Split AC BACnet gateway · BACnet points list

Gree GMS BACnet Converter (GMS GW) - R series BACnet points list

Updated 28 October 2026

Short answer

The GMS GW is a Gree-branded gateway (built by CoolAutomation) that links up to 1 or 12 Gree split indoor units over two RS-485 lines to BACnet/IP or BACnet MS/TP. Every unit gets a common object set (on/off, mode, fan, setpoint, room temperature, locks) plus series-specific objects; this file is the common set plus the R-series extras.

This page lists 32 BACnet objects for the Gree GMS BACnet Converter (GMS GW) - R series — 21 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Gree’s own free documentation, linked below.

Manufacturer
Gree
Model
GMS BACnet Converter (GMS GW) - R series
Equipment
Split AC BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
32 (21 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
GMS GW 1, GMS GW 12, GMVGMSGW, Gree Mini Split BACnet Converter, CoolAutomation Gree gateway
Source document
Gree Mini Split (GMS) BACnet Converter User Manual · 1.1 · rev. 2023-12-11 (Version 1.1)
Download CSV 32 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Gree GMS BACnet Converter (GMS GW) - R series

Integration in brief

Address each split unit from its wired controller, pick BACnet/IP or MS/TP, set a unique device instance from the LCD menu, then map each unit's object block using the instance formula. On/off, mode, fan and setpoint are writable value objects; room temperature and failure status are read-only.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 256ON/OFFStart/stop the split unitWrite
MV 257Operation ModeCool/heat/auto/dry/fanWrite
AV 256SetPoint TemperatureRoom temperature setpoint, °C/°FWrite
MV 256Fan SpeedLow / medium / high / auto (plus extra speeds)Write
AI 256Room TemperatureRoom temperature, °C/°FRead
BI 256split unit Failure StatusFailure flag; Active_Text carries the codeRead

Enable & remote start

No enable point; a unit is controllable once it has a unique remote control address on line L1 or L2. BV 'Global Lock' and the two Lock BVs stop local wired-controller changes.

Network setup

Watch out for

Gree GMS BACnet Converter (GMS GW) - R series BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

32 of 32 shown
Type
Multi-stateOther
Access
Show
Gree GMS BACnet Converter (GMS GW) - R series BACnet Points List
DescriptionStates
BImin256split unit Failure StatusUnit failure; Active_Text holds the failure codeRead0=No Failure, 1=Failure
BVmin256ON/OFFUnit on/offWrite0=Off, 1=On
BV258Lock (prohibit) ON/OFF change from Wired ControllerLock on/off at the wired controllerWrite
BV259Lock (prohibit) Operation Mode change from Wired ControllerLock mode change at the wired controllerWrite
BV261Global LockLock all wired-controller changesWrite
AImin256Room TemperatureRoom temperature°C/°FRead
AVmin256SetPoint TemperatureTemperature setpoint°C/°FWrite
MVmin256Fan SpeedFan speedWrite0=Low, 1=Medium, 2=High, 3=Auto, 4=Top, 5=Very Low, 6=Super High
MVmin257Operation ModeOperating modeWrite0=Cool, 1=Heat, 2=Auto, 3=Dry, 5=Fan
MV258Louver Position (swing)Louver swingWrite5=Auto (swing), 6=OFF (stop)
BI1048845DefrostingDefrost activeRead
BI1048846ODU Fan StateOutdoor fan stateRead
BI10488474-Way ValveReversing valve stateRead
BI1048848Compressor StatusCompressor runningRead
BV1048839Health FunctionHealth function on/offWrite
BV1048840I-Demand FunctionI-Demand function on/offWrite
BV1048841Dry FunctionDry function on/offWrite
BV1048842Quiet ModeQuiet mode on/offWrite
BV1048843Memory FunctionMemory function on/offWrite
BV1048844Wired Controller Temperature PresentationWired controller display unitsWrite0=Celsius, 1=Fahrenheit
BV1048849Absence FunctionAbsence function on/offWrite
BV1048850Low Temperature Dry FunctionLow temperature dry on/offWrite
BV1048851Fresh Air FunctionFresh air function on/offWrite
BV1048852Cooling Set Point Limit EnableEnable cooling setpoint limitWrite
BV1048853Heating Set Point Limit EnableEnable heating setpoint limitWrite
AV1048837Cooling Set Point LimitCooling setpoint limit°C/°FWrite
AV1048838Heating Set Point LimitHeating setpoint limit°C/°FWrite
PIV1048832IDU Type CodeIndoor unit type codeRead
PIV1048833Sleep FunctionSleep functionRead
PIV1048834Modbus AddressUnit Modbus addressRead
PIV1048835Outdoor Temperature °COutdoor temperature°CRead
PIV1048836Evaporation Temperature °CEvaporator temperature°CRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GMS BACnet Converter (GMS GW) - R series and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Gree GMS BACnet Converter (GMS GW) - R series

How many BACnet points does the Gree GMS BACnet Converter (GMS GW) - R series have?

This list has 32 BACnet objects: 1 analog input, 3 analog values, 5 binary inputs, 15 binary values, 3 multi-state values, 5 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Gree GMS BACnet Converter (GMS GW) - R series BACnet points are writable?

21 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Gree GMS BACnet Converter (GMS GW) - R series BACnet documentation?

The source is Gree Mini Split (GMS) BACnet Converter User Manual (1.1), revision 2023-12-11 (Version 1.1), published free by Gree at https://www.greecomfort.com/assets/our-products/mini-split-controls/documents/cool-automation-mini-split-controls-user-manual.pdf.

What are the minimum BACnet points to integrate the Gree GMS BACnet Converter (GMS GW) - R series?

Start with BV 256 ON/OFF (Start/stop the split unit); MV 257 Operation Mode (Cool/heat/auto/dry/fan); AV 256 SetPoint Temperature (Room temperature setpoint, °C/°F); MV 256 Fan Speed (Low / medium / high / auto (plus extra speeds)); AI 256 Room Temperature (Room temperature, °C/°F); BI 256 split unit Failure Status (Failure flag; Active_Text carries the code).

How do I enable BMS control of the Gree GMS BACnet Converter (GMS GW) - R series?

No enable point; a unit is controllable once it has a unique remote control address on line L1 or L2. BV 'Global Lock' and the two Lock BVs stop local wired-controller changes.

How do I check these points on the real GMS BACnet Converter (GMS GW) - R series?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Gree BACnet points lists

Source: Gree Mini Split (GMS) BACnet Converter User Manual · 1.1 · rev. 2023-12-11 (Version 1.1). Object names, instances and units are reproduced as published; descriptions are our own.