Boiler controller gateway · BACnet points list

Laars OmniTherm - ProtoNode BACnet points list

Updated 28 October 2026

Short answer

The ProtoNode reads the OmniTherm control over Modbus RTU and serves 121 objects per unit. Analog inputs cover temperatures, flame signal, 0-10 V inputs and outputs, firing rate, lockout and alarm codes, burner status, history counters and cascade lead/lag states; binary inputs break out the safety chain and output bits. Writable AVs and BVs hold the CH1, CH2, DHW and cascade enables, set points and PID terms plus three demand switches.

This page lists 121 BACnet objects for the Laars OmniTherm - ProtoNode — 28 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Laars’s own free documentation, linked below.

Manufacturer
Laars
Model
OmniTherm - ProtoNode
Equipment
Boiler controller gateway
Equipment type
Boilers & water heaters
BACnet objects
121 (28 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Default device instance
50000 + device Node-ID
Also known as
OmniTherm, Laars OmniTherm, ProtoNode FPC-N34, ProtoNode FPC-N35, FPC-N34-0701, Laars ProtoNode
Source document
Vendor Protocol Mapping (LAARS Vendor Mappings for the ProtoNode FPC-N34 / FPC-N35) · 4404 · rev. Document Revision 14.B, October 2020
Download CSV 121 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Laars OmniTherm - ProtoNode

Integration in brief

Enable CH1 with AV 0, set BV 1 CH 1 Demand switch for a call for heat and write the CH1 set point (or the cascade CH set point for a cascade). Read the run contact, Burner Status 2, outlet temperature and firing rate, and watch the alarm contact and lockout code.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AV 0CH1 Enable/DisableCH1 enable (1 = enable)Write
BV 1CH 1 Demand switchCH1 call for heat (1 = heat demand)Write
AV 1CH1 Set PointCH1 water set pointWrite
AV 27Cascade CH Set PointSet point when units run in cascadeWrite
BI 11Digital Output Status - Run contactRun outputRead
AI 85Burner Status 2Burner state; 51 = firing, 1 = locked outRead
AI 1Outlet sensorOutlet water temperatureRead
AI 33Modulating Burner1 Firing rateBurner 1 firing rateRead
BI 12Digital Output Status - Alarm ContactAlarm outputRead
AI 35Lockout codeLockout code (0-29)Read

Enable & remote start

AV 0 CH1 Enable/Disable (0 = disable, 1 = enable) and BV 1 CH 1 Demand switch (0 = no heat demand, 1 = heat demand). CH2 and DHW have matching objects.

Network setup

Watch out for

Laars OmniTherm - ProtoNode BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

121 of 121 shown
Type
Access
Show
Laars OmniTherm - ProtoNode BACnet Points List
DescriptionStates
AI0Inlet sensorRead
AImin1Outlet sensorRead
AI2Stack sensorRead
AI3DHW sensorRead
AI4System Inlet SensorRead
AI5System Outlet SensorRead
AI6Outdoor SensorRead
AI12Flame Signal 1Read
AI140-10VDC (4-20mA) Input for BASRead
AI150-10VDC (4-20mA) Input for PumpRead
AI160-10VDC (4-20mA) Input for Mixing ValveRead
AI170-10VDC (4-20mA) Input for AuxiliaryRead
AI20Demand sourceRead0=None, 1=Anti-Short Cycle, 2=Service, 3=DHW, 4=Cascade, 5=External, 6=CH1, 7=CH2, 8=CH3, 9=CH4, 10=Anti-Frost, 11=Warm weather shutdown
AI230-10VDC (4-20mA) Output for Pump SpeedRead
AI240-10VDC (4-20mA) Output for Fan SpeedRead
AI250-10VDC (4-20mA) Output for Mixing ValveRead
AI260-10VDC (4-20mA) Output for Auxiliary 1Read
AI27Modulating Fan 1 - SpeedRead
AImin33Modulating Burner1 Firing rateRead
AImin35Lockout codeRead0=Low Flow Error, 1=Low Water Cut Off Error, 2=Manual Reset High Limit Error, 3=Blocked Flue Error, 4=High Gas Pressure Error, 5=Low Gas Pressure Error, 6=Auto Reset High Limit Error, 7=Spare Safety Chain Error, 8=Outlet Probe Error, 9=Outlet Probe Drift Error, 10=Outlet Probe High Limit Error, 11=Flue Probe Error, 12=Condensing Shutdown Error, 13=Flue Probe Drift Error, 14=Flue Probe High Limit Error, 15=Inlet Probe Error, 16=Delta T Error, 17=Generic Lockout, 18=Burner1 APS Switch Error, 19=Burner2 APS Switch Error, 20=Burner1 HSI Flame Error, 21=Burner2 HSI Flame Error, 22=Burner1 Max Trials Error, 23=Burner2 Max Trials Error, 24=Burner1 Max Flame Lost Error, 25=Burner2 Max Flame Lost Error, 26=Burner1 Proven HSI Error, 27=Burner2 Proven HSI Error, 28=Burner1 Fan Speed Error, 29=Burner2 Fan Speed Error
AI36Alarm reasonRead30=24VDC Error, 31=24VAC Error, 32=DHW Probe Error, 33=System Supply Probe Error, 34=System Return Probe Error, 35=Outdoor Probe Error, 36=Spare1 Probe Error, 37=Spare2 Probe Error, 38=Spare3 Probe Error, 39=Spare4 Probe Error, 40=Spare5 Probe Error, 41=High Limit Auto Error, 42=High Delta T Error, 43=Fan Speed Error, 44=Condensing Alarm
AI37Hold codeRead
AI38History - DHW Demand CyclesRead
AI39History - CH1 Demand CyclesRead
AI40History - CH2 Demand CyclesRead
AI43History - Cascade Demand CyclesRead
AI44History - Burner Stage 1 CyclesRead
AI48History - Boiler Pump CyclesRead
AI49History - DHW Pump CyclesRead
AI50History - System Pump CyclesRead
AI51History - Average Boiler Outlet TemperatureRead
AI52History - Maximum Boiler Outlet TemperatureRead
AI53History - Minimum Boiler Outlet TemperatureRead
AI54History - Boiler Average Firing TemperatureRead
AI55History - Boiler Maximum Firing TimeRead
AI56History - Boiler Minimum Firing TimeRead
AI57Controller Cycle CountRead
AI58Controller run timeRead
AI59Lead Lag (Cascade) lead statusRead
AI60Lead Lag (Cascade) lag statusRead
AI61Lead Lag (Cascade) lead Setpoint SourceRead
AI62Lead Lag (Cascade) lead Pump DemandRead
AI63Lead Lag (Cascade) setpointRead
AI64Lead Lag (Cascade) modulation sensorRead
AI65Lead Lag (Cascade) active serviceRead
AI66Lag 1 StateRead0=Lag is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AI67Lag 1 Firing RateFiring rate, 0-100 %%Read
AI68Lag 2 StateRead0=Lag is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AI69Lag 2 Firing RateFiring rate, 0-100 %%Read
AI70Lag 3 StateRead0=Lag is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AI71Lag 3 Firing RateFiring rate, 0-100 %%Read
AI72Lag 4 StateRead0=Lag is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AI73Lag 4 Firing RateFiring rate, 0-100 %%Read
AI74Lag 5 StateRead0=Slave is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AI75Lag 5 Firing RateFiring rate, 0-100 %%Read
AI76Lag 6 StateRead0=Lag is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AI77Lag 6 Firing RateFiring rate, 0-100 %%Read
AI78Lag 7 StateRead0=Lag is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AI79Lag 7 Firing RateFiring rate, 0-100 %%Read
AI80Lead 0 StateRead0=Lead is unknown, 1=Available, 2=Add stage, 3=Suspend stage, 4=Firing, 5=On leave, 6=Disabled, 7=Recovering
AI81Lead 0 Firing RateFiring rate, 0-100 %%Read
AI82Lead Firing RateFiring rate, 0-100 %%Read
AI83Active CH SetpointRead
AI84Burner Status 1Read0=None, 5=Start, 24=Error Block, 160=Standby, 165=Check Safety Swtich, 166=Run, 177=Prepurge Open, 181=Parameter Block, 183=Lockout, 188=Testmode, 194=Prepurge Closed, 195=Wait for HIS Free, 196=HIS Preheat/Prespark, 200=Verify Primary SF, 217=interpurge, 241=Postpurge, 245=Trial for Ignition, 250=Trial for Ignition Main, 52=Post Purge
AImin85Burner Status 2Read0=Disabled, 1=Locked out, 2-3=Reserved, 4=Anti-short cycle, 34=Standby Hold, 35=Standby Delay, 48=Normal Standby, 49=Preparing, 50=Ignition, 51=Firing, 52=Post Purge
AI86CH Set Point SourceRead0=no CH source, 1=CH1, 2=CH2, 3=CH3, 4=CH4, 5=External Demand
AI87CH Requested RateRead
AI88DHW Requested RateRead
AI89Boiler Pump StatusRead
AI90Cascade Master Heat DemandRead
AI91Burner 1 Run TimeRead
AI92Burner 2 Run TimeRead
AVmin0CH1 Enable/DisableWrite0=Disable, 1=Enable
AVmin1CH1 Set PointWrite
AV2CH1 PWrite
AV3CH1 IWrite
AV4CH1 DWrite
AV5CH2 Enable/DisableWrite0=Disable, 1=Enable
AV6CH2 Set PointWrite
AV7CH2 PWrite
AV8CH2 IWrite
AV9CH2 DWrite
AV20DHW Enable/DisableWrite0=Disable, 1=Enable
AV21DHW Set PointWrite
AV22DHW PWrite
AV23DHW IWrite
AV24DHW DWrite
AVmin27Cascade CH Set PointWrite
AV28Cascade CH PWrite
AV29Cascade CH IWrite
AV30Cascade CH DWrite
AV35Hybrid Set PointWrite
AV36Hybrid Differential TemperatureWrite
AV37Vari-Prime P - Proportional TermWrite
AV38Vari-Prime I - Integral TermWrite
AV39Vari-Prime D - Derivative TermWrite
AV40Vari-Prime Delta TWrite
BI1Safety Chain Status - Flow SwitchModbus register 18 bit 0Read
BI2Safety Chain Status - LWCOModbus register 18 bit 1Read
BI3Safety Chain Status - MRHLModbus register 18 bit 2Read
BI4Safety Chain Status - Blocked FlueModbus register 18 bit 3Read
BI5Safety Chain Status - High Gas PressureModbus register 18 bit 4Read
BI6Safety Chain Status - Low Gas PressureModbus register 18 bit 5Read
BI7Safety Chain Status - Field InterlockModbus register 18 bit 6Read
BI8Safety Chain Status - ARHLModbus register 18 bit 7Read
BI9Non-safety Chain Status - Field Input 1Modbus register 19 bit 0Read
BI10Non-safety Chain Status - Field Input 2Modbus register 19 bit 1Read
BImin11Digital Output Status - Run contactModbus register 21 bit 0Read
BImin12Digital Output Status - Alarm ContactModbus register 21 bit 1Read
BI13Digital Output Status - DHW PumpModbus register 21 bit 2Read
BI14Digital Output Status - System PumpModbus register 21 bit 3Read
BI15Digital Output Status - Louver contactModbus register 21 bit 4Read
BI16Digital Output Status - Aux dry contact 1Modbus register 21 bit 5Read
BI17Digital Output Status - Aux dry contact 2Modbus register 21 bit 6Read
BI18Digital Output Status - Boiler pumpModbus register 21 bit 7Read
BI19Digital Output Status - Aux powered contactModbus register 21 bit 8Read
BI20Gas and Pilot Valve Status - Burner 1 Pilot Gas valveModbus register 22 bit 0Read
BI21Gas and Pilot Valve Status - Burner 1 Gas valve 1Modbus register 22 bit 1Read
BV0DHW Demand switchWrite0=No Heat Demand, 1=Heat Demand
BVmin1CH 1 Demand switchWrite0=No Heat Demand, 1=Heat Demand
BV2CH 2 Demand switchWrite0=No Heat Demand, 1=Heat Demand

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the OmniTherm - ProtoNode and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Laars OmniTherm - ProtoNode

How many BACnet points does the Laars OmniTherm - ProtoNode have?

This list has 121 BACnet objects: 72 analog inputs, 25 analog values, 21 binary inputs, 3 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Laars OmniTherm - ProtoNode BACnet points are writable?

28 of the 121 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Laars OmniTherm - ProtoNode BACnet documentation?

The source is Vendor Protocol Mapping (LAARS Vendor Mappings for the ProtoNode FPC-N34 / FPC-N35) (4404), revision Document Revision 14.B, October 2020, published free by Laars at https://www.laars.com/uploads/products/4404.pdf.

What are the minimum BACnet points to integrate the Laars OmniTherm - ProtoNode?

Start with AV 0 CH1 Enable/Disable (CH1 enable (1 = enable)); BV 1 CH 1 Demand switch (CH1 call for heat (1 = heat demand)); AV 1 CH1 Set Point (CH1 water set point); AV 27 Cascade CH Set Point (Set point when units run in cascade); BI 11 Digital Output Status - Run contact (Run output); AI 85 Burner Status 2 (Burner state; 51 = firing, 1 = locked out); AI 1 Outlet sensor (Outlet water temperature); AI 33 Modulating Burner1 Firing rate (Burner 1 firing rate); BI 12 Digital Output Status - Alarm Contact (Alarm output); AI 35 Lockout code (Lockout code (0-29)).

How do I enable BMS control of the Laars OmniTherm - ProtoNode?

AV 0 CH1 Enable/Disable (0 = disable, 1 = enable) and BV 1 CH 1 Demand switch (0 = no heat demand, 1 = heat demand). CH2 and DHW have matching objects.

How do I check these points on the real OmniTherm - ProtoNode?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Laars BACnet points lists

Source: Vendor Protocol Mapping (LAARS Vendor Mappings for the ProtoNode FPC-N34 / FPC-N35) · 4404 · rev. Document Revision 14.B, October 2020. Object names, instances and units are reproduced as published; descriptions are our own.