- H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP
Variable frequency drive (HVAC fan and pump) · BACnet points list
LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP BACnet points list
Updated 6 November 2026
The H100+ has BACnet MS/TP on its integrated RS-485 port (COM-02 Int485 Proto = 4 BACnet). The fixed object list has writable AVs for frequency reference, ramps, PID reference/feedback, command timeout and three analog outputs, BVs for run/stop, reset and relay outputs, AIs for drive monitors and trip/warning words, and BIs for drive state and terminal I/O. Several objects (AV 9, AI 28, BI 31-35) belong to the extension I/O.
This page lists 85 BACnet objects for the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from LS Electric’s own free documentation, linked below.
- Manufacturer
- LS Electric
- Model
- H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP
- Equipment
- Variable frequency drive (HVAC fan and pump)
- Equipment type
- VFDs & pumps
- BACnet objects
- 85 (21 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 237000
- Also known as
- H100+, H100 Plus, H100Plus, LSLV-H100+, LSLV-H100 Plus, LS H100+ BACnet
Reference only, provided as-is: verify against LS Electric’s current documentation and the live device before use. Not official LS Electric information. Terms of use.
BMS integration notes: LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP
Set COM-02 Int485 Proto = 4 (BACnet), the MAC address in COM-01, baud in COM-03 and the device instance in COM-84/COM-85. Set DRV-06 Cmd Source = Int 485 and DRV-07 Freq Ref Src = Int 485, then write BV 2 to run, BV 1 to stop and AV 4 for speed. Read BI 2, AI 5, AI 4 and BI 4.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2 | RunForwardCmd | Run forward command (True = run) | Write |
| BV 1 | StopCmd | Stop command (True = stop) | Write |
| AV 4 | CommandFreqSet | Frequency reference, Hz | Write |
| BV 4 | ResetFaultCmd | Reset a tripped drive | Write |
| BI 2 | RunningForward | Running forward status | Read |
| AI 5 | OutputFreq | Output frequency, Hz | Read |
| AI 4 | OutputCurrent | Motor amps | Read |
| AI 8 | OutputPower | Output power, kW | Read |
| BI 4 | Tripped | Any active trip | Read |
| BI 30 | Warning | Any active warning | Read |
Enable & remote start
DRV-06 Cmd Source must be 3 (Int 485) for the run/stop BVs and DRV-07 Freq Ref Src 6 (Int 485) for AV 4. The drive has Hand-Off-Auto keys; AV 2-4 can be written in AUTO mode only.
Heartbeat & communication loss
AV 1 CommTimeoutSet (0.1-120 s) and MV 1 LostCommand (0 None, 1 Coast Stop, 2 Decel Stop, 3 Hold Input, 4 Hold Output, 5 Lost Preset) set the lost-command time and action. The manual's speed-command-loss parameters (Lost Cmd Mode / Lost Cmd Time in the PRT group, default 1.0 s) also apply to integrated RS-485.
Sensors & values from the BMS
AV 6 PIDFeedbackSet lets the BMS write the PID feedback and AV 5 PIDReferenceSet the PID setpoint.
Network setup
- COM-02 Int485 Proto = 4 (BACnet). COM-01 Int485 St ID is the MAC address, 0-127.
- COM-03 baud: 9600 (default), 19200, 38400 or 76800 bps for BACnet. COM-04 sets parity (D8/PN/S1 default, even or odd).
- COM-83 BAC Max Master, 1-127, default 127.
- Device instance = COM-84 x 1000 + COM-85 (defaults 237 and 0, so 237000).
- COM-86 BAC PassWord (default 0 = ignored) protects ReinitializeDevice warm/cold start.
- With COM-96 PowerOn Resume = Yes, written AV values survive a power cycle.
Watch out for
- BV 1 StopCmd, BV 2 RunForwardCmd and BV 3 RunReverseCmd are separate commands; write the stop BV to stop.
- ReadPropertyMultiple is not in the listed services; poll with ReadProperty.
LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | CommTimeoutSet | Command timeout setting, 0.1-120.0 | s | Write | |
| AV | 2 | AccelTimeSet | Acceleration time setting, 0.0-600.0 | s | Write | |
| AV | 3 | DecelTimeSet | Deceleration time setting, 0.0-600.0 | s | Write | |
| AVmin | 4 | CommandFreqSet | Frequency reference, 0.00 to DRV-20 max frequency | Hz | Write | |
| AV | 5 | PIDReferenceSet | PID reference (setpoint), 0-100.0 | % | Write | |
| AV | 6 | PIDFeedbackSet | PID feedback from the network, 0-100.0 | % | Write | |
| AV | 7 | CommAo1 | Comm. analog output 1 level, 0-100.0 | % | Write | |
| AV | 8 | CommAo2 | Comm. analog output 2 level, 0-100.0 | % | Write | |
| AV | 9 | CommAo2 | Comm. analog output 3 level (extension I/O), 0-100.0 | % | Write | |
| MV | 1 | LostCommand | Action on lost command | Write | 0=None, 1=Coast Stop, 2=Decel Stop, 3=HoldInput, 4=HoldOutput, 5=LostPreset | |
| BVmin | 1 | StopCmd | Stop command | Write | False/True | |
| BVmin | 2 | RunForwardCmd | Run forward command | Write | False/True | |
| BV | 3 | RunReverseCmd | Run reverse command | Write | False/True | |
| BVmin | 4 | ResetFaultCmd | Fault reset command | Write | False/True | |
| BV | 5 | FreeRunStopCmd | Free-run (coast) stop command | Write | False/True | |
| BV | 6 | Relay1Cmd | Relay 1 on/off command | Write | False/True | |
| BV | 7 | Relay2Cmd | Relay 2 on/off command | Write | False/True | |
| BV | 8 | Relay3Cmd | Relay 3 on/off command | Write | False/True | |
| BV | 9 | Relay4Cmd | Relay 4 on/off command | Write | False/True | |
| BV | 10 | Relay5Cmd | Relay 5 on/off command | Write | False/True | |
| BV | 11 | Q1Cmd | Q1 output on/off command | Write | False/True | |
| AI | 1 | InvCap (kW) | Inverter capacity | kW | Read | |
| AI | 2 | InvCap (HP) | Inverter capacity | hp | Read | |
| AI | 3 | InvVoltageClass | Inverter voltage class | V | Read | |
| AImin | 4 | OutputCurrent | Output current | A | Read | |
| AImin | 5 | OutputFreq | Output frequency | Hz | Read | |
| AI | 6 | OutputVolgate | Output voltage | V | Read | |
| AI | 7 | DCLinkVoltage | DC link voltage | V | Read | |
| AImin | 8 | OutputPower | Output power | kW | Read | |
| AI | 9 | AI1 | Analog input 1 value | % | Read | |
| AI | 10 | AI2 | Analog input 2 value | % | Read | |
| AI | 11 | OutputRPM | Output speed | rpm | Read | |
| AI | 12 | Pole | Motor pole number | Read | ||
| AI | 13 | InvStatus | Inverter state word (common area 0h0305) | Read | ||
| AI | 14 | LatchTripInfo1 | Latch-type trip flags 1 (0h0330) | Read | ||
| AI | 15 | LatchTripInfo2 | Latch-type trip flags 2 (0h0331) | Read | ||
| AI | 16 | LatchTripInfo3 | Latch-type trip flags 3 (0h0335) | Read | ||
| AI | 17 | LevelTripInfo | Level-type trip flags (0h0332) | Read | ||
| AI | 18 | HWDIagInfo | H/W diagnosis trip flags (0h0333) | Read | ||
| AI | 19 | WarningInfo | Warning flags (0h0334) | Read | ||
| AI | 20 | KiloWattHour | Energy, kWh part | kWh | Read | |
| AI | 21 | MegaWattHour | Energy, MWh part | MWh | Read | |
| AI | 22 | PowerFactor | Power factor | Read | ||
| AI | 23 | RunTimeDay | Run time, days | Day | Read | |
| AI | 24 | RunTimeMin | Run time, minutes | Day | Read | |
| AI | 25 | PidOutValue | PID output value | % | Read | |
| AI | 26 | PidReferenceValue | PID setpoint value | % | Read | |
| AI | 27 | PidFeedbackValue | PID feedback value | % | Read | |
| AI | 28 | AI3 | Analog input 3 value | % | Read | |
| BI | 1 | Stopped | Stopped | Read | ||
| BImin | 2 | RunningForward | Running forward | Read | ||
| BI | 3 | RunningReverse | Running reverse | Read | ||
| BImin | 4 | Tripped | Trip active | Read | ||
| BI | 5 | Accelerating | Accelerating | Read | ||
| BI | 6 | Decelerating | Decelerating | Read | ||
| BI | 7 | SteadySpeed | At steady speed | Read | ||
| BI | 8 | RunningDC | Operating at 0 step speed | Read | ||
| BI | 9 | Stopping | Stopping | Read | ||
| BI | 10 | FwdRunCommandState | Forward run command state | Read | ||
| BI | 11 | RevRunCommandState | Reverse run command state | Read | ||
| BI | 12 | P1 | Input P1 state | Read | ||
| BI | 13 | P2 | Input P2 state | Read | ||
| BI | 14 | P3 | Input P3 state | Read | ||
| BI | 15 | P4 | Input P4 state | Read | ||
| BI | 16 | P5 | Input P5 state | Read | ||
| BI | 17 | P6 | Input P6 state | Read | ||
| BI | 18 | P7 | Input P7 state | Read | ||
| BI | 19 | Relay1 | Relay 1 state | Read | ||
| BI | 20 | Relay2 | Relay 2 state | Read | ||
| BI | 21 | Relay3 | Relay 3 state | Read | ||
| BI | 22 | Relay4 | Relay 4 state | Read | ||
| BI | 23 | Relay5 | Relay 5 state | Read | ||
| BI | 24 | Q1 | Q1 output state | Read | ||
| BI | 25 | SpeedSearch | Speed search active | Read | ||
| BI | 26 | HWOCS | H/W overcurrent (OCS) occurred | Read | ||
| BI | 27 | SWOCS | S/W overcurrent (OCS) occurred | Read | ||
| BI | 28 | RunningDwell | Dwell operation active | Read | ||
| BI | 29 | SteadyState | Steady state | Read | ||
| BImin | 30 | Warning | Warning active | Read | ||
| BI | 31 | P8 | Input P8 state (extension I/O) | Read | ||
| BI | 32 | P9 | Input P9 state (extension I/O) | Read | ||
| BI | 33 | Relay6 | Relay 6 state (extension I/O) | Read | ||
| BI | 34 | Relay7 | Relay 7 state (extension I/O) | Read | ||
| BI | 35 | Relay8 | Relay 8 state (extension I/O) | Read | ||
| MI | 1 | UnitsDisplay | Speed display unit setting | Read | 1=Hz, 2=RPM |
No points match these filters.
Object ID lookup: LS Electric H100+ HVAC drive, embedded BACnet MS/TP point IDs by name
AV1CommTimeoutSetAV2AccelTimeSetAV3DecelTimeSetAV4CommandFreqSetAV5PIDReferenceSetAV6PIDFeedbackSetAV7CommAo1AV8CommAo2AV9CommAo2MV1LostCommandBV1StopCmdBV2RunForwardCmdBV3RunReverseCmdBV4ResetFaultCmdBV5FreeRunStopCmdBV6Relay1CmdBV7Relay2CmdBV8Relay3CmdBV9Relay4CmdBV10Relay5CmdBV11Q1CmdAI1InvCap (kW)AI2InvCap (HP)AI3InvVoltageClassAI4OutputCurrentAI5OutputFreqAI6OutputVolgateAI7DCLinkVoltageAI8OutputPowerAI9AI1AI10AI2AI11OutputRPMAI12PoleAI13InvStatusAI14LatchTripInfo1AI15LatchTripInfo2AI16LatchTripInfo3AI17LevelTripInfoAI18HWDIagInfoAI19WarningInfoAI20KiloWattHourAI21MegaWattHourAI22PowerFactorAI23RunTimeDayAI24RunTimeMinAI25PidOutValueAI26PidReferenceValueAI27PidFeedbackValueAI28AI3BI1StoppedBI2RunningForwardBI3RunningReverseBI4TrippedBI5AcceleratingBI6DeceleratingBI7SteadySpeedBI8RunningDCBI9StoppingBI10FwdRunCommandStateBI11RevRunCommandStateBI12P1BI13P2BI14P3BI15P4BI16P5BI17P6BI18P7BI19Relay1BI20Relay2BI21Relay3BI22Relay4BI23Relay5BI24Q1BI25SpeedSearchBI26HWOCSBI27SWOCSBI28RunningDwellBI29SteadyStateBI30WarningBI31P8BI32P9BI33Relay6BI34Relay7BI35Relay8MI1UnitsDisplay
Integration notes
- From the LSLV-H100+ User Manual (2nd edition, July 2026), section 7.4.5 Object Map (PDF pp359-363). Only the BACnet objects are listed; the Metasys N2 map that follows is left out.
- AV 8 and AV 9 are both printed with the object name CommAo2; AV 9 is the analog output 3 (extension I/O) setting.
- AV 2, AV 3 and AV 4 can be written in AUTO mode only. AV 4 cannot exceed DRV-20 Max Freq and is used when DRV-07 Freq Ref Src = Int 485.
- To drive the analog outputs from AV 7-9, set OUT-01 AO1 Mode, OUT-07 AO2 Mode and APO-30 AO3 Mode to 16-18 (Comm Output 1-3).
- To drive relays from BV 6-11, set the relay function (OUT-31 to OUT-39) to 0 (None).
- AI 24 RunTimeMin is printed with units Day; the doc's description says run time by minute. The printed MSI is listed as MI; MSV as MV.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP
How many BACnet points does the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP have?
This list has 85 BACnet objects: 28 analog inputs, 9 analog values, 35 binary inputs, 11 binary values, 1 multi-state input, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP BACnet points are writable?
21 of the 85 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP BACnet documentation?
The source is LSLV-H100+ Series User Manual, 7.4 BACnet Communication (H100+ Programming Manual v8 (2nd edition)), revision 2026-07, published free by LS Electric at https://www.lselectricamerica.com/api/v1/fo/ctpApi/fileDownUrl?filePath=CTP%2FManual%2F1684678068%2FH100%2B%20Programming%20Manual_v8_260730.pdf.
What are the minimum BACnet points to integrate the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP?
Start with BV 2 RunForwardCmd (Run forward command (True = run)); BV 1 StopCmd (Stop command (True = stop)); AV 4 CommandFreqSet (Frequency reference, Hz); BV 4 ResetFaultCmd (Reset a tripped drive); BI 2 RunningForward (Running forward status); AI 5 OutputFreq (Output frequency, Hz); AI 4 OutputCurrent (Motor amps); AI 8 OutputPower (Output power, kW); BI 4 Tripped (Any active trip); BI 30 Warning (Any active warning).
How do I enable BMS control of the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP?
DRV-06 Cmd Source must be 3 (Int 485) for the run/stop BVs and DRV-07 Freq Ref Src 6 (Int 485) for AV 4. The drive has Hand-Off-Auto keys; AV 2-4 can be written in AUTO mode only.
Does the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP need a BACnet heartbeat or have a communication timeout?
AV 1 CommTimeoutSet (0.1-120 s) and MV 1 LostCommand (0 None, 1 Coast Stop, 2 Decel Stop, 3 Hold Input, 4 Hold Output, 5 Lost Preset) set the lost-command time and action. The manual's speed-command-loss parameters (Lost Cmd Mode / Lost Cmd Time in the PRT group, default 1.0 s) also apply to integrated RS-485.
Can the BMS supply sensor values to the LS Electric H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP?
AV 6 PIDFeedbackSet lets the BMS write the PID feedback and AV 5 PIDReferenceSet the PID setpoint.
How do I check these points on the real H100+ (H100 Plus) HVAC drive, embedded BACnet MS/TP?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More LS Electric BACnet points lists
Source: LSLV-H100+ Series User Manual, 7.4 BACnet Communication · H100+ Programming Manual v8 (2nd edition) · rev. 2026-07. Object names, instances and units are reproduced as published; descriptions are our own.