Boiler controller gateway · BACnet points list

Laars Multiburner control - ProtoNode BACnet points list

Updated 28 October 2026

Short answer

The ProtoNode reads the Multiburner control over Modbus RTU and serves 149 objects per boiler. Analog inputs cover temperatures, flame signals, fan and blower speeds, lockout and blocking codes, history counters and lead-lag slave states; binary inputs show the safety chain switches, contacts and gas valve stages. Writable AVs and BVs hold the CH1-CH4, DHW and cascade enables, setpoints and PID terms plus the demand switches.

This page lists 149 BACnet objects for the Laars Multiburner control - ProtoNode — 48 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Laars’s own free documentation, linked below.

Manufacturer
Laars
Model
Multiburner control - ProtoNode
Equipment
Boiler controller gateway
Equipment type
Boilers & water heaters
BACnet objects
149 (48 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50000 + device Node-ID
Also known as
Multiburner, Laars Multiburner, Multi-burner, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode
Source document
Vendor Protocol Mapping (LAARS Vendor Mappings for the ProtoNode FPC-N34 / FPC-N35) · 4404 · rev. Document Revision 14.B, October 2020
Download CSV 149 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Laars Multiburner control - ProtoNode

Integration in brief

Enable the CH1 circuit, give it a call for heat with BV 1 and write the CH1 setpoint (or the cascade setpoint when boilers run in cascade). Read the run contact, burner 1 status and outlet temperature, and watch the alarm contact and lockout code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0CH1 enable/disableCH1 heating circuit enableWrite
BV 1CH1 demandCH1 call for heatWrite
AV 1CH1 setpointCH1 water setpointWrite
AV 27Cascade setpointSetpoint when boilers run in cascadeWrite
BI 2100Boiler Run ContactBoiler run outputRead
AI 84Burner 1 statusBurner 1 state codeRead
AI 1Outlet TempOutlet water temperatureRead
BI 2101Alarm ContactAlarm outputRead
AI 35Lockout CodeLockout reason codeRead

Enable & remote start

AV 0 CH1 enable/disable enables the CH1 circuit and BV 1 CH1 demand is its call for heat; the mapping gives no values for either. CH2-CH4 and DHW have matching enable, setpoint and demand objects.

Network setup

Watch out for

Laars Multiburner control - ProtoNode BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

149 of 149 shown
Type
Access
Show
Laars Multiburner control - ProtoNode BACnet Points List
DescriptionStates
AI0Inlet TempTemperatureRead
AImin1Outlet TempTemperatureRead
AI3DHW TempTemperatureRead
AI4System Inlet TempTemperatureRead
AI5System Outlet TempTemperatureRead
AI6Outdoor TempTemperatureRead
AI7Aux1 TempTemperatureRead
AI8Aux2 TempTemperatureRead
AI9Aux3 TempTemperatureRead
AI10Aux4 TempTemperatureRead
AI11Aux5 TempTemperatureRead
AI12Flame signal 1Read
AI13Flame signal 2Read
AI14Analogue input 1Read
AI15Analogue input 2Read
AI16Analogue input 3Read
AI17Analogue input 4Read
AI20Current demand sourceRead
AI23Analogue output 1Read
AI24Analogue output 2Read
AI25Analogue output 3Read
AI26Analogue output 4Read
AI27Fan1 SpeedRead
AI28Fan2SpeedRead
AI29Blower 1 speedRead
AI30Blower 2 speedRead
AI31HSI1 currentRead
AI32HSI2 currentRead
AI33Burner 1 power rating%Read
AI34Burner 2 power rating%Read
AImin35Lockout CodeRead
AI36Blocking CodeRead
AI38DHW Call for Heat / 10Count divided by 10Read
AI39CH1 Call For Heat / 10Count divided by 10Read
AI40CH2 Call For Heat / 10Count divided by 10Read
AI41CH3 Call For Heat / 10Count divided by 10Read
AI42CH4 Call For Heat / 10Count divided by 10Read
AI43Cascade Call For Heat / 10Count divided by 10Read
AI44Valve 1 Stage1 Cycles / 10Count divided by 10Read
AI45Valve 2 Stage1 Cycles / 10Count divided by 10Read
AI46Valve 1 Stage2 Cycles / 10Count divided by 10Read
AI47Valve 2 Stage2 Cycles / 10Count divided by 10Read
AI48Boiler pump cycles / 10Count divided by 10Read
AI49DHW pump Cycles / 10Count divided by 10Read
AI50System pump Cycles / 10Count divided by 10Read
AI51Average outlet tempTemperatureRead
AI52Max outlet tempTemperatureRead
AI53Min outlet tempTemperatureRead
AI54Average firing timehRead
AI55Max firing timehRead
AI56Min firing timehRead
AI64Modulation probeRead
AI65Activate serviceRead
AI66Slave 1 stateRead
AI67Slave 1 firing rateRead
AI68Slave 2 stateRead
AI69Slave 2 firing rateRead
AI70Slave 3 stateRead
AI71Slave 3 firing rateRead
AI72Slave 4 stateRead
AI73Slave 4 firing rateRead
AI74Slave 5 stateRead
AI75Slave 5 firing rateRead
AI76Slave 6 stateRead
AI77Slave 6 firing rateRead
AI78Slave 7 stateRead
AI79Slave 7 firing rateRead
AI80Master stateRead
AI81Master firing rateRead
AI83Active CH setpointRead
AImin84Burner 1 statusRead
AI85Burner 2 statusRead
AI89Boiler pump statusRead
AI90Master demandRead
AI91Burner 1 run timehRead
AI92Burner 2 run timehRead
AVmin0CH1 enable/disableWrite
AVmin1CH1 setpointTemperatureWrite
AV2CH1 PWrite
AV3CH1 IWrite
AV4CH1 DWrite
AV5CH2 enable/disableWrite
AV6CH2 setpointTemperatureWrite
AV7CH2 PWrite
AV8CH2 IWrite
AV9CH2 DWrite
AV10CH3 enable/disableWrite
AV11CH3 setpointTemperatureWrite
AV12CH3 PWrite
AV13CH3 IWrite
AV14CH3 DWrite
AV15CH4 enable/disableWrite
AV16CH4 setpointTemperatureWrite
AV17CH4 PWrite
AV18CH4 IWrite
AV19CH4 DWrite
AV20DHW enable/disableWrite
AV21DHW setpointTemperatureWrite
AV22DHW PWrite
AV23DHW IWrite
AV24DHW DWrite
AV25DHW recirculation enableWrite
AV26DHW recirculation Set pointTemperatureWrite
AVmin27Cascade setpointTemperatureWrite
AV28Cascade PWrite
AV29Cascade IWrite
AV30Cascade DWrite
AV35Hybrid setpointTemperatureWrite
AV36Hybrid differential tempTemperatureWrite
AV37VariPrime PWrite
AV38VariPrime IWrite
AV39VariPrime DWrite
AV40VariPrime delta TTemperatureWrite
AV41AntiCondens EnableWrite
AV42AntiCondens TempTemperatureWrite
AV43AntiCondens PWrite
AV44AntiCondens IWrite
AV45AntiCondens DWrite
BI1800Flow SwitchRead
BI1801Low Water Cut OffRead
BI1802Man Reset High LimitRead
BI1803Pressure SwitchRead
BI1804High Gas Pressure SwitchRead
BI1805Low Gas Pressure SwitchRead
BI1806Field Interlock SwitchRead
BI1807Spare Safety Chain SwitchRead
BI1900Damper Interlock SwitchRead
BI1901Spare1 SwitchRead
BImin2100Boiler Run ContactRead
BImin2101Alarm ContactRead
BI2102DHW PumpRead
BI2103System PumpRead
BI2104Louver ContactRead
BI2105Spare1 ContactRead
BI2106Spare2 ContactRead
BI2107Boiler PumpRead
BI2108Spare OutputRead
BI2200Pilot Valve Stage 1Read
BI2201Valve 1 Stage 1Read
BI2202Valve 2 Stage 1Read
BI2203Pilot valve stage 2Read
BI2204Valve 1 Stage 2Read
BI2205Valve 2 Stage 2Read
BV0DHW demandWrite
BVmin1CH1 demandWrite
BV2CH2 demandWrite
BV3CH3 demandWrite
BV4CH4 demandWrite
BV5Parameters enableWrite

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Multiburner control - ProtoNode and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Laars Multiburner control - ProtoNode

How many BACnet points does the Laars Multiburner control - ProtoNode have?

This list has 149 BACnet objects: 76 analog inputs, 42 analog values, 25 binary inputs, 6 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Laars Multiburner control - ProtoNode BACnet points are writable?

48 of the 149 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Laars Multiburner control - ProtoNode BACnet documentation?

The source is Vendor Protocol Mapping (LAARS Vendor Mappings for the ProtoNode FPC-N34 / FPC-N35) (4404), revision Document Revision 14.B, October 2020, published free by Laars at https://www.laars.com/uploads/products/4404.pdf.

What are the minimum BACnet points to integrate the Laars Multiburner control - ProtoNode?

Start with AV 0 CH1 enable/disable (CH1 heating circuit enable); BV 1 CH1 demand (CH1 call for heat); AV 1 CH1 setpoint (CH1 water setpoint); AV 27 Cascade setpoint (Setpoint when boilers run in cascade); BI 2100 Boiler Run Contact (Boiler run output); AI 84 Burner 1 status (Burner 1 state code); AI 1 Outlet Temp (Outlet water temperature); BI 2101 Alarm Contact (Alarm output); AI 35 Lockout Code (Lockout reason code).

How do I enable BMS control of the Laars Multiburner control - ProtoNode?

AV 0 CH1 enable/disable enables the CH1 circuit and BV 1 CH1 demand is its call for heat; the mapping gives no values for either. CH2-CH4 and DHW have matching enable, setpoint and demand objects.

How do I check these points on the real Multiburner control - ProtoNode?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Laars BACnet points lists