Variable frequency drive · BACnet points list

Lenze MCH Series drive (AC Tech, BACnet MS/TP) BACnet points list

Updated 7 November 2026Unofficial source

Short answer

The MCH Series is an older Lenze AC Tech HVAC drive. The BACnet version talks BACnet MS/TP as a slave device at 9600 baud, so the BMS must bind to it statically. It has a small fixed object set: speed and PID setpoint commands, run/stop, fault reset, and status and fault readbacks.

This page lists 23 BACnet objects for the Lenze MCH Series drive (AC Tech, BACnet MS/TP) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Lenze’s documentation hosted by Internet Archive (manualzilla collection), not by Lenze itself, so treat it as unofficial.

Manufacturer
Lenze
Model
MCH Series drive (AC Tech, BACnet MS/TP)
Equipment
Variable frequency drive
Equipment type
VFDs & pumps
BACnet objects
23 (5 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Default device instance
1240000
Also known as
AC Tech MCH, Lenze AC Tech MCH, MCH Series BACnet, RG-MHBAC
Source document
MCH Series Drives BACnet Communications Guide · RG-MHBAC-e2 · rev. 2003 (unofficial copy, hosted by Internet Archive (manualzilla collection))
Download CSV 23 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Lenze’s current documentation and the live device before use. Not official Lenze information. Terms of use.

BMS integration notes: Lenze MCH Series drive (AC Tech, BACnet MS/TP)

Integration in brief

Leave parameter 57 Serial at WITH TIMER, give the drive a MAC address and device number, keep parameter 24 Auto Source at KEYPAD and set parameter 30 Control to SERIAL AUTO (or S AUTO/NO HND). With the H/O/A in AUTO the BMS can then start the drive with BO 1 and set speed with AV 1 (or the PID setpoint with AV 2).

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1CMD RUN_STOPStart/stop commandCommand
AV 1KEY SPD CMDSpeed command, HzWrite
BV 1CLEAR FAULTFault reset; write CLR then NRMWrite
BI 1RUN_STOPRun statusRead
AI 1OUTPUT FREQOutput frequency, HzRead
MI 4HOA MODEMust be AUTO for LAN commandsRead
BI 3OK_FAULTDrive faultRead
MI 2FAULTPresent fault codeRead

Enable & remote start

Parameter 57 Serial must be WITH TIMER or W/O TIMER and parameter 24 Auto Source must be KEYPAD. Parameter 30 Control sets what the LAN may do: SERIAL SPEED allows speed/setpoint only, SERIAL AUTO or S AUTO/NO HND also allows start. The H/O/A must be in AUTO; in OFF or HAND the drive ignores LAN start and speed commands. LAN stop commands are always accepted.

Heartbeat & communication loss

With parameter 57 = WITH TIMER, a serial watchdog (parameter 60, 10-65535 s, default 30 s) takes the drive out of serial control if the LAN stops talking; in SERIAL AUTO a running drive trips on SERIAL FAULT. Set parameter 57 to W/O TIMER to disable it.

Network setup

Watch out for

Lenze MCH Series drive (AC Tech, BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

23 of 23 shown
Type
Access
Show
Lenze MCH Series drive (AC Tech, BACnet MS/TP) BACnet Points List
DescriptionStates
AImin1OUTPUT FREQActual output frequencyHzRead
AI2COMMAND FREQCommanded frequencyHzRead
AI3LOAD PERCENTLoad current, % of rated%Read
AI4RUNTIME HRSTotal runtime hourshRead
AI5DC BUS VOLTSDC bus voltage, % of nominal%Read
AI6PID SETPOINTCommanded PID setpoint%Read
AI7PID FEEDBACKPID feedback value%Read
AVmin1KEY SPD CMDKeypad speed command (LAN writable)HzWrite
AV2KEY STPT CMDKeypad PID setpoint command (LAN writable)%Write
BImin1RUN_STOPRun/stop statusReadInactive=STP, Active=RUN
BI2DIRECTIONCurrent directionReadInactive=FWD, Active=REV
BImin3OK_FAULTFault conditionReadInactive=OK, Active=FLT
BI4TB14_RELAY2TB-14 / relay 2 output stateReadInactive=OFF, Active=ON
BI5TB15_RELAY3TB-15 / relay 3 output stateReadInactive=OFF, Active=ON
BI6RELAY1Relay 1 output stateReadInactive=OFF, Active=ON
BOmin1CMD RUN_STOPStart/stop command (priority array)CommandInactive=STP, Active=RUN
BVmin1CLEAR FAULTClear present faultWriteInactive=NRM, Active=CLR
MI1RUN STATUSOperational statusRead1=LOCK, 2=FAULT, 3=PEND, 4=STOP, 5=BRAKE, 6=RUN@0, 7=RUN, 8=ACCEL, 9=DECEL, 10=LIMIT, 11=F DEC, 12=INVAL, 13=KSTOP, 14=KSTOP, 15=RSTOP, 16=SSTOP
MImin2FAULTPresent faultRead1=NO FAULT, 2=OUTPUT, 3=E-STOP, 4=HI VOLTS, 5=HI TEMP, 6=OVERLOAD, 7=OUTPUT, 8=LO VOLTS, 9=START ER, 10=BRAKE ER, 11=FOLLOWER, 12=DB ERROR, 13=PWR SAG, 14=CONTROL, 15=LANGUAGE, 16=EXTERNAL, 17=INTERNAL16, 18=PWR TRAN, 19=INTERNAL18, 20=INTERNAL19, 21=INTERNAL20, 22=INTERNAL21, 23=INTERNAL22, 24=INTERNAL23, 25=SERIAL
MI3PID MODEPID modeRead1=OFF, 2=NORMAL, 3=REVERSE
MImin4HOA MODEHand/Off/Auto modeRead1=OFF, 2=HAND, 3=AUTO
MI5SPD_STPT REFActive speed/setpoint reference sourceRead1=-KEY, 2=-VDC, 3=-IDC, 4=SP#1, 5=SP#2, 6=SP#3, 7=SP#4, 8=-MOP, 9=-SER, 10=-MKB, 11=-AKB, 12=-VDC, 13=-IDC, 14=SP#1, 15=SP#2, 16=SP#3, 17=SP#4, 18=-MOP, 19=-SER
MV1SOURCE SELSpeed source selectionWrite1=NORMAL, 2=HAND, 3=AUTO
Object ID lookup: Lenze MCH Series drive point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MCH Series drive (AC Tech, BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lenze MCH Series drive (AC Tech, BACnet MS/TP)

How many BACnet points does the Lenze MCH Series drive (AC Tech, BACnet MS/TP) have?

This list has 23 BACnet objects: 7 analog inputs, 2 analog values, 6 binary inputs, 1 binary output, 1 binary value, 5 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lenze MCH Series drive (AC Tech, BACnet MS/TP) BACnet points are writable?

5 of the 23 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Lenze MCH Series drive (AC Tech, BACnet MS/TP) BACnet documentation?

Lenze does not publish it on its own website. This list comes from MCH Series Drives BACnet Communications Guide (RG-MHBAC-e2), revision 2003, a copy hosted by Internet Archive (manualzilla collection) at https://archive.org/download/manualzilla-id-5789887/5789887.pdf. Ask Lenze or its representative for the current revision.

What are the minimum BACnet points to integrate the Lenze MCH Series drive (AC Tech, BACnet MS/TP)?

Start with BO 1 CMD RUN_STOP (Start/stop command); AV 1 KEY SPD CMD (Speed command, Hz); BV 1 CLEAR FAULT (Fault reset; write CLR then NRM); BI 1 RUN_STOP (Run status); AI 1 OUTPUT FREQ (Output frequency, Hz); MI 4 HOA MODE (Must be AUTO for LAN commands); BI 3 OK_FAULT (Drive fault); MI 2 FAULT (Present fault code).

How do I enable BMS control of the Lenze MCH Series drive (AC Tech, BACnet MS/TP)?

Parameter 57 Serial must be WITH TIMER or W/O TIMER and parameter 24 Auto Source must be KEYPAD. Parameter 30 Control sets what the LAN may do: SERIAL SPEED allows speed/setpoint only, SERIAL AUTO or S AUTO/NO HND also allows start. The H/O/A must be in AUTO; in OFF or HAND the drive ignores LAN start and speed commands. LAN stop commands are always accepted.

Does the Lenze MCH Series drive (AC Tech, BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?

With parameter 57 = WITH TIMER, a serial watchdog (parameter 60, 10-65535 s, default 30 s) takes the drive out of serial control if the LAN stops talking; in SERIAL AUTO a running drive trips on SERIAL FAULT. Set parameter 57 to W/O TIMER to disable it.

How do I check these points on the real MCH Series drive (AC Tech, BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Lenze BACnet points lists

Source: MCH Series Drives BACnet Communications Guide · RG-MHBAC-e2 · rev. 2003. Object names, instances and units are reproduced as published; descriptions are our own.