Infinitum Aircore EC+ BACnet MS/TP module BACnet points list

Updated 6 November 2026

Short answer

Aircore EC+ motors get BACnet MS/TP from a BTL-certified plug-in module on the motor's CIM (communication interface module) board. Each Modbus-style register is mirrored as one BACnet object: binary and analog outputs for run/stop, direction, speed command, operating limits, control-source and terminal settings, and analog and binary inputs for bus voltage and current, temperatures, actual speed and run state, I/O states, fault and warning words, motor identity, firmware and run-time counters.

This page lists 125 BACnet objects for the Infinitum Aircore EC+ BACnet MS/TP module — 52 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Infinitum’s own free documentation, linked below.

Manufacturer
Infinitum
Model
Aircore EC+ BACnet MS/TP module
Equipment
EC motor with integrated variable frequency drive
Equipment type
VFDs & pumps
BACnet objects
125 (52 writable)
Transport
BACnet MS/TP
Firmware
Not stated
Also known as
Aircore EC+, Aircore EC Plus, Infinitum Aircore, Infinitum BACnet module, AE catalog option B
Source document
Aircore EC+ BACnet User Manual · BACnet Version 1.4, Release Gen4 · rev. October 2025
Download CSV 125 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Infinitum’s current documentation and the live device before use. Not official Infinitum information. Terms of use.

BMS integration notes: Infinitum Aircore EC+ BACnet MS/TP module

Integration in brief

Set each motor's device instance and baud rate with Infinitum's NPU tool over the CIM board's micro-USB port, terminate the bus ends with the on-board DIP switch, then command BO 1 run/stop and AO 3 speed command. Read BI 74, AI 76, AI 63 and BI 86/AI 90, and clear faults with BO 88.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 1Run/Stop CmdRun/stop commandCommand
AO 3Speed CommandSpeed command from the BMSCommand
BO 88Clear FaultsClears active faultsCommand
BI 74Run/Stop ActualActual run stateRead
AI 76Speed ActualActual motor speedRead
AI 63Avg CurrentAverage motor currentRead
BI 86Active FaultsAny active faultRead
AI 90Fault WordBit-coded fault wordRead

Enable & remote start

The list includes source selectors for speed (AO 21 Speed Source), run/stop (AO 22 Run/Stop Source), direction (AO 23) and fault clearing (AO 24); this manual doesn't give their values, so set them per the Aircore EC+ IOM manual before commanding over BACnet MS/TP.

Network setup

Watch out for

Infinitum Aircore EC+ BACnet MS/TP module BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

125 of 125 shown
Type
Access
Show
Infinitum Aircore EC+ BACnet MS/TP module BACnet Points List
DescriptionStates
AI15Max Accel AllowMax Acceleration (register 1112)Read
AI16Max Decel AllowMax Deceleration (register 1113)Read
AI25dummy1Start Function (register 1206)Read
AI26dummy2Stop Function (register 1207)Read
AI35dummy3AI1 Filter (register 2004)Read
AI36dummy4AI1 Fault Action (register 2005)Read
AI44DI1 FunctionDI1 Function (register 2101)Read
AI45DI2 FunctionDI2 Function (register 2102)Read
AI46DI3 FunctionDI3 Function (register 2103)Read
AI47DI4 FunctionDI4 Function (register 2104)Read
AI60DC Bus VoltageDC Bus Voltage (register 3001)Read
AI61DC Bus CurrentDC Bus Current (register 3002)Read
AI62DC Bus PowerDC Bus Power (register 3003)Read
AImin63Avg CurrentAverage Current (register 3004)Read
AI64Inp RMS CurrentInput RMS current (register 3005)Read
AI65Inp RMS VoltageInput RMS voltage (register 3006)Read
AI66Temp RTDStator (RTD) (register 3101)Read
AI67Temp AverageStator Average (register 3102)Read
AI68Temp HeatsinkT3 HeatSink (register 3103)Read
AI69Temp NTC1T2 Stator NTC1 (register 3104)Read
AI70Temp INV BoardINV Board Temp (register 3105)Read
AI71Spare1T1 INV J7 (spare) (register 3106)Read
AI72Temp NTC2T4 Stator NTC2 (register 3107)Read
AI73Temp CIMT14 CIM Board temp (register 3114)Read
AImin76Speed ActualSpeed_krpm (register 3303)Read
AI77AI1 ValueAIN1 (register 3501)Read
AI78AI1 RawAIN1 Raw (register 3502)Read
AI79AO1 ValueAOUT1 (register 3601)Read
AImin90Fault WordFault Word (register 4011)Read
AI91Warning WordWarning Word (register 4021)Read
AI92Parameter TableParameter Table Version (register 7001)Read
AI93Motor Max Ampsmax current (register 7002)Read
AI94Motor VoltageMotor Voltage (register 7003)Read
AI95Motor SN 1New SN1 (register 7004)Read
AI96Motor SN 2New SN2 (register 7005)Read
AI97Motor SN 3New SN3 (register 7006)Read
AI98Motor SN 4New SN4 (register 7007)Read
AI99Motor SN 5New SN5 (register 7008)Read
AI100Motor SN 6New SN6 (register 7009)Read
AI101Motor SN 7New SN7 (register 7010)Read
AI102Motor SN 8Old SN1 (register 7011)Read
AI103Motor SN 9Old SN2 (register 7012)Read
AI104Motor SN 10Old SN3 (register 7013)Read
AI105Motor SN 11Old SN4 (register 7014)Read
AI106Motor ModelModel (register 7021)Read
AI107Motor rated RPMMotor rated speed (register 7022)Read
AI108INV FW MajorINV FW Major (register 7031)Read
AI109INV FW MinorINV FW Minor (register 7032)Read
AI110CIM FW MajorCIM FW Major (register 7033)Read
AI111CIM FW MinorCIM FW Minor (register 7034)Read
AI112Motor TypeMotor Type (register 7035)Read
AI113Hardware IDHardware ID (register 7036)Read
AI114INV FW PatchINV FW Patch (register 7037)Read
AI115CIM FW PatchCIM FW Patch (register 7038)Read
AI116Hardware ID INVHardware ID INV (register 7039)Read
AI117Hardware ID VFDHardware ID VFD (register 7040)Read
AI118Hardware ID CIMHardware ID CIM (register 7041)Read
AI119HorsepowerHorsepower (register 7042)Read
AI120Frame SizeFrame Size (register 7043)Read
AI121Stator TypeStator type (register 7044)Read
AI122Drive RuntimeDrive Runtime hours (register 7101)Read
AI123Motor RuntimeMotor Runtime hours (register 7102)Read
AI124Motor MWhMotor Energy megawatt-hours (register 7103)Read
AOmin3Speed CommandSW Speed (register 1003)Command
AO4Speed User MinSpeed User Minimum (register 1101)Command
AO5Speed User MaxSpeed User Maximum (register 1102)Command
AO6Speed Abs MinSpeed Absolute Minimum (register 1103)Command
AO7Speed Abs MaxSpeed Absolute Maximum (register 1104)Command
AO8Accel Ramp TimeAcceleration Ramp Duration (register 1105)Command
AO9Decel Ramp TimeDeceleration Ramp Duration (register 1106)Command
AO10Skip Speed 1Skip Speed 1 Min (register 1107)Command
AO11Skip Speed 2Skip Speed 1 Max (register 1108)Command
AO12Skip Speed 3Skip Speed 2 Min (register 1109)Command
AO13Skip Speed BWSkip Speed 2 Max (register 1110)Command
AO14Dir AllowedDirection Allowed (register 1111)Command
AO17Speed Model MinSpeed Model Minimum (register 1114)Command
AO18Speed Model MaxSpeed Model Maximum (register 1115)Command
AO19Load InertiaLoad Inertia (register 1116)Command
AO20Control ModeControl Mode (register 1201)Command
AO21Speed SourceSpeed Input Source (register 1202)Command
AO22Run/Stop SourceStart/Stop Input Source (register 1203)Command
AO23Dir SourceDirection Input Source (register 1204)Command
AO24Clr Flt SourceClear Fault Input Source (register 1205)Command
AO27Enable FoldbackEnable Foldback (register 1208)Command
AO28Disable SourceInterlock Input Source (register 1209)Command
AO29Override SourceOverride Input Source (register 1210)Command
AO30Reset AttemptsReset Attempts (register 1301)Command
AO31Reset DelayReset Delay (register 1302)Command
AO32AI1 FunctionAI1 Function (register 2001)Command
AO33AI1 Min SettingAI1 Minimum Setting (register 2002)Command
AO34AI1 Max SettingAI1 Maximum Setting (register 2003)Command
AO38AI1 Open Max VAI1 Open Max V (register 2010)Command
AO39AI1 Open RPMAI1 Open Speed RPM (register 2011)Command
AO40AI1 Stop Min VAI1 Stop Min V (register 2012)Command
AO41AI1 Stop Max VAI1 Stop Max V (register 2013)Command
AO43A1 FailOv ToutAI1 FailOver Timeout (register 2015)Command
AO48Const Speed 1Constant Speed 1 (register 2201)Command
AO49Const Speed 2Constant Speed 2 (register 2202)Command
AO50Const Speed 3Constant Speed 3 (register 2203)Command
AO51Const Speed 4Constant Speed 4 (register 2204)Command
AO52Override SpeedOverride Speed (register 2205)Command
AO53AO1 FunctionAO1 Function (register 2301)Command
AO54AO1 Scaling MinAO1 Scaling Minimum (register 2302)Command
AO55AO1 Scaling MaxAO1 Scaling Maximum (register 2303)Command
AO56AO1 FilterAO1 Filter (register 2304)Command
AO58DO1 FunctionDO1 Function (register 2401)Command
AO59DO2 FunctionDO2 Function (register 2402)Command
AO125Parameter SaveParameter Save (register 8701)Command
BImin74Run/Stop ActualRun/Stop Actual (register 3301)Read
BI75Dir ActualDirection Actual (register 3302)Read
BI80DI1 ValueDIN1 (register 3701)Read
BI81DI2 ValueDIN2 (register 3702)Read
BI82DI3 ValueDIN3 (register 3703)Read
BI83DI4 ValueDIN4 (register 3704)Read
BI84DO1 ValueDOUT1 (register 3801)Read
BI85DO2 ValueDOUT2 (register 3802)Read
BImin86Active FaultsActive Faults (register 4001)Read
BI87Active WarningsActive Warnings (register 4002)Read
BOmin1Run/Stop CmdSW Run/Stop (register 1001)Command
BO2Direction CmdSW Direction (register 1002)Command
BO37AI1 Type SelectAI1 Type Selection (register 2006)Command
BO42AI1 FailOv StopAI1 FailOver Stop (register 2014)Command
BO57AO1 TypeAO1 Type (register 2305)Command
BOmin88Clear FaultsClear Faults (register 4003)Command
BO89Clear WarningsClear Warnings (register 4004)Command
Object ID lookup: Infinitum Aircore EC+ BACnet MS/TP module point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the Aircore EC+ BACnet MS/TP module and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Infinitum Aircore EC+ BACnet MS/TP module

How many BACnet points does the Infinitum Aircore EC+ BACnet MS/TP module have?

This list has 125 BACnet objects: 63 analog inputs, 45 analog outputs, 10 binary inputs, 7 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Infinitum Aircore EC+ BACnet MS/TP module BACnet points are writable?

52 of the 125 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Infinitum Aircore EC+ BACnet MS/TP module BACnet documentation?

The source is Aircore EC+ BACnet User Manual (BACnet Version 1.4, Release Gen4), revision October 2025, published free by Infinitum at https://support.goinfinitum.com/hc/en-us/article_attachments/52467145317907.

What are the minimum BACnet points to integrate the Infinitum Aircore EC+ BACnet MS/TP module?

Start with BO 1 Run/Stop Cmd (Run/stop command); AO 3 Speed Command (Speed command from the BMS); BO 88 Clear Faults (Clears active faults); BI 74 Run/Stop Actual (Actual run state); AI 76 Speed Actual (Actual motor speed); AI 63 Avg Current (Average motor current); BI 86 Active Faults (Any active fault); AI 90 Fault Word (Bit-coded fault word).

How do I enable BMS control of the Infinitum Aircore EC+ BACnet MS/TP module?

The list includes source selectors for speed (AO 21 Speed Source), run/stop (AO 22 Run/Stop Source), direction (AO 23) and fault clearing (AO 24); this manual doesn't give their values, so set them per the Aircore EC+ IOM manual before commanding over BACnet MS/TP.

How do I check these points on the real Aircore EC+ BACnet MS/TP module?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

Source: Aircore EC+ BACnet User Manual · BACnet Version 1.4, Release Gen4 · rev. October 2025. Object names, instances and units are reproduced as published; descriptions are our own.