Easy BACnet
  1. Home
  2. BACnet points lists
  3. LS Electric
  4. H100 drive with CBAC-H100 Ethernet module (BACnet IP)

Variable frequency drive (BACnet IP option module) · BACnet points list

LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) BACnet points list

Updated 6 November 2026

Short answer

The CBAC-H100 Ethernet module adds BACnet IP, EtherNet/IP or Modbus TCP to the H100; COM-21 = 0 selects BACnet IP (default). The object list matches the H100+ embedded MS/TP map without the extension I/O objects: AVs for frequency reference, ramps, PID reference/feedback and command timeout, BVs for run/stop/reset and relays, AIs for monitors and trip words, BIs for drive state and terminals.

This page lists 76 BACnet objects for the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) — 18 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from LS Electric’s own free documentation, linked below.

Manufacturer
LS Electric
Model
H100 drive with CBAC-H100 Ethernet module (BACnet IP)
Equipment
Variable frequency drive (BACnet IP option module)
Equipment type
VFDs & pumps
BACnet objects
76 (18 writable)
Transport
BACnet IP
Firmware
Needs H100 inverter OS 1.22 or later
Default device instance
237000
Also known as
H100, LSLV-H100, CBAC-H100, H100 BACnet IP, H100 Ethernet option, LS H100 BACnet/IP
Source document
H100 BACnet IP (Ethernet) Communication Module User Manual · V1.2 · rev. 2026-09-30
Download CSV 76 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against LS Electric’s current documentation and the live device before use. Not official LS Electric information. Terms of use.

BMS integration notes: LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP)

Integration in brief

Install the CBAC-H100 module, set COM-21 = 0 (BACnet IP), the IP address, subnet and gateway in COM-12 to COM-20 and the device instance in COM-84/COM-85, then set COM-94 = Yes to apply. Set DRV-06 Cmd Source and DRV-07 Freq Ref Src to Field Bus, write BV 2 to run, BV 1 to stop and AV 4 for speed, and read BI 2, AI 5, AI 4 and BI 4.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 2RunForwardCmdRun forward command (True = run)Write
BV 1StopCmdStop command (True = stop)Write
AV 4CommandFreqSetFrequency reference, HzWrite
BV 4ResetFaultCmdReset a tripped driveWrite
BI 2RunningForwardRunning forward statusRead
AI 5OutputFreqOutput frequency, HzRead
AI 4OutputCurrentMotor ampsRead
AI 8OutputPowerOutput power, kWRead
BI 4TrippedAny active tripRead
BI 30WarningAny active warningRead

Enable & remote start

DRV-06 Cmd Source = 4 (Field Bus) for run/stop and DRV-07 Freq Ref Src = 7 (Field Bus) for AV 4. AV 2-4 can be written in AUTO mode only.

Heartbeat & communication loss

PRT-12 Lost Cmd Mode (default None: keep the last state; Free-Run, Dec, Hold Input, Hold Output, Lost Preset) and PRT-13 Lost Cmd Time (0.1-120 s, default 1.0 s) set the action when the network command is lost; PRT-14 is the Lost Preset speed. AV 1 CommTimeoutSet and MV 1 LostCommand have the same range and options.

Sensors & values from the BMS

AV 6 PIDFeedbackSet lets the BMS write the PID feedback and AV 5 PIDReferenceSet the PID setpoint.

Network setup

Watch out for

LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

76 of 76 shown
Type
Access
Show
LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) BACnet Points List
DescriptionStates
AV1CommTimeoutSetCommand timeout setting, 0.1-120.0sWrite
AV2AccelTimeSetAcceleration time setting, 0.0-600.0sWrite
AV3DecelTimeSetDeceleration time setting, 0.0-600.0sWrite
AVmin4CommandFreqSetFrequency reference, 0.00 to DRV-20 max frequencyHzWrite
AV5PIDReferenceSetPID reference (setpoint), 0-100.0%Write
AV6PIDFeedbackSetPID feedback from the network, 0-100.0%Write
MV1LostCommandAction on lost commandWrite0=None, 1=FreeRun, 2=Dec, 3=HoldInput, 4=HoldOutput, 5=LostPreset
BVmin1StopCmdStop commandWriteFalse(0)/True(1)
BVmin2RunForwardCmdRun forward commandWriteFalse(0)/True(1)
BV3RunReverseCmdRun reverse commandWriteFalse(0)/True(1)
BVmin4ResetFaultCmdFault reset commandWriteFalse(0)/True(1)
BV5FreeRunStopCmdFree-run (coast) stop commandWriteFalse(0)/True(1)
BV6Relay1CmdRelay 1 on/off commandWriteFalse(0)/True(1)
BV7Relay2CmdRelay 2 on/off commandWriteFalse(0)/True(1)
BV8Relay3CmdRelay 3 on/off commandWriteFalse(0)/True(1)
BV9Relay4CmdRelay 4 on/off commandWriteFalse(0)/True(1)
BV10Relay5CmdRelay 5 on/off commandWriteFalse(0)/True(1)
BV11Q1CmdQ1 output on/off commandWriteFalse(0)/True(1)
AI1InvCap (kW)Inverter capacitykWRead
AI2InvCap(HP)Inverter capacityhpRead
AI3InvVoltageClassInverter voltage classVRead
AImin4OutputCurrentOutput currentARead
AImin5OutputFreqOutput frequencyHzRead
AI6OutputVolgateOutput voltageVRead
AI7DCLinkVoltageDC link voltageVRead
AImin8OutputPowerOutput powerkWRead
AI9AI1Analog input 1 value%Read
AI10AI2Analog input 2 value%Read
AI11OutputRPMOutput speedrpmRead
AI12PoleMotor pole numberRead
AI13InvStatusInverter state word (common area 0h0305)Read
AI14LatchTripInfo1Latch-type trip flags 1 (0h0330)Read
AI15LatchTripInfo2Latch-type trip flags 2 (0h0331)Read
AI16LatchTripInfo3Latch-type trip flags 3 (0h0335)Read
AI17LevelTripInfoLevel-type trip flags (0h0332)Read
AI18HWDIagInfoH/W diagnosis trip flags (0h0333)Read
AI19WarningInfoWarning flags (0h0334)Read
AI20KiloWattHourEnergy, kWh partkWhRead
AI21MegaWattHourEnergy, MWh partMWhRead
AI22PowerFactorPower factorRead
AI23RunTimeDayRun time, daysDayRead
AI24RunTimeMinRun time, minutesDayRead
AI25PidOutValuePID output value%Read
AI26PidReferenceValuePID setpoint value%Read
AI27PidFeedbackValuePID feedback value%Read
BI1StoppedStoppedRead
BImin2RunningForwardRunning forwardRead
BI3RunningReverseRunning reverseRead
BImin4TrippedTrip activeRead
BI5AcceleratingAcceleratingRead
BI6DeceleratingDeceleratingRead
BI7SteadySpeedAt steady speedRead
BI8RunningDCOperating at 0 step speedRead
BI9StoppingStoppingRead
BI10FwdRunCommandStateForward run command stateRead
BI11RevRunCommandStateReverse run command stateRead
BI12P1Input P1 stateRead
BI13P2Input P2 stateRead
BI14P3Input P3 stateRead
BI15P4Input P4 stateRead
BI16P5Input P5 stateRead
BI17P6Input P6 stateRead
BI18P7Input P7 stateRead
BI19Relay1Relay 1 stateRead
BI20Relay2Relay 2 stateRead
BI21Relay3Relay 3 stateRead
BI22Relay4Relay 4 stateRead
BI23Relay5Relay 5 stateRead
BI24Q1Q1 output stateRead
BI25SpeedSearchSpeed search activeRead
BI26HWOCSH/W overcurrent (OCS) occurredRead
BI27SWOCSS/W overcurrent (OCS) occurredRead
BI28RunningDwellDwell operation activeRead
BI29SteadyStateSteady stateRead
BImin30WarningWarning activeRead
MI1UnitsDisplaySpeed display unit settingRead1=Hz, 2=RPM
Object ID lookup: LS Electric H100 drive with CBAC-H100 Ethernet module point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the H100 drive with CBAC-H100 Ethernet module (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP)

How many BACnet points does the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) have?

This list has 76 BACnet objects: 27 analog inputs, 6 analog values, 30 binary inputs, 11 binary values, 1 multi-state input, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) BACnet points are writable?

18 of the 76 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) BACnet documentation?

The source is H100 BACnet IP (Ethernet) Communication Module User Manual (V1.2), revision 2026-09-30, published free by LS Electric at https://www.lselectricamerica.com/api/v1/fo/ctpApi/fileDownUrl?filePath=CTP%2FManual%2F790179813%2FH100%20BACNET%20IP(Ethernet)_User%20Manual_EN_V1.2_260930.pdf.

What are the minimum BACnet points to integrate the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP)?

Start with BV 2 RunForwardCmd (Run forward command (True = run)); BV 1 StopCmd (Stop command (True = stop)); AV 4 CommandFreqSet (Frequency reference, Hz); BV 4 ResetFaultCmd (Reset a tripped drive); BI 2 RunningForward (Running forward status); AI 5 OutputFreq (Output frequency, Hz); AI 4 OutputCurrent (Motor amps); AI 8 OutputPower (Output power, kW); BI 4 Tripped (Any active trip); BI 30 Warning (Any active warning).

How do I enable BMS control of the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP)?

DRV-06 Cmd Source = 4 (Field Bus) for run/stop and DRV-07 Freq Ref Src = 7 (Field Bus) for AV 4. AV 2-4 can be written in AUTO mode only.

Does the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP) need a BACnet heartbeat or have a communication timeout?

PRT-12 Lost Cmd Mode (default None: keep the last state; Free-Run, Dec, Hold Input, Hold Output, Lost Preset) and PRT-13 Lost Cmd Time (0.1-120 s, default 1.0 s) set the action when the network command is lost; PRT-14 is the Lost Preset speed. AV 1 CommTimeoutSet and MV 1 LostCommand have the same range and options.

Can the BMS supply sensor values to the LS Electric H100 drive with CBAC-H100 Ethernet module (BACnet IP)?

AV 6 PIDFeedbackSet lets the BMS write the PID feedback and AV 5 PIDReferenceSet the PID setpoint.

How do I check these points on the real H100 drive with CBAC-H100 Ethernet module (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More LS Electric BACnet points lists

Source: H100 BACnet IP (Ethernet) Communication Module User Manual · V1.2 · rev. 2026-09-30. Object names, instances and units are reproduced as published; descriptions are our own.