Easy BACnet
  1. Home
  2. BACnet points lists
  3. Lenze
  4. i500 inverter (BACnet MS/TP)

Variable frequency drive · BACnet points list

Lenze i500 inverter (BACnet MS/TP) BACnet points list

Updated 28 October 2026

Short answer

The Lenze i500 inverter talks BACnet MS/TP directly. Its PICS lists 77 fixed objects: 16 binary values that trigger the drive's mappable network functions (run forward, quick stop, reset and so on), status bits from the drive status word, a frequency setpoint and readings as analog values, and a mailbox for reading and writing any drive parameter.

This page lists 77 BACnet objects for the Lenze i500 inverter (BACnet MS/TP) — 34 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Lenze’s own free documentation, linked below.

Manufacturer
Lenze
Model
i500 inverter (BACnet MS/TP)
Equipment
Variable frequency drive
Equipment type
VFDs & pumps
BACnet objects
77 (34 writable)
Transport
BACnet MS/TP
Firmware
Firmware V01.04, application software V05.02.00.xx
Also known as
i500, Lenze i500, i510, i550, I51AE, Lenze i500 BACnet
Source document
Lenze i500 BACnet Protocol Implementation Conformance Statement · PICS V01.04 · rev. 2018-04-23
Download CSV 77 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Lenze i500 inverter (BACnet MS/TP)

Integration in brief

Use AV 9 Network Control to hand control to BACnet, write the frequency setpoint to AV 0 and run with BV 4 Run forward (default mapping). Read BV 22 running, AV 13 frequency, AV 17 current and BV 20 fault, and reset with BV 7. Check the 0x400E mapping on site, since BV 0-15 can be remapped.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 4Run forwardRun command (default mapping)Command
AV 9Network ControlActivates network control (0x2631:037)Command
AV 0Net.freq 0.01Frequency setpoint in 0.01 HzCommand
BV 7Reset errorReset a tripped drive (default mapping)Command
BV 22E:Running ForwardRunning forward statusRead
BV 25E:Control from NetworkDrive is under network controlRead
AV 13Frequency 0.01Actual output frequencyRead
AV 17Motor CurrentMotor ampsRead
BV 20E:Faulted/TripAny active drive faultRead
AV 14Error CodeActive error codeRead

Enable & remote start

AV 9 Network Control (0x2631:037) activates network control and AV 8 sets the default setpoint source (0x2860:001); BV 25 and BV 26 show when network control and the network setpoint are active. The PICS gives no values for AV 8 or AV 9; see the i500 manual.

Sensors & values from the BMS

AV 1 PID Setpoint takes a network PID setpoint (in the PID unit) when the drive's process controller is used.

Network setup

Watch out for

Lenze i500 inverter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

77 of 77 shown
Type
Access
Show
Lenze i500 inverter (BACnet MS/TP) BACnet Points List
DescriptionStates
AI0AI1 terminal %Analog input at terminal AI1 (0x2DA4:001)%Read
AI1AI1 terminal %Analog input at terminal AI2 (0x2DA5:001)%Read
AO0NetWordIN3Analog output value (0x4008:003)%Command
AVmin0Net.freq 0.01Network frequency setpoint (0x400B:005)0.01 HzCommand
AV1PID SetpointNetwork PID setpoint, PID unit (0x400B:007)Command
AV2Target torqueTarget torque (0x6071)%Command
AV3Accelerat. time 1Acceleration time 1 (0x2917)secWrite
AV4Decelerat. Time 1Deceleration time 1 (0x2918)secWrite
AV5QSP dec. timeQuick stop deceleration time (0x291C)secWrite
AV6ReservedReservedRead
AV7ReservedReservedRead
AV8Freq. setp. src.Default setpoint source (0x2860:001)Command
AVmin9Network ControlActivate network control (0x2631:037)Command
AV10Save ParametersSave parameters (0x2022:003)Write
AV11Mailbox ParameterParameter index/subindex for mailbox, 0xAAAABB00Write
AV12Mailbox DataMailbox value read or to writeWrite
AVmin13Frequency 0.01Actual frequency (0x400C:006), 0.01 HzHzRead
AVmin14Error CodeError code (0x603F)Read
AV15Drive StatusDrive status (0x400C:005)Read
AV16Motor VoltageMotor voltage (0x2D89)VRead
AVmin17Motor CurrentMotor current (0x2D88)ARead
AV18Current ActualMotor load, % of rated (0x6078)%Read
AV19Effective powerEffective output power (0x2DA2:001)kWRead
AV20Apparent powerApparent output power (0x2DA2:002)kVARead
AV21Heatsink temp.Heatsink temperature (0x2D84:001)°CRead
AV22DC-bus voltageDC bus voltage (0x2D87)VRead
AV23PID process var.PID actual feedback, PID unit (0x401F:002)Read
AV24Torque ActualActual torque, % of nominal (0x6077)%Read
AV25Active controlActive control source (0x282B:001)Read
AV26Active setpointActive setpoint source (0x282B:002)Read
AV27ReservedReservedRead
AV28ReservedReservedRead
AV29ReservedUser object 1 when set up as AVWrite
AV30ReservedUser object 2 when set up as AVWrite
BI0Digital Input 1Status of digital input 1Read0=Not Active, 1=Active
BI1Digital Input 2Status of digital input 2Read0=Not Active, 1=Active
BI2Digital Input 3Status of digital input 3Read0=Not Active, 1=Active
BI3Digital Input 4Status of digital input 4Read0=Not Active, 1=Active
BI4Digital Input 5Status of digital input 5Read0=Not Active, 1=Active
BV0Not activeReserved (no function mapped by default)Command0=Not Active, 1=Active
BV1Not activeReserved (no function mapped by default)Command0=Not Active, 1=Active
BV2Quick stopQuick stop (default map 0x400E:003 = 3)Command0=Not Active, 1=Active
BV3Not activeReserved (no function mapped by default)Command0=Not Active, 1=Active
BVmin4Run forwardRun forward (default map 0x400E:005 = 8)Command0=Not Active, 1=Active
BV5Setp: Preset b0Preset setpoint select bit 0 (default map)Command0=Not Active, 1=Active
BV6Setp: Preset b1Preset setpoint select bit 1 (default map)Command0=Not Active, 1=Active
BVmin7Reset errorReset error (default map 0x400E:008 = 4)Command0=Not Active, 1=Active
BV8Not activeReserved (no function mapped by default)Command0=Not Active, 1=Active
BV9DC brakingDC braking (default map 0x400E:010 = 5)Command0=Not Active, 1=Active
BV10Not activeReserved (no function mapped by default)Command0=Not Active, 1=Active
BV11Not activeReserved (no function mapped by default)Command0=Not Active, 1=Active
BV12Reverse rot. dir.Reverse direction (default map 0x400E:013 = 13)Command0=Not Active, 1=Active
BV13Not activeReserved (no function mapped by default)Command0=Not Active, 1=Active
BV14Not activeReserved (no function mapped by default)Command0=Not Active, 1=Active
BV15Not activeReserved (no function mapped by default)Command0=Not Active, 1=Active
BV16Mailbox ReadWrite 1 to read the parameter set in AV 11Write0=Not Active, 1=Active
BV17Mailbox WriteWrite 1 to write AV 12 into the parameter in AV 11Write0=Not Active, 1=Active
BV18ReservedReservedRead0=Not Active, 1=Active
BV19ReservedReservedRead0=Not Active, 1=Active
BVmin20E:Faulted/TripFault/trip activeRead0=Not Active, 1=Active
BV21E:Warning ActiveWarning activeRead0=Not Active, 1=Active
BVmin22E:Running ForwardRunning forwardRead0=Not Active, 1=Active
BV23E:Running ReverseRunning reverseRead0=Not Active, 1=Active
BV24E:ReadyDrive readyRead0=Not Active, 1=Active
BVmin25E:Control from NetworkNetwork control activeRead0=Not Active, 1=Active
BV26E: Reference from NetworkNetwork setpoint activeRead0=Not Active, 1=Active
BV27E:At ReferenceAt reference speedRead0=Not Active, 1=Active
BV28Profile State bit0Profile state bit 0 (0x400C:001)Read0=Not Active, 1=Active
BV29Profile State bit1Profile state bit 1 (0x400C:001)Read0=Not Active, 1=Active
BV30Profile State bit2Profile state bit 2 (0x400C:001)Read0=Not Active, 1=Active
BV31Profile State bit3Profile state bit 3 (0x400C:001)Read0=Not Active, 1=Active
BV32E:PID activeProcess (PID) controller activeRead0=Not Active, 1=Active
BV33E:Torque mode activeTorque mode activeRead0=Not Active, 1=Active
BV34E:Current LimitCurrent limit reachedRead0=Not Active, 1=Active
BV35E:DC Brake ActiveDC braking activeRead0=Not Active, 1=Active
BV36ReservedUser object 1 when set up as BVWrite0=Not Active, 1=Active
BV37ReservedUser object 2 when set up as BVWrite0=Not Active, 1=Active

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the i500 inverter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Lenze i500 inverter (BACnet MS/TP)

How many BACnet points does the Lenze i500 inverter (BACnet MS/TP) have?

This list has 77 BACnet objects: 2 analog inputs, 1 analog output, 31 analog values, 5 binary inputs, 38 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Lenze i500 inverter (BACnet MS/TP) BACnet points are writable?

34 of the 77 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Lenze i500 inverter (BACnet MS/TP) BACnet documentation?

The source is Lenze i500 BACnet Protocol Implementation Conformance Statement (PICS V01.04), revision 2018-04-23, published free by Lenze at https://www.bacnetinternational.net/catalog/manu/lenze%20americas/lenze_i500_bacnet_pics_v01_04.pdf.

What are the minimum BACnet points to integrate the Lenze i500 inverter (BACnet MS/TP)?

Start with BV 4 Run forward (Run command (default mapping)); AV 9 Network Control (Activates network control (0x2631:037)); AV 0 Net.freq 0.01 (Frequency setpoint in 0.01 Hz); BV 7 Reset error (Reset a tripped drive (default mapping)); BV 22 E:Running Forward (Running forward status); BV 25 E:Control from Network (Drive is under network control); AV 13 Frequency 0.01 (Actual output frequency); AV 17 Motor Current (Motor amps); BV 20 E:Faulted/Trip (Any active drive fault); AV 14 Error Code (Active error code).

How do I enable BMS control of the Lenze i500 inverter (BACnet MS/TP)?

AV 9 Network Control (0x2631:037) activates network control and AV 8 sets the default setpoint source (0x2860:001); BV 25 and BV 26 show when network control and the network setpoint are active. The PICS gives no values for AV 8 or AV 9; see the i500 manual.

Can the BMS supply sensor values to the Lenze i500 inverter (BACnet MS/TP)?

AV 1 PID Setpoint takes a network PID setpoint (in the PID unit) when the drive's process controller is used.

How do I check these points on the real i500 inverter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Lenze i500 BACnet Protocol Implementation Conformance Statement · PICS V01.04 · rev. 2018-04-23. Object names, instances and units are reproduced as published; descriptions are our own.