Variable frequency drive (HVAC fan and pump) · BACnet points list

LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP BACnet points list

Updated 6 November 2026

Short answer

The H100+ has BACnet MS/TP on its integrated RS-485 port (COM-02 Int485 Proto = 4 BACnet). The fixed object list has writable AVs for frequency reference, ramps, PID reference/feedback, command timeout and three analog outputs, BVs for run/stop, reset and relay outputs, AIs for drive monitors and trip/warning words, and BIs for drive state and terminal I/O. Several objects (AV 9, AI 28, BI 31-35) belong to the extension I/O.

This page lists 85 BACnet objects for the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from LS Electric’s own free documentation, linked below.

Manufacturer
LS Electric
Model
H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP
Equipment
Variable frequency drive (HVAC fan and pump)
Equipment type
VFDs & pumps
BACnet objects
85 (21 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
237000
Also known as
H100+, H100 Plus, H100Plus, LSLV-H100+, LSLV-H100 Plus, LS H100+ BACnet
Source document
LSLV-H100+ Series User Manual, 7.4 BACnet Communication · H100+ Programming Manual v8 (2nd edition) · rev. 2026-07
Download CSV 85 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against LS Electric’s current documentation and the live device before use. Not official LS Electric information. Terms of use.

BMS integration notes: LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP

Integration in brief

Set COM-02 Int485 Proto = 4 (BACnet), the MAC address in COM-01, baud in COM-03 and the device instance in COM-84/COM-85. Set DRV-06 Cmd Source = Int 485 and DRV-07 Freq Ref Src = Int 485, then write BV 2 to run, BV 1 to stop and AV 4 for speed. Read BI 2, AI 5, AI 4 and BI 4.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2RunForwardCmdRun forward command (True = run)Write
BV 1StopCmdStop command (True = stop)Write
AV 4CommandFreqSetFrequency reference, HzWrite
BV 4ResetFaultCmdReset a tripped driveWrite
BI 2RunningForwardRunning forward statusRead
AI 5OutputFreqOutput frequency, HzRead
AI 4OutputCurrentMotor ampsRead
AI 8OutputPowerOutput power, kWRead
BI 4TrippedAny active tripRead
BI 30WarningAny active warningRead

Enable & remote start

DRV-06 Cmd Source must be 3 (Int 485) for the run/stop BVs and DRV-07 Freq Ref Src 6 (Int 485) for AV 4. The drive has Hand-Off-Auto keys; AV 2-4 can be written in AUTO mode only.

Heartbeat & communication loss

AV 1 CommTimeoutSet (0.1-120 s) and MV 1 LostCommand (0 None, 1 Coast Stop, 2 Decel Stop, 3 Hold Input, 4 Hold Output, 5 Lost Preset) set the lost-command time and action. The manual's speed-command-loss parameters (Lost Cmd Mode / Lost Cmd Time in the PRT group, default 1.0 s) also apply to integrated RS-485.

Sensors & values from the BMS

AV 6 PIDFeedbackSet lets the BMS write the PID feedback and AV 5 PIDReferenceSet the PID setpoint.

Network setup

Watch out for

LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

85 of 85 shown
Type
Access
Show
LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP BACnet Points List
DescriptionStates
AV1CommTimeoutSetCommand timeout setting, 0.1-120.0sWrite
AV2AccelTimeSetAcceleration time setting, 0.0-600.0sWrite
AV3DecelTimeSetDeceleration time setting, 0.0-600.0sWrite
AVmin4CommandFreqSetFrequency reference, 0.00 to DRV-20 max frequencyHzWrite
AV5PIDReferenceSetPID reference (setpoint), 0-100.0%Write
AV6PIDFeedbackSetPID feedback from the network, 0-100.0%Write
AV7CommAo1Comm. analog output 1 level, 0-100.0%Write
AV8CommAo2Comm. analog output 2 level, 0-100.0%Write
AV9CommAo2Comm. analog output 3 level (extension I/O), 0-100.0%Write
MV1LostCommandAction on lost commandWrite0=None, 1=Coast Stop, 2=Decel Stop, 3=HoldInput, 4=HoldOutput, 5=LostPreset
BVmin1StopCmdStop commandWriteFalse/True
BVmin2RunForwardCmdRun forward commandWriteFalse/True
BV3RunReverseCmdRun reverse commandWriteFalse/True
BVmin4ResetFaultCmdFault reset commandWriteFalse/True
BV5FreeRunStopCmdFree-run (coast) stop commandWriteFalse/True
BV6Relay1CmdRelay 1 on/off commandWriteFalse/True
BV7Relay2CmdRelay 2 on/off commandWriteFalse/True
BV8Relay3CmdRelay 3 on/off commandWriteFalse/True
BV9Relay4CmdRelay 4 on/off commandWriteFalse/True
BV10Relay5CmdRelay 5 on/off commandWriteFalse/True
BV11Q1CmdQ1 output on/off commandWriteFalse/True
AI1InvCap (kW)Inverter capacitykWRead
AI2InvCap (HP)Inverter capacityhpRead
AI3InvVoltageClassInverter voltage classVRead
AImin4OutputCurrentOutput currentARead
AImin5OutputFreqOutput frequencyHzRead
AI6OutputVolgateOutput voltageVRead
AI7DCLinkVoltageDC link voltageVRead
AImin8OutputPowerOutput powerkWRead
AI9AI1Analog input 1 value%Read
AI10AI2Analog input 2 value%Read
AI11OutputRPMOutput speedrpmRead
AI12PoleMotor pole numberRead
AI13InvStatusInverter state word (common area 0h0305)Read
AI14LatchTripInfo1Latch-type trip flags 1 (0h0330)Read
AI15LatchTripInfo2Latch-type trip flags 2 (0h0331)Read
AI16LatchTripInfo3Latch-type trip flags 3 (0h0335)Read
AI17LevelTripInfoLevel-type trip flags (0h0332)Read
AI18HWDIagInfoH/W diagnosis trip flags (0h0333)Read
AI19WarningInfoWarning flags (0h0334)Read
AI20KiloWattHourEnergy, kWh partkWhRead
AI21MegaWattHourEnergy, MWh partMWhRead
AI22PowerFactorPower factorRead
AI23RunTimeDayRun time, daysDayRead
AI24RunTimeMinRun time, minutesDayRead
AI25PidOutValuePID output value%Read
AI26PidReferenceValuePID setpoint value%Read
AI27PidFeedbackValuePID feedback value%Read
AI28AI3Analog input 3 value%Read
BI1StoppedStoppedRead
BImin2RunningForwardRunning forwardRead
BI3RunningReverseRunning reverseRead
BImin4TrippedTrip activeRead
BI5AcceleratingAcceleratingRead
BI6DeceleratingDeceleratingRead
BI7SteadySpeedAt steady speedRead
BI8RunningDCOperating at 0 step speedRead
BI9StoppingStoppingRead
BI10FwdRunCommandStateForward run command stateRead
BI11RevRunCommandStateReverse run command stateRead
BI12P1Input P1 stateRead
BI13P2Input P2 stateRead
BI14P3Input P3 stateRead
BI15P4Input P4 stateRead
BI16P5Input P5 stateRead
BI17P6Input P6 stateRead
BI18P7Input P7 stateRead
BI19Relay1Relay 1 stateRead
BI20Relay2Relay 2 stateRead
BI21Relay3Relay 3 stateRead
BI22Relay4Relay 4 stateRead
BI23Relay5Relay 5 stateRead
BI24Q1Q1 output stateRead
BI25SpeedSearchSpeed search activeRead
BI26HWOCSH/W overcurrent (OCS) occurredRead
BI27SWOCSS/W overcurrent (OCS) occurredRead
BI28RunningDwellDwell operation activeRead
BI29SteadyStateSteady stateRead
BImin30WarningWarning activeRead
BI31P8Input P8 state (extension I/O)Read
BI32P9Input P9 state (extension I/O)Read
BI33Relay6Relay 6 state (extension I/O)Read
BI34Relay7Relay 7 state (extension I/O)Read
BI35Relay8Relay 8 state (extension I/O)Read
MI1UnitsDisplaySpeed display unit settingRead1=Hz, 2=RPM
Object ID lookup: LS Electric H100+ HVAC drive, embedded BACnet MS/TP point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP

How many BACnet points does the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP have?

This list has 85 BACnet objects: 28 analog inputs, 9 analog values, 35 binary inputs, 11 binary values, 1 multi-state input, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP BACnet points are writable?

21 of the 85 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP BACnet documentation?

The source is LSLV-H100+ Series User Manual, 7.4 BACnet Communication (H100+ Programming Manual v8 (2nd edition)), revision 2026-07, published free by LS Electric at https://www.lselectricamerica.com/api/v1/fo/ctpApi/fileDownUrl?filePath=CTP%2FManual%2F1684678068%2FH100%2B%20Programming%20Manual_v8_260730.pdf.

What are the minimum BACnet points to integrate the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP?

Start with BV 2 RunForwardCmd (Run forward command (True = run)); BV 1 StopCmd (Stop command (True = stop)); AV 4 CommandFreqSet (Frequency reference, Hz); BV 4 ResetFaultCmd (Reset a tripped drive); BI 2 RunningForward (Running forward status); AI 5 OutputFreq (Output frequency, Hz); AI 4 OutputCurrent (Motor amps); AI 8 OutputPower (Output power, kW); BI 4 Tripped (Any active trip); BI 30 Warning (Any active warning).

How do I enable BMS control of the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP?

DRV-06 Cmd Source must be 3 (Int 485) for the run/stop BVs and DRV-07 Freq Ref Src 6 (Int 485) for AV 4. The drive has Hand-Off-Auto keys; AV 2-4 can be written in AUTO mode only.

Does the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP need a BACnet heartbeat or have a communication timeout?

AV 1 CommTimeoutSet (0.1-120 s) and MV 1 LostCommand (0 None, 1 Coast Stop, 2 Decel Stop, 3 Hold Input, 4 Hold Output, 5 Lost Preset) set the lost-command time and action. The manual's speed-command-loss parameters (Lost Cmd Mode / Lost Cmd Time in the PRT group, default 1.0 s) also apply to integrated RS-485.

Can the BMS supply sensor values to the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP?

AV 6 PIDFeedbackSet lets the BMS write the PID feedback and AV 5 PIDReferenceSet the PID setpoint.

How do I check these points on the real H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More LS Electric BACnet points lists

Source: LSLV-H100+ Series User Manual, 7.4 BACnet Communication · H100+ Programming Manual v8 (2nd edition) · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.