ValHigh supply temp alarm level; alarm shuts unit down (retained)°FWrite
BI8OA_Damp.ValOA Damper CommandRead0=Closed; 1=Open
BI9RA_Damp.ValRA Damper CommandRead0=Closed; 1=Open
BI13Tempering_Mode.ValTempering ModeRead0=Heat; 1=Cool
BI14AlarmMng.AlrmResAlarm Reset StatusRead0=No; 1=Yes
BI15SF_Status.ValSF Status from Current SensorRead0=Off; 1=On
BI16EF_Status.ValEF Status from Current SensorRead0=Off; 1=On
BI17Alarm_Out.ValSerious Alarm (Also a physical output)Read0=OK; 1=Alarm
BI18Heating_Enable_1.ValHeating Stage 1Read0=Off; 1=On
BI19Cooling_Stage_1.ValCooling Stage 1Read0=Off; 1=On
BI20Cooling_Stage_2.ValCooling Stage 2Read0=Off; 1=On
BImin21UnitOnUnit On StatusRead0=Off; 1=On
BI22Al_SupplyFan.ActiveSupply Fan Start AlarmRead0=OK; 1=Alarm
BI23Al_ExhaustFan.ActiveExhaust Fan Start AlarmRead0=OK; 1=Alarm
BI49Bypass_Damper.ValBypass Damper CommandRead0=Close; 1=Open
BI50OfflineAlrm_CPCOE_1.ActiveExpansion Module is offlineRead0=OK; 1=Alarm
BI57Heating_Enable_2.ValHeating Stage 2Read0=Off; 1=On
BI61DehumidMode_OnUnit is in dehumidification modeRead0=Off; 1=On
BI64HGRH_2Pos.ValOutput to two-position HGRH valveRead0=Off; 1=on
BI71UnitOffByDefrostUnit is off by VRF Defrost ModeRead0=No; 1=Yes
BImin72Any_Alarm_Out.ValAny Alarm is True StatusRead0=OK; 1=Alarm
BI73BoostMode.ValBoost Mode valueRead0=Normal; 1=Boost
BI76BMS_EnableBMS control enabled (on/off, unoccupied, single fan)Read0=Off; 1=on
BI500Al_retain.ActiveToo Many Writes to Retained MemoryRead0=OK; 1=Alarm
BI501Al_Err_retain_write.ActiveToo Many Writes to Retained MemoryRead0=OK; 1=Alarm
BI502Al_Device_Test.ActiveUnit Was Left In Device Test ModeRead0=OK; 1=Alarm
BI503Al_BMS_Offline.ActiveBMS Is OfflineRead0=OK; 1=Alarm
BI504OfflineAlrm_CPCOE_1.ActiveOffline Alarm Expansion ModuleRead0=OK; 1=Alarm
BI505CfgErrAlrm_CPCOE_1.ActiveExpansion Module Config ErrorRead0=OK; 1=Alarm
BI508AI_Smoke.ActiveSmoke Alarm Input EngagedRead0=OK; 1=Alarm
BI509AI_Freeze.ActiveFreezestat Alarm Input EngagedRead0=OK; 1=Alarm
BI510Al_SupplyFan.ActiveSupply Fan Start AlarmRead0=OK; 1=Alarm
BI511Al_ExhaustFan.ActiveExhaust Fan Start AlarmRead0=OK; 1=Alarm
BI512Al_SA_Airflow.ActiveSupply Airflow Out of Tolerance AlarmRead0=OK; 1=Alarm
BI513Al_EA_Airflow.ActiveExhaust Airflow Out of Tolerance AlarmRead0=OK; 1=Alarm
BI514Al_SA_PressTol.ActiveSA Static Pressure Level AlarmRead0=OK; 1=Alarm
BI515Al_CO2.ActiveCO2 Level AlarmRead0=OK; 1=Alarm
BI516Al_SupAir_Low_Temp_Warn.ActiveSupply Air Low Temperature WarningRead0=OK; 1=Alarm
BI517Al_SupAir_Low_Temp_Alarm.ActiveSupply Air Low Temperature AlarmRead0=OK; 1=Alarm
BI518Al_SupAir_Hi_Temp_Warn.ActiveSupply Air High Temperature WarningRead0=OK; 1=Alarm
BI519Al_SupAir_Hi_Temp_Alarm.ActiveSupply Air High Temperature AlarmRead0=OK; 1=Alarm
BI520Al_VOC.ActiveVOC level is above limitRead0=OK; 1=Alarm
BI521Al_EA_PressTol.ActiveEA Static Pressure Level AlarmRead0=OK; 1=Alarm
BI522Al_H2OLeak.ActiveWater leak has been detectedRead0=OK; 1=Alarm
BI523Al_SmokePurge.ActiveSmoke purge has been activatedRead0=OK; 1=Alarm
BI524Al_VRV_AlarmVRV System AlarmRead0=OK; 1=Alarm
BI525Al_RefLeakDetectedRefrigerant Leak DetectedRead0=OK; 1=Alarm
BI526Al_RefLeakDetected_ManRefrigerant Leak Detected—Man ResetRead0=OK; 1=Alarm
BI527Al_RefLeakDetected_UntilRefrigerant Leak Detected—Mult OccurRead0=OK; 1=Alarm
BI528Al_SA_Hum_Prb.ActiveSupply Air Humidity Sensor is faultyRead0=OK; 1=Alarm
BI529Al_EA_Hum_Prb.ActiveExhaust Air Humidity Sensor is faultyRead0=OK; 1=Alarm
BI530Al_OA_Temp_Prb.ActiveOA Temperature Sensor Open or ShortRead0=OK; 1=Alarm
BI531Al_OA_Hum_Prb.ActiveOA Relative Humidity Transmitter Out of RangeRead0=OK; 1=Alarm
BI532Al_RA_Temp_Prb.ActiveRA Temperature Sensor Open or ShortRead0=OK; 1=Alarm
BI533Al_RA_Hum_Prb.ActiveRA Relative Humidity Transmitter Out of RangeRead0=OK; 1=Alarm
BI534Al_SA_Temp_Prb.ActiveSA Temperature Sensor Open or ShortRead0=OK; 1=Alarm
BI535Al_EA_Temp_Prb.ActiveEA Temperature Sensor Open or ShortRead0=OK; 1=Alarm
BI536Al_OA_Flt_Press_Prb.ActiveOA Filter Pressure Transmitter Out of RangeRead0=OK; 1=Alarm
BI537Al_RA_Flt_Press_Prb.ActiveRA Filter Pressure Transmitter Out of RangeRead0=OK; 1=Alarm
BI538Al_OA_Flow_Rate_Prb.ActiveOA Flow Rate Pressure Transmitter Out of RangeRead0=OK; 1=Alarm
BI539Al_EA_Flow_Rate_Prb.ActiveEA Flow Rate Pressure Transmitter Out of RangeRead0=OK; 1=Alarm
BI540Al_CO2_Level_Prb.ActiveCO2 Level Transmitter Out of RangeRead0=OK; 1=Alarm
BI541Al_Duct_Press_Prb.ActiveDuct Pressure Transmitter Out of RangeRead0=OK; 1=Alarm
BI542Al_Supply_Temp_Prb.ActiveConditioned Air (CA) Temperature Sensor Open or ShortRead0=OK; 1=Alarm
BI543Al_Coil_LAT_Prb.ActiveCoil leaving Temp Sensor is faultyRead0=OK; 1=Alarm
BI544Al_VOC_Level_Prb.ActiveVOC Probe AlarmRead0=OK; 1=Alarm
BI545Al_Space_Press_Prb.ActiveSpace Pressure Probe AlarmRead0=OK; 1=Alarm
BI546Al_CO2_2_Prb.Active2nd CO2 sensor is faultyRead0=OK; 1=Alarm
BI548Al_CO2_2_Prb.Active3rd CO2 sensor is faultyRead0=OK; 1=Alarm
BI549Al_CO2_3_Prb.Active4th CO2 sensor is faultyRead0=OK; 1=Alarm
BI560Al_RA_Flt_Press.ActiveRA Filter Needs ChangeRead0=OK; 1=Alarm
BI561Al_OA_Flt_Press.ActiveOA Filter Needs ChangeRead0=OK; 1=Alarm
BI562Al_UnitLife.ActiveUnit Service RequestRead0=OK; 1=Alarm
BI564Al_SupplyFanLife.ActiveSupply Fan Service RequestRead0=OK; 1=Alarm
BI565Al_ExhaustFanLife.ActiveExhaust Fan Service RequestRead0=OK; 1=Alarm
BV566Al_CoolStage1LifeCompressor 1 Service Threshold ReachedRead0=OK; 1=Alarm
BV567Al_CoolStage2LifeCompressor 2 Service Threshold ReachedRead0=OK; 1=Alarm
BV568Al_LowSupPressLow pressure limit supply fanRead0=OK; 1=Alarm
BV569Al_HighSupPressHigh pressure limit supply fanRead0=OK; 1=Alarm
BV570Al_LowExhPressLow pressure limit exhaust fanRead0=OK; 1=Alarm
BV571Al_HighExhPressHigh pressure limit exhaust fanRead0=OK; 1=Alarm
BVmin10OnOffUnitMng.BmsOnOffBMS On/Off CommandWrite0=Off; 1=On
BV11OnOffUnitMng.BmsEfOnlyBMS exhaust-fan-only command; table gives no access or rangeRead
BVmin12AlarmMng.AlrmResByBmsAlarm Reset BMS CommandWrite0=OK; 1=Reset
BV13One_Fan_ModeFan that runs in single-fan modeWrite0=Exhaust Fan; 1=Supply Fan
BV60BMS_SetHeatCoolBMS Set Heat/Cool Capability (retained)Write0=No; 1=Allow
BV61BMS_HeatCoolModeBMS Heat/Cool Mode Setting (retained)Write0=Heat; 1=Cool
BVmin63BmsUnoccBMS unoccupied mode command (unit must be on)Write0=No; 1=Yes
BV74BMS_HW_Valve_ControlBMS HW Valve ControlWrite0=No; 1=Allow
BV75Heating_Enable_1.ValHeating Stage 1 BMS EnableWrite0=Off; 1=On
BV524Al_VRV_Alarm.TriggerVRV alarm set to fault from VRV system (retained)Write0=OK; 1=Alarm
MI2SF_ControlType_BNSupply fan control typeRead0=Constant Speed; 1=Supply Airflow; 2=Duct Static; 3=Room Static; 4=CO2; 5=VOC; 6=CO2 Flow
MI3EF_ControlType_BNExhaust fan control typeRead1=Constant Speed; 2=Exhaust Airflow; 3=SF Command Tracking; 4=SF Flow Tracking; 5=Return Static
MI4HTG_ControlType_BNHeating control typeRead
MI5CLG_ControlType_BNCooling control typeRead
MI6Heating_SetPtType_BNHeating setpoint typeRead1=Adjust; 2=OA Reset
MImin7UnitStatus_BNUnit status / reason the unit is offRead1=Unit on; 2=Off by alarm; 3=Off by BMS; 4=Off by scheduler; 5=Off by digital input; 6=Off at keypad; 8=Exhaust fan only; 9=Supply fan only; 11=Cool locked out by BMS; 12=Heat locked out by BMS; 13=Device test (>1 h); 14=Sensor override (>24 h); 15=Off by CO2 level; 16=Frost control on
MI8Cooling_SetPtType_BNCooling setpoint typeRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Premium Commercial Controls (ERV & DOAS) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the RenewAire Premium Commercial Controls (ERV & DOAS)

How many BACnet points does the RenewAire Premium Commercial Controls (ERV & DOAS) have?

This list has 184 BACnet objects: 30 analog inputs, 57 analog values, 74 binary inputs, 16 binary values, 7 multi-state inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which RenewAire Premium Commercial Controls (ERV & DOAS) BACnet points are writable?

66 of the 184 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official RenewAire Premium Commercial Controls (ERV & DOAS) BACnet documentation?

The source is Premium Commercial Controls Installation, Operation and Maintenance Manual (ERV & DOAS) (147641_010_MAY26), revision 2026-05, published free by RenewAire at https://renewaire.com/wp-content/uploads/2025/05/Premium-Controls-Supplement_147641_010_MAY26.pdf.

What are the minimum BACnet points to integrate the RenewAire Premium Commercial Controls (ERV & DOAS)?

Start with BV 10 OnOffUnitMng.BmsOnOff (Run/stop command (1 = on)); BV 63 BmsUnocc (Unoccupied mode command (1 = yes, unit stays on)); AV 55 Occ_HTG_Setp.Val (Occupied heating setpoint, °F (retained)); AV 56 Occ_CLG_Setp.Val (Occupied cooling setpoint, °F (retained)); AV 80 BMS_SupplyFanCommand (Supply fan speed, 0-100 % (BMS direct mode)); AV 81 BMS_ExhaustFanCommand (Exhaust fan speed, 0-100 % (BMS direct mode)); BV 12 AlarmMng.AlrmResByBms (Alarm reset (1 = reset; the unit clears it)); BI 21 UnitOn (Unit running status (1 = on)); MI 7 UnitStatus_BN (Operating state, or why the unit is off); BI 72 Any_Alarm_Out.Val (Any active alarm).

How do I enable BMS control of the RenewAire Premium Commercial Controls (ERV & DOAS)?

BMS control of on/off is switched on at the keypad (first BMS screen). Once on, the unit will not start until the BMS writes BV 10 = On, so enable it only when the BMS is ready. The unit also needs the start/stop digital input closed, the keypad set On, the scheduler (if used) in an ON period and no serious alarm; any of these can stop it. BI 76 shows whether BMS control is enabled.

Does the RenewAire Premium Commercial Controls (ERV & DOAS) need a BACnet heartbeat or have a communication timeout?

No BACnet timeout setting is documented. BI 503 Al_BMS_Offline flags that the BMS is offline and clears itself (auto reset); the manual does not say what the unit does then and documents no keep-alive write.

Can the BMS supply sensor values to the RenewAire Premium Commercial Controls (ERV & DOAS)?

AV 53 BMS_CO2_Reading takes a CO2 value from the BMS in place of a wired sensor. AV 54 is named BMS_Space_Press_Reading but the table describes it as a coil leaving-air setpoint for dehumidification, so check it on site. The BMS can also force heat or cool: set BV 60 to Allow, then write BV 61 (0 = heat, 1 = cool).

How do I check these points on the real Premium Commercial Controls (ERV & DOAS)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More RenewAire BACnet points lists

Source: Premium Commercial Controls Installation, Operation and Maintenance Manual (ERV & DOAS) · 147641_010_MAY26 · rev. 2026-05. Object names, instances and units are reproduced as published; descriptions are our own.