- MCH Series drive (AC Tech, BACnet MS/TP)
Variable frequency drive · BACnet points list
Lenze MCH Series drive (AC Tech, BACnet MS/TP) BACnet points list
Updated 7 November 2026Unofficial source
The MCH Series is an older Lenze AC Tech HVAC drive. The BACnet version talks BACnet MS/TP as a slave device at 9600 baud, so the BMS must bind to it statically. It has a small fixed object set: speed and PID setpoint commands, run/stop, fault reset, and status and fault readbacks.
This page lists 23 BACnet objects for the Lenze MCH Series drive (AC Tech, BACnet MS/TP) — 5 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of Lenze’s documentation hosted by Internet Archive (manualzilla collection), not by Lenze itself, so treat it as unofficial.
- Manufacturer
- Lenze
- Model
- MCH Series drive (AC Tech, BACnet MS/TP)
- Equipment
- Variable frequency drive
- Equipment type
- VFDs & pumps
- BACnet objects
- 23 (5 writable)
- Transport
- BACnet MS/TP
- Firmware
- Not stated
- Default device instance
- 1240000
- Also known as
- AC Tech MCH, Lenze AC Tech MCH, MCH Series BACnet, RG-MHBAC
- Source document
- MCH Series Drives BACnet Communications Guide · RG-MHBAC-e2 · rev. 2003 (unofficial copy, hosted by Internet Archive (manualzilla collection))
Reference only, provided as-is: verify against Lenze’s current documentation and the live device before use. Not official Lenze information. Terms of use.
BMS integration notes: Lenze MCH Series drive (AC Tech, BACnet MS/TP)
Leave parameter 57 Serial at WITH TIMER, give the drive a MAC address and device number, keep parameter 24 Auto Source at KEYPAD and set parameter 30 Control to SERIAL AUTO (or S AUTO/NO HND). With the H/O/A in AUTO the BMS can then start the drive with BO 1 and set speed with AV 1 (or the PID setpoint with AV 2).
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BO 1 | CMD RUN_STOP | Start/stop command | Command |
| AV 1 | KEY SPD CMD | Speed command, Hz | Write |
| BV 1 | CLEAR FAULT | Fault reset; write CLR then NRM | Write |
| BI 1 | RUN_STOP | Run status | Read |
| AI 1 | OUTPUT FREQ | Output frequency, Hz | Read |
| MI 4 | HOA MODE | Must be AUTO for LAN commands | Read |
| BI 3 | OK_FAULT | Drive fault | Read |
| MI 2 | FAULT | Present fault code | Read |
Enable & remote start
Parameter 57 Serial must be WITH TIMER or W/O TIMER and parameter 24 Auto Source must be KEYPAD. Parameter 30 Control sets what the LAN may do: SERIAL SPEED allows speed/setpoint only, SERIAL AUTO or S AUTO/NO HND also allows start. The H/O/A must be in AUTO; in OFF or HAND the drive ignores LAN start and speed commands. LAN stop commands are always accepted.
Heartbeat & communication loss
With parameter 57 = WITH TIMER, a serial watchdog (parameter 60, 10-65535 s, default 30 s) takes the drive out of serial control if the LAN stops talking; in SERIAL AUTO a running drive trips on SERIAL FAULT. Set parameter 57 to W/O TIMER to disable it.
Network setup
- MAC address: parameter 58, default 128 (0-254).
- Baud rate is fixed at 9600.
- Device instance: parameters 85 and 86, default 1240000.
Watch out for
- MS/TP slave only: the BMS must use static binding.
- BV 1 must go back to NRM before another fault clear is accepted.
- Once the LAN writes AV 1 the keypad cannot change speed until H/O/A is toggled to HAND or OFF.
- LAN speed control needs MI 5 in state 1, 9 or 10; LAN setpoint control needs state 11 or 19.
- The drive does not accept start commands from the LAN while in programming mode, and the display must show SSTOP for a LAN start to work.
Lenze MCH Series drive (AC Tech, BACnet MS/TP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | OUTPUT FREQ | Actual output frequency | Hz | Read | |
| AI | 2 | COMMAND FREQ | Commanded frequency | Hz | Read | |
| AI | 3 | LOAD PERCENT | Load current, % of rated | % | Read | |
| AI | 4 | RUNTIME HRS | Total runtime hours | h | Read | |
| AI | 5 | DC BUS VOLTS | DC bus voltage, % of nominal | % | Read | |
| AI | 6 | PID SETPOINT | Commanded PID setpoint | % | Read | |
| AI | 7 | PID FEEDBACK | PID feedback value | % | Read | |
| AVmin | 1 | KEY SPD CMD | Keypad speed command (LAN writable) | Hz | Write | |
| AV | 2 | KEY STPT CMD | Keypad PID setpoint command (LAN writable) | % | Write | |
| BImin | 1 | RUN_STOP | Run/stop status | Read | Inactive=STP, Active=RUN | |
| BI | 2 | DIRECTION | Current direction | Read | Inactive=FWD, Active=REV | |
| BImin | 3 | OK_FAULT | Fault condition | Read | Inactive=OK, Active=FLT | |
| BI | 4 | TB14_RELAY2 | TB-14 / relay 2 output state | Read | Inactive=OFF, Active=ON | |
| BI | 5 | TB15_RELAY3 | TB-15 / relay 3 output state | Read | Inactive=OFF, Active=ON | |
| BI | 6 | RELAY1 | Relay 1 output state | Read | Inactive=OFF, Active=ON | |
| BOmin | 1 | CMD RUN_STOP | Start/stop command (priority array) | Command | Inactive=STP, Active=RUN | |
| BVmin | 1 | CLEAR FAULT | Clear present fault | Write | Inactive=NRM, Active=CLR | |
| MI | 1 | RUN STATUS | Operational status | Read | 1=LOCK, 2=FAULT, 3=PEND, 4=STOP, 5=BRAKE, 6=RUN@0, 7=RUN, 8=ACCEL, 9=DECEL, 10=LIMIT, 11=F DEC, 12=INVAL, 13=KSTOP, 14=KSTOP, 15=RSTOP, 16=SSTOP | |
| MImin | 2 | FAULT | Present fault | Read | 1=NO FAULT, 2=OUTPUT, 3=E-STOP, 4=HI VOLTS, 5=HI TEMP, 6=OVERLOAD, 7=OUTPUT, 8=LO VOLTS, 9=START ER, 10=BRAKE ER, 11=FOLLOWER, 12=DB ERROR, 13=PWR SAG, 14=CONTROL, 15=LANGUAGE, 16=EXTERNAL, 17=INTERNAL16, 18=PWR TRAN, 19=INTERNAL18, 20=INTERNAL19, 21=INTERNAL20, 22=INTERNAL21, 23=INTERNAL22, 24=INTERNAL23, 25=SERIAL | |
| MI | 3 | PID MODE | PID mode | Read | 1=OFF, 2=NORMAL, 3=REVERSE | |
| MImin | 4 | HOA MODE | Hand/Off/Auto mode | Read | 1=OFF, 2=HAND, 3=AUTO | |
| MI | 5 | SPD_STPT REF | Active speed/setpoint reference source | Read | 1=-KEY, 2=-VDC, 3=-IDC, 4=SP#1, 5=SP#2, 6=SP#3, 7=SP#4, 8=-MOP, 9=-SER, 10=-MKB, 11=-AKB, 12=-VDC, 13=-IDC, 14=SP#1, 15=SP#2, 16=SP#3, 17=SP#4, 18=-MOP, 19=-SER | |
| MV | 1 | SOURCE SEL | Speed source selection | Write | 1=NORMAL, 2=HAND, 3=AUTO |
No points match these filters.
Object ID lookup: Lenze MCH Series drive point IDs by name
AI1OUTPUT FREQAI2COMMAND FREQAI3LOAD PERCENTAI4RUNTIME HRSAI5DC BUS VOLTSAI6PID SETPOINTAI7PID FEEDBACKAV1KEY SPD CMDAV2KEY STPT CMDBI1RUN_STOPBI2DIRECTIONBI3OK_FAULTBI4TB14_RELAY2BI5TB15_RELAY3BI6RELAY1BO1CMD RUN_STOPBV1CLEAR FAULTMI1RUN STATUSMI2FAULTMI3PID MODEMI4HOA MODEMI5SPD_STPT REFMV1SOURCE SEL
Integration notes
- The drive is an MS/TP slave, so only BMS devices that support static device binding can reach it.
- Default MAC address is 128 (parameter 58, range 0-254); baud rate is fixed at 9600.
- Device instance is set with parameters 85 (bits 16-22) and 86 (bits 0-15); default 1240000.
- Object names are the short names printed in brackets in the object map; the access column is inferred from object type and the object descriptions.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the MCH Series drive (AC Tech, BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Lenze MCH Series drive (AC Tech, BACnet MS/TP)
How many BACnet points does the Lenze MCH Series drive (AC Tech, BACnet MS/TP) have?
This list has 23 BACnet objects: 7 analog inputs, 2 analog values, 6 binary inputs, 1 binary output, 1 binary value, 5 multi-state inputs, 1 multi-state value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Lenze MCH Series drive (AC Tech, BACnet MS/TP) BACnet points are writable?
5 of the 23 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Lenze MCH Series drive (AC Tech, BACnet MS/TP) BACnet documentation?
Lenze does not publish it on its own website. This list comes from MCH Series Drives BACnet Communications Guide (RG-MHBAC-e2), revision 2003, a copy hosted by Internet Archive (manualzilla collection) at https://archive.org/download/manualzilla-id-5789887/5789887.pdf. Ask Lenze or its representative for the current revision.
What are the minimum BACnet points to integrate the Lenze MCH Series drive (AC Tech, BACnet MS/TP)?
Start with BO 1 CMD RUN_STOP (Start/stop command); AV 1 KEY SPD CMD (Speed command, Hz); BV 1 CLEAR FAULT (Fault reset; write CLR then NRM); BI 1 RUN_STOP (Run status); AI 1 OUTPUT FREQ (Output frequency, Hz); MI 4 HOA MODE (Must be AUTO for LAN commands); BI 3 OK_FAULT (Drive fault); MI 2 FAULT (Present fault code).
How do I enable BMS control of the Lenze MCH Series drive (AC Tech, BACnet MS/TP)?
Parameter 57 Serial must be WITH TIMER or W/O TIMER and parameter 24 Auto Source must be KEYPAD. Parameter 30 Control sets what the LAN may do: SERIAL SPEED allows speed/setpoint only, SERIAL AUTO or S AUTO/NO HND also allows start. The H/O/A must be in AUTO; in OFF or HAND the drive ignores LAN start and speed commands. LAN stop commands are always accepted.
Does the Lenze MCH Series drive (AC Tech, BACnet MS/TP) need a BACnet heartbeat or have a communication timeout?
With parameter 57 = WITH TIMER, a serial watchdog (parameter 60, 10-65535 s, default 30 s) takes the drive out of serial control if the LAN stops talking; in SERIAL AUTO a running drive trips on SERIAL FAULT. Set parameter 57 to W/O TIMER to disable it.
How do I check these points on the real MCH Series drive (AC Tech, BACnet MS/TP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Lenze BACnet points lists
Source: MCH Series Drives BACnet Communications Guide · RG-MHBAC-e2 · rev. 2003. Object names, instances and units are reproduced as published; descriptions are our own.