Laars Sola control - ProtoNode BACnet points list

Updated 28 October 2026

Short answer

The ProtoNode reads the Sola control over Modbus RTU and serves 88 objects per boiler: 64 analog inputs and 24 analog values. The AIs cover sensors, firing rate, burner and CH/DHW status codes, pump status and lead-lag slave states; the AVs hold CH enable, CH, DHW and lead-lag setpoints, time-of-day setpoints and resettable counters.

This page lists 88 BACnet objects for the Laars Sola control - ProtoNode — 24 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Laars’s own free documentation, linked below.

Manufacturer
Laars
Model
Sola control - ProtoNode
Equipment
Boiler controller gateway
Equipment type
Boilers & water heaters
BACnet objects
88 (24 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50000 + device Node-ID
Also known as
Sola, Laars Sola, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode
Source document
Vendor Protocol Mapping (LAARS Vendor Mappings for the ProtoNode FPC-N34 / FPC-N35) · 4404 · rev. Document Revision 14.B, October 2020
Download CSV 88 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Laars Sola control - ProtoNode

Integration in brief

Write CH Enable and the CH setpoint (or the lead-lag setpoint on a lead-lag master), then read back CH status, the burner sequence, outlet temperature, firing rate and the lockout code. The mapping gives no values or units, so check written values against the boiler display.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 76CH EnableCentral heat enableWrite
AV 46CH setpointCentral heat water setpointWrite
AV 50Lead Lag setpointSetpoint for a lead-lag (cascade) masterWrite
AI 19CH statusCentral heat status codeRead
AI 71Burner Control SequenceBurner sequence stateRead
AI 2Outlet sensorOutlet water temperatureRead
AI 3Firing rateBurner firing rateRead
AI 16Lockout codeLockout status codeRead

Enable & remote start

AV 76 CH Enable is the writable enable. The mapping does not give its values or say how it interacts with the boiler's own enable settings. AV 87 Burner Switch is also writable but is not explained.

Network setup

Watch out for

Laars Sola control - ProtoNode BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

88 of 88 shown
Type
Access
Show
Laars Sola control - ProtoNode BACnet Points List
DescriptionStates
AI1Demand sourceRead
AImin2Outlet sensorTemperatureRead
AImin3Firing rateRead
AI4Fan speedRead
AI5Flame signalRead
AI6Inlet sensorTemperatureRead
AI7DHW sensorTemperatureRead
AI8S5 sensorTemperatureRead
AI9Stack sensorTemperatureRead
AI104 - 20 mA remote ctl inputRead
AI11Active CH setpointTemperatureRead
AI12Active DHW setpointTemperatureRead
AI13Active LL setpointTemperatureRead
AI14Analog modulation inputRead
AI15Burner control statusRead
AImin16Lockout codeRead
AI17Alarm reasonRead
AI18Hold codeRead
AImin19CH statusRead
AI20CH setpoint sourceRead
AI21CH heat demandRead
AI22CH burner demandRead
AI23CH requested rateRead
AI24DHW statusRead
AI25DHW Priority CountRead
AI26DHW heat demandRead
AI27DHW burner demandRead
AI28DHW requested rateRead
AI29DHW pump statusRead
AI30DHW Pump Idle Days CountRead
AI31System pump statusRead
AI32System Pump Idle Days CountRead
AI33Boiler pump statusRead
AI34Boiler Pump Idle Days CountRead
AI39Controller Cycle CountRead
AI40Controller run timeRead
AI41Lead lag master statusRead
AI42Lead lag slave statusRead
AI43Lead Lag Master Setpoint SourceRead
AI44Lead Lag Master Pump DemandRead
AI45Outdoor temperatureTemperatureRead
AI53Lead Lag active serviceRead
AI54Slave 1 StateRead
AI55Slave 1 firing rateRead
AI56Slave 2 StateRead
AI57Slave 2 firing rateRead
AI58Slave 3 StateRead
AI59Slave 3 firing rateRead
AI60Slave 4 StateRead
AI61Slave 4 firing rateRead
AI62Slave 5 StateRead
AI63Slave 5 firing rateRead
AI64Slave 6 StateRead
AI65Slave 6 firing rateRead
AI66Slave 7 StateRead
AI67Slave 7 firing rateRead
AI68Slave 8 StateRead
AI69Slave 8 firing rateRead
AI70Master firing rateRead
AImin71Burner Control SequenceRead
AI72Active Rate LimiterRead
AI74Lead Lag Slave DemandRead
AI75Lead Lag Slave Requested RateRead
AI88S10 Sensor ReadingTemperatureRead
AV35Burner run timehWrite
AV36DHW pump cycle countWrite
AV37System pump cycle countWrite
AV38Boiler pump cycle countWrite
AVmin46CH setpointTemperatureWrite
AV47CH TOD setpointTemperatureWrite
AV48DHW Demand SwitchWrite
AV49Outlet high limit setpointTemperatureWrite
AVmin50Lead Lag setpointTemperatureWrite
AV51Leadlag modulation sensorWrite
AV52Warm weather shutdown setpointTemperatureWrite
AV73Burner Cycle CountWrite
AVmin76CH EnableWrite
AV77DHW SetpointTemperatureWrite
AV78DHW Time Of Day SetpointTemperatureWrite
AV79Lead Lag Slave EnableWrite
AV80Lead Lag Time Of Day SetpointTemperatureWrite
AV81Lead Lag Operation SwitchWrite
AV82Warm Weather Shutdown Enbl/DisblWrite
AV83Lead Lag DHW SetpointTemperatureWrite
AV84Lead Lag DHW Time Of Day SPTemperatureWrite
AV85Password Reg 1Write
AV86Password Reg 2Write
AV87Burner SwitchWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Sola control - ProtoNode and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Laars Sola control - ProtoNode

How many BACnet points does the Laars Sola control - ProtoNode have?

This list has 88 BACnet objects: 64 analog inputs, 24 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Laars Sola control - ProtoNode BACnet points are writable?

24 of the 88 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Laars Sola control - ProtoNode BACnet documentation?

The source is Vendor Protocol Mapping (LAARS Vendor Mappings for the ProtoNode FPC-N34 / FPC-N35) (4404), revision Document Revision 14.B, October 2020, published free by Laars at https://www.laars.com/uploads/products/4404.pdf.

What are the minimum BACnet points to integrate the Laars Sola control - ProtoNode?

Start with AV 76 CH Enable (Central heat enable); AV 46 CH setpoint (Central heat water setpoint); AV 50 Lead Lag setpoint (Setpoint for a lead-lag (cascade) master); AI 19 CH status (Central heat status code); AI 71 Burner Control Sequence (Burner sequence state); AI 2 Outlet sensor (Outlet water temperature); AI 3 Firing rate (Burner firing rate); AI 16 Lockout code (Lockout status code).

How do I enable BMS control of the Laars Sola control - ProtoNode?

AV 76 CH Enable is the writable enable. The mapping does not give its values or say how it interacts with the boiler's own enable settings. AV 87 Burner Switch is also writable but is not explained.

How do I check these points on the real Sola control - ProtoNode?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Laars BACnet points lists

Source: Vendor Protocol Mapping (LAARS Vendor Mappings for the ProtoNode FPC-N34 / FPC-N35) · 4404 · rev. Document Revision 14.B, October 2020. Object names, instances and units are reproduced as published; descriptions are our own.