Energy recovery ventilator (ERV) BACnet fan control · BACnet points list

RenewAire BACnet Fan Control BACNETFC-W BACnet points list

Updated 28 October 2026

Short answer

The BACNETFC-W is a wall-mounted controller accessory that lets a BMS turn a RenewAire ERV on and off over BACnet MS/TP, alongside its keypad and a remote interlock input. On HE and LE units it also sets supply and exhaust fan speeds independently as 0-10 V signals; on EV Premium(+) and SL units it only switches the fan enable. The object list is small and fixed: 16 objects.

This page lists 16 BACnet objects for the RenewAire BACnet Fan Control BACNETFC-W — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from RenewAire’s own free documentation, linked below.

Manufacturer
RenewAire
Model
BACnet Fan Control BACNETFC-W
Equipment
Energy recovery ventilator (ERV) BACnet fan control
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
16 (5 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
BACNETFC-W, BACNETFC, RenewAire BACnet Fan Control, RenewAire BACnet fan controller
Source document
BACnet Fan Control Supplemental Installation & Operation Manual BACNETFC-W - Residential and Commercial Units · 105802_003_FEB26 · rev. 2026-02
Download CSV 16 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: RenewAire BACnet Fan Control BACNETFC-W

Integration in brief

Set BMS Enable to ON in the controller's program menu (or write BV 1), then start and stop the ERV with BV 2. On HE and LE units write the supply and exhaust fan setpoints (AV 1, AV 2) as 0-10 V. Read BV 4 for unit status; there is no alarm object.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2BMS On/OffRun/stop command (1 = on)Write
BV 1Enable BMSMust be On for BMS on/off controlWrite
AV 1Supply Fan SetpointSupply fan speed signal, 0-10 V (HE/LE units)Write
AV 2Exhaust Fan SetpointExhaust fan speed signal, 0-10 V (HE/LE units)Write
BV 4Unit StatusUnit on/off statusRead
BI 1InterlockInterlock input, 1 = closedRead

Enable & remote start

BMS Enable (BV 1, also in the keypad's program menu) must be ON for the BMS to switch the unit with BV 2. The manual says that with it on, all conditions must be met for the unit to start; the main screen shows separate run indicators for the user setting (BV 3), the BMS and the interlock (BI 1).

Heartbeat & communication loss

AV 3 Network Activity Timeout (1-120 s, default 60 s) is set at the keypad in program mode. The supplement does not say what the controller does when it expires.

Network setup

Watch out for

RenewAire BACnet Fan Control BACNETFC-W BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

16 of 16 shown
Type
Access
Show
RenewAire BACnet Fan Control BACNETFC-W BACnet Points List
DescriptionStates
AO1Supply Fan CommandSupply fan 0-10 V output, read onlyVRead
AO2Exhaust Fan CommandExhaust fan 0-10 V output, read onlyVRead
AVmin1Supply Fan SetpointSupply fan output setpoint, 0-10 V, default 5.0 VVWrite
AVmin2Exhaust Fan SetpointExhaust fan output setpoint, 0-10 V, default 5.0 VVWrite
AV3Network Activity TimeoutNetwork activity timeout, 1-120 s, default 60 s; keypad settingsRead
AV7Active Display Back-lightActive display backlight, default 50 %; keypad setting%Read
AV8Inactive Display Back-lightInactive display backlight, default 50 %; keypad setting%Read
BImin1InterlockRemote on/off (interlock) inputRead0=Open; 1=Closed
BO1Supply Fan EnableSupply fan enable output, read onlyRead0=Off; 1=On
BO2Exhaust Fan EnableExhaust fan enable output, read onlyRead0=Off; 1=On
BO3Supply DamperSupply damper output, read onlyRead0=Off; 1=On
BO4Exhaust DamperExhaust damper output, read onlyRead0=Off; 1=On
BVmin1Enable BMSEnables control from the BMSWrite0=Off; 1=On
BVmin2BMS On/OffBMS on/off commandWrite0=Off; 1=On
BV3User On/OffUser on/off; also set at the keypadWrite0=Off; 1=On
BVmin4Unit StatusUnit operating statusRead0=Off; 1=On

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the BACnet Fan Control BACNETFC-W and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the RenewAire BACnet Fan Control BACNETFC-W

How many BACnet points does the RenewAire BACnet Fan Control BACNETFC-W have?

This list has 16 BACnet objects: 2 analog outputs, 5 analog values, 1 binary input, 4 binary outputs, 4 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which RenewAire BACnet Fan Control BACNETFC-W BACnet points are writable?

5 of the 16 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official RenewAire BACnet Fan Control BACNETFC-W BACnet documentation?

The source is BACnet Fan Control Supplemental Installation & Operation Manual BACNETFC-W - Residential and Commercial Units (105802_003_FEB26), revision 2026-02, published free by RenewAire at https://renewaire.com/wp-content/uploads/2025/06/BACnet_Fan_Control_Supplement_105802_003_FEB26.pdf.

What are the minimum BACnet points to integrate the RenewAire BACnet Fan Control BACNETFC-W?

Start with BV 2 BMS On/Off (Run/stop command (1 = on)); BV 1 Enable BMS (Must be On for BMS on/off control); AV 1 Supply Fan Setpoint (Supply fan speed signal, 0-10 V (HE/LE units)); AV 2 Exhaust Fan Setpoint (Exhaust fan speed signal, 0-10 V (HE/LE units)); BV 4 Unit Status (Unit on/off status); BI 1 Interlock (Interlock input, 1 = closed).

How do I enable BMS control of the RenewAire BACnet Fan Control BACNETFC-W?

BMS Enable (BV 1, also in the keypad's program menu) must be ON for the BMS to switch the unit with BV 2. The manual says that with it on, all conditions must be met for the unit to start; the main screen shows separate run indicators for the user setting (BV 3), the BMS and the interlock (BI 1).

Does the RenewAire BACnet Fan Control BACNETFC-W need a BACnet heartbeat or have a communication timeout?

AV 3 Network Activity Timeout (1-120 s, default 60 s) is set at the keypad in program mode. The supplement does not say what the controller does when it expires.

How do I check these points on the real BACnet Fan Control BACNETFC-W?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.