Variable frequency drive (BACnet IP option module) · BACnet points list
LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) BACnet points list
Updated 6 November 2026
The CBAC-H100 Ethernet module adds BACnet IP, EtherNet/IP or Modbus TCP to the H100; COM-21 = 0 selects BACnet IP (default). The object list matches the H100+ embedded MS/TP map without the extension I/O objects: AVs for frequency reference, ramps, PID reference/feedback and command timeout, BVs for run/stop/reset and relays, AIs for monitors and trip words, BIs for drive state and terminals.
This page lists 76 BACnet objects for the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from LS Electric’s own free documentation, linked below.
- Manufacturer
- LS Electric
- Model
- H100 drive with CBAC-H100 Ethernet module (BACnet IP)
- Equipment
- Variable frequency drive (BACnet IP option module)
- Equipment type
- VFDs & pumps
- BACnet objects
- 76 (18 writable)
- Transport
- BACnet IP
- Firmware
- Needs H100 inverter OS 1.22 or later
- Default device instance
- 237000
- Also known as
- H100, LSLV-H100, CBAC-H100, H100 BACnet IP, H100 Ethernet option, LS H100 BACnet/IP
Reference only, provided as-is: verify against LS Electric’s current documentation and the live device before use. Not official LS Electric information. Terms of use.
BMS integration notes: LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP)
Install the CBAC-H100 module, set COM-21 = 0 (BACnet IP), the IP address, subnet and gateway in COM-12 to COM-20 and the device instance in COM-84/COM-85, then set COM-94 = Yes to apply. Set DRV-06 Cmd Source and DRV-07 Freq Ref Src to Field Bus, write BV 2 to run, BV 1 to stop and AV 4 for speed, and read BI 2, AI 5, AI 4 and BI 4.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 2 | RunForwardCmd | Run forward command (True = run) | Write |
| BV 1 | StopCmd | Stop command (True = stop) | Write |
| AV 4 | CommandFreqSet | Frequency reference, Hz | Write |
| BV 4 | ResetFaultCmd | Reset a tripped drive | Write |
| BI 2 | RunningForward | Running forward status | Read |
| AI 5 | OutputFreq | Output frequency, Hz | Read |
| AI 4 | OutputCurrent | Motor amps | Read |
| AI 8 | OutputPower | Output power, kW | Read |
| BI 4 | Tripped | Any active trip | Read |
| BI 30 | Warning | Any active warning | Read |
Enable & remote start
DRV-06 Cmd Source = 4 (Field Bus) for run/stop and DRV-07 Freq Ref Src = 7 (Field Bus) for AV 4. AV 2-4 can be written in AUTO mode only.
Heartbeat & communication loss
PRT-12 Lost Cmd Mode (default None: keep the last state; Free-Run, Dec, Hold Input, Hold Output, Lost Preset) and PRT-13 Lost Cmd Time (0.1-120 s, default 1.0 s) set the action when the network command is lost; PRT-14 is the Lost Preset speed. AV 1 CommTimeoutSet and MV 1 LostCommand have the same range and options.
Sensors & values from the BMS
AV 6 PIDFeedbackSet lets the BMS write the PID feedback and AV 5 PIDReferenceSet the PID setpoint.
Network setup
- COM-21 Opt Parameter-12 = 0 selects BACnet IP (default); 1 EtherNet/IP, 2 Modbus TCP.
- COM-10 selects DHCP (1) or static (0); COM-12 to COM-15 IP address, COM-16 subnet as CIDR bits (default 24), COM-17 to COM-20 gateway.
- With BACnet IP selected, COM-22 sets the UDP port (default 0xBAC0 = 47808) and COM-23 the Out of Service mode.
- Device instance = COM-84 x 1000 + COM-85 (defaults 237 and 0, so 237000). COM-86 password (default 0) protects warm/cold start and the web server.
- Set COM-94 Comm Update = 1 (Yes) after changing COM-07 or COM-10 to COM-23; the drive restarts when the IP or option type changes.
- CNF-30 shows the installed module as BACnet IP (or Reserved-18/19 on older inverter software).
Watch out for
- BV 1 StopCmd, BV 2 RunForwardCmd and BV 3 RunReverseCmd are separate commands; write the stop BV to stop.
- Lost Cmd Mode defaults to None, so the drive keeps its last command when the BMS goes quiet.
- ReadPropertyMultiple is not in the listed services; poll with ReadProperty.
- The module's web server is monitoring only; it cannot run the drive.
LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | CommTimeoutSet | Command timeout setting, 0.1-120.0 | s | Write | |
| AV | 2 | AccelTimeSet | Acceleration time setting, 0.0-600.0 | s | Write | |
| AV | 3 | DecelTimeSet | Deceleration time setting, 0.0-600.0 | s | Write | |
| AVmin | 4 | CommandFreqSet | Frequency reference, 0.00 to DRV-20 max frequency | Hz | Write | |
| AV | 5 | PIDReferenceSet | PID reference (setpoint), 0-100.0 | % | Write | |
| AV | 6 | PIDFeedbackSet | PID feedback from the network, 0-100.0 | % | Write | |
| MV | 1 | LostCommand | Action on lost command | Write | 0=None, 1=FreeRun, 2=Dec, 3=HoldInput, 4=HoldOutput, 5=LostPreset | |
| BVmin | 1 | StopCmd | Stop command | Write | False(0)/True(1) | |
| BVmin | 2 | RunForwardCmd | Run forward command | Write | False(0)/True(1) | |
| BV | 3 | RunReverseCmd | Run reverse command | Write | False(0)/True(1) | |
| BVmin | 4 | ResetFaultCmd | Fault reset command | Write | False(0)/True(1) | |
| BV | 5 | FreeRunStopCmd | Free-run (coast) stop command | Write | False(0)/True(1) | |
| BV | 6 | Relay1Cmd | Relay 1 on/off command | Write | False(0)/True(1) | |
| BV | 7 | Relay2Cmd | Relay 2 on/off command | Write | False(0)/True(1) | |
| BV | 8 | Relay3Cmd | Relay 3 on/off command | Write | False(0)/True(1) | |
| BV | 9 | Relay4Cmd | Relay 4 on/off command | Write | False(0)/True(1) | |
| BV | 10 | Relay5Cmd | Relay 5 on/off command | Write | False(0)/True(1) | |
| BV | 11 | Q1Cmd | Q1 output on/off command | Write | False(0)/True(1) | |
| AI | 1 | InvCap (kW) | Inverter capacity | kW | Read | |
| AI | 2 | InvCap(HP) | Inverter capacity | hp | Read | |
| AI | 3 | InvVoltageClass | Inverter voltage class | V | Read | |
| AImin | 4 | OutputCurrent | Output current | A | Read | |
| AImin | 5 | OutputFreq | Output frequency | Hz | Read | |
| AI | 6 | OutputVolgate | Output voltage | V | Read | |
| AI | 7 | DCLinkVoltage | DC link voltage | V | Read | |
| AImin | 8 | OutputPower | Output power | kW | Read | |
| AI | 9 | AI1 | Analog input 1 value | % | Read | |
| AI | 10 | AI2 | Analog input 2 value | % | Read | |
| AI | 11 | OutputRPM | Output speed | rpm | Read | |
| AI | 12 | Pole | Motor pole number | Read | ||
| AI | 13 | InvStatus | Inverter state word (common area 0h0305) | Read | ||
| AI | 14 | LatchTripInfo1 | Latch-type trip flags 1 (0h0330) | Read | ||
| AI | 15 | LatchTripInfo2 | Latch-type trip flags 2 (0h0331) | Read | ||
| AI | 16 | LatchTripInfo3 | Latch-type trip flags 3 (0h0335) | Read | ||
| AI | 17 | LevelTripInfo | Level-type trip flags (0h0332) | Read | ||
| AI | 18 | HWDIagInfo | H/W diagnosis trip flags (0h0333) | Read | ||
| AI | 19 | WarningInfo | Warning flags (0h0334) | Read | ||
| AI | 20 | KiloWattHour | Energy, kWh part | kWh | Read | |
| AI | 21 | MegaWattHour | Energy, MWh part | MWh | Read | |
| AI | 22 | PowerFactor | Power factor | Read | ||
| AI | 23 | RunTimeDay | Run time, days | Day | Read | |
| AI | 24 | RunTimeMin | Run time, minutes | Day | Read | |
| AI | 25 | PidOutValue | PID output value | % | Read | |
| AI | 26 | PidReferenceValue | PID setpoint value | % | Read | |
| AI | 27 | PidFeedbackValue | PID feedback value | % | Read | |
| BI | 1 | Stopped | Stopped | Read | ||
| BImin | 2 | RunningForward | Running forward | Read | ||
| BI | 3 | RunningReverse | Running reverse | Read | ||
| BImin | 4 | Tripped | Trip active | Read | ||
| BI | 5 | Accelerating | Accelerating | Read | ||
| BI | 6 | Decelerating | Decelerating | Read | ||
| BI | 7 | SteadySpeed | At steady speed | Read | ||
| BI | 8 | RunningDC | Operating at 0 step speed | Read | ||
| BI | 9 | Stopping | Stopping | Read | ||
| BI | 10 | FwdRunCommandState | Forward run command state | Read | ||
| BI | 11 | RevRunCommandState | Reverse run command state | Read | ||
| BI | 12 | P1 | Input P1 state | Read | ||
| BI | 13 | P2 | Input P2 state | Read | ||
| BI | 14 | P3 | Input P3 state | Read | ||
| BI | 15 | P4 | Input P4 state | Read | ||
| BI | 16 | P5 | Input P5 state | Read | ||
| BI | 17 | P6 | Input P6 state | Read | ||
| BI | 18 | P7 | Input P7 state | Read | ||
| BI | 19 | Relay1 | Relay 1 state | Read | ||
| BI | 20 | Relay2 | Relay 2 state | Read | ||
| BI | 21 | Relay3 | Relay 3 state | Read | ||
| BI | 22 | Relay4 | Relay 4 state | Read | ||
| BI | 23 | Relay5 | Relay 5 state | Read | ||
| BI | 24 | Q1 | Q1 output state | Read | ||
| BI | 25 | SpeedSearch | Speed search active | Read | ||
| BI | 26 | HWOCS | H/W overcurrent (OCS) occurred | Read | ||
| BI | 27 | SWOCS | S/W overcurrent (OCS) occurred | Read | ||
| BI | 28 | RunningDwell | Dwell operation active | Read | ||
| BI | 29 | SteadyState | Steady state | Read | ||
| BImin | 30 | Warning | Warning active | Read | ||
| MI | 1 | UnitsDisplay | Speed display unit setting | Read | 1=Hz, 2=RPM |
No points match these filters.
Object ID lookup: LS Electric H100 drive with CBAC-H100 Ethernet module point IDs by name
AV1CommTimeoutSetAV2AccelTimeSetAV3DecelTimeSetAV4CommandFreqSetAV5PIDReferenceSetAV6PIDFeedbackSetMV1LostCommandBV1StopCmdBV2RunForwardCmdBV3RunReverseCmdBV4ResetFaultCmdBV5FreeRunStopCmdBV6Relay1CmdBV7Relay2CmdBV8Relay3CmdBV9Relay4CmdBV10Relay5CmdBV11Q1CmdAI1InvCap (kW)AI2InvCap(HP)AI3InvVoltageClassAI4OutputCurrentAI5OutputFreqAI6OutputVolgateAI7DCLinkVoltageAI8OutputPowerAI9AI1AI10AI2AI11OutputRPMAI12PoleAI13InvStatusAI14LatchTripInfo1AI15LatchTripInfo2AI16LatchTripInfo3AI17LevelTripInfoAI18HWDIagInfoAI19WarningInfoAI20KiloWattHourAI21MegaWattHourAI22PowerFactorAI23RunTimeDayAI24RunTimeMinAI25PidOutValueAI26PidReferenceValueAI27PidFeedbackValueBI1StoppedBI2RunningForwardBI3RunningReverseBI4TrippedBI5AcceleratingBI6DeceleratingBI7SteadySpeedBI8RunningDCBI9StoppingBI10FwdRunCommandStateBI11RevRunCommandStateBI12P1BI13P2BI14P3BI15P4BI16P5BI17P6BI18P7BI19Relay1BI20Relay2BI21Relay3BI22Relay4BI23Relay5BI24Q1BI25SpeedSearchBI26HWOCSBI27SWOCSBI28RunningDwellBI29SteadyStateBI30WarningMI1UnitsDisplay
Integration notes
- From the H100 BACnet IP (Ethernet) User Manual EN V1.2, section 11.2.5 (PDF pp33-39).
- Compared with the H100+ embedded MS/TP map, this list has no AV 7-9 (comm analog outputs), AI 28 or BI 31-35 (extension I/O).
- AV 2, AV 3 and AV 4 can be written in AUTO mode only; AV 4 cannot exceed DRV-20 Max Freq.
- To drive relays from BV 6-10, set OUT-31 to OUT-35 to 0 (None).
- For priority control, the manual says to write clear (255) to give the priority back.
- AI 24 RunTimeMin is printed with units Day though it is run time in minutes. The printed MSI is listed as MI; MSV as MV.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the H100 drive with CBAC-H100 Ethernet module (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP)
How many BACnet points does the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) have?
This list has 76 BACnet objects: 27 analog inputs, 6 analog values, 30 binary inputs, 11 binary values, 1 multi-state input, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) BACnet points are writable?
18 of the 76 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) BACnet documentation?
The source is H100 BACnet IP (Ethernet) Communication Module User Manual (V1.2), revision 2026-09-30, published free by LS Electric at https://www.lselectricamerica.com/api/v1/fo/ctpApi/fileDownUrl?filePath=CTP%2FManual%2F790179813%2FH100%20BACNET%20IP(Ethernet)_User%20Manual_EN_V1.2_260930.pdf.
What are the minimum BACnet points to integrate the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP)?
Start with BV 2 RunForwardCmd (Run forward command (True = run)); BV 1 StopCmd (Stop command (True = stop)); AV 4 CommandFreqSet (Frequency reference, Hz); BV 4 ResetFaultCmd (Reset a tripped drive); BI 2 RunningForward (Running forward status); AI 5 OutputFreq (Output frequency, Hz); AI 4 OutputCurrent (Motor amps); AI 8 OutputPower (Output power, kW); BI 4 Tripped (Any active trip); BI 30 Warning (Any active warning).
How do I enable BMS control of the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP)?
DRV-06 Cmd Source = 4 (Field Bus) for run/stop and DRV-07 Freq Ref Src = 7 (Field Bus) for AV 4. AV 2-4 can be written in AUTO mode only.
Does the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) need a BACnet heartbeat or have a communication timeout?
PRT-12 Lost Cmd Mode (default None: keep the last state; Free-Run, Dec, Hold Input, Hold Output, Lost Preset) and PRT-13 Lost Cmd Time (0.1-120 s, default 1.0 s) set the action when the network command is lost; PRT-14 is the Lost Preset speed. AV 1 CommTimeoutSet and MV 1 LostCommand have the same range and options.
Can the BMS supply sensor values to the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP)?
AV 6 PIDFeedbackSet lets the BMS write the PID feedback and AV 5 PIDReferenceSet the PID setpoint.
How do I check these points on the real H100 drive with CBAC-H100 Ethernet module (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More LS Electric BACnet points lists
Source: H100 BACnet IP (Ethernet) Communication Module User Manual · V1.2 · rev. 2026-09-30. Object names, instances and units are reproduced as published; descriptions are our own.