- Home
- BACnet points lists
- Gree
- GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI
Split AC BACnet gateway · BACnet points list
Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI BACnet points list
Updated 28 October 2026
Same Gree GMS gateway as the R-series entry, but for M/W/P/X series units on a DWUNI wired controller. The common Class 0 objects are identical; the Class 1 series-specific objects use their own numbering.
This page lists 23 BACnet objects for the Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Gree’s own free documentation, linked below.
- Manufacturer
- Gree
- Model
- GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI
- Equipment
- Split AC BACnet gateway
- Equipment type
- VRF & split air conditioners
- BACnet objects
- 23 (19 writable)
- Transport
- BACnet IP, BACnet MS/TP
- Firmware
- Not stated
- Also known as
- GMS GW 1, GMS GW 12, GMVGMSGW, DWUNI, Gree Multi BACnet
BMS integration notes: Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI
Address each split unit from its DWUNI wired controller, pick BACnet/IP or MS/TP, set a unique device instance from the LCD menu, then map each unit's object block using the instance formula. Control uses the common on/off, mode, fan and setpoint objects.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| BV 256 | ON/OFF | Start/stop the split unit | Write |
| MV 257 | Operation Mode | Cool/heat/auto/dry/fan | Write |
| AV 256 | SetPoint Temperature | Room temperature setpoint, °C/°F | Write |
| MV 256 | Fan Speed | Low / medium / high / auto (plus extra speeds) | Write |
| AI 256 | Room Temperature | Room temperature, °C/°F | Read |
| BI 256 | split unit Failure Status | Failure flag; Active_Text carries the code | Read |
Enable & remote start
No enable point; a unit is controllable once it has a unique remote control address on line L1 or L2. BV 'Global Lock' and the two Lock BVs stop local wired-controller changes.
Network setup
- Device instance is set from the gateway's LCD menu (Menu > BACnet > Instance number) and takes effect after a restart.
- The BAC A/B RS-485 port runs either BACnet MS/TP or Modbus RTU; choose BACnet in the 'Line 3' setting of the USB configuration tool.
- BACnet/IP runs on the Ethernet port; network settings are changed with the ifconfig command in the gateway terminal.
- Set each indoor unit's remote control address (0-63) on its wired controller before mapping objects.
Watch out for
- Instances are computed from line and remote control address, so re-addressing a unit moves all of its objects.
- DWUNI units have a single Set Point Limits Enable (BV 12) instead of separate cooling/heating enables.
- Class 1 object numbers overlap with R-series objects of different meaning; don't reuse an R-series template.
Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.
| Description | States | |||||
|---|---|---|---|---|---|---|
| BImin | 256 | split unit Failure Status | Unit failure; Active_Text holds the failure code | Read | 0=No Failure, 1=Failure | |
| BVmin | 256 | ON/OFF | Unit on/off | Write | 0=Off, 1=On | |
| BV | 258 | Lock (prohibit) ON/OFF change from Wired Controller | Lock on/off at the wired controller | Write | ||
| BV | 259 | Lock (prohibit) Operation Mode change from Wired Controller | Lock mode change at the wired controller | Write | ||
| BV | 261 | Global Lock | Lock all wired-controller changes | Write | ||
| AImin | 256 | Room Temperature | Room temperature | °C/°F | Read | |
| AVmin | 256 | SetPoint Temperature | Temperature setpoint | °C/°F | Write | |
| MVmin | 256 | Fan Speed | Fan speed | Write | 0=Low, 1=Medium, 2=High, 3=Auto, 4=Top, 5=Very Low, 6=Super High | |
| MVmin | 257 | Operation Mode | Operating mode | Write | 0=Cool, 1=Heat, 2=Auto, 3=Dry, 5=Fan | |
| MV | 258 | Louver Position (swing) | Louver swing | Write | 5=Auto (swing), 6=OFF (stop) | |
| BV | 1048836 | Health Function | Health function on/off | Write | ||
| BV | 1048837 | I-Demand Function | I-Demand function on/off | Write | ||
| BV | 1048838 | Dry Function | Dry function on/off | Write | ||
| BV | 1048839 | Quiet Mode | Quiet mode on/off | Write | ||
| BV | 1048840 | Memory Function | Memory function on/off | Write | ||
| BV | 1048841 | Wired Controller Temperature Presentation | Wired controller display units | Write | 0=Celsius, 1=Fahrenheit | |
| BV | 1048842 | Absence Function | Absence function on/off | Write | ||
| BV | 1048843 | Low Temperature Dry Function | Low temperature dry on/off | Write | ||
| BV | 1048844 | Set Point Limits Enable | Enable setpoint limits | Write | ||
| AV | 1048834 | Cooling Set Point Limit | Cooling setpoint limit | °C/°F | Write | |
| AV | 1048835 | Heating Set Point Limit | Heating setpoint limit | °C/°F | Write | |
| PIV | 1048832 | Modbus Address | Unit Modbus address | Read | ||
| PIV | 1048833 | Outdoor Temperature °C | Outdoor temperature | °C | Read |
No points match these filters.
Integration notes
- Instance formula: Class x 1048576 + (Line - 1) x 131072 + remote control address x 256 + object number. Common objects are Class 0, series-specific objects Class 1. This file lists line 1, address 1 (L1.001).
- Each split unit needs a unique remote control address (0-63 per line), set from its wired controller; the gateway shows it as L<line>.<address>.
- The manual has no read/write column; access was inferred from object type (BV/AV/MV writable, BI/AI/PIV read-only).
- The gateway is made by CoolAutomation for Gree; GMS GW 1 handles one unit, GMS GW 12 up to 12 units over two RS-485 lines.
- R-series units use a different Class 1 object set (see the separate GMS GW R-series entry).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI
How many BACnet points does the Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI have?
This list has 23 BACnet objects: 1 analog input, 3 analog values, 1 binary input, 13 binary values, 3 multi-state values, 2 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI BACnet points are writable?
19 of the 23 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.
Where is the official Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI BACnet documentation?
The source is Gree Mini Split (GMS) BACnet Converter User Manual (1.1), revision 2023-12-11 (Version 1.1), published free by Gree at https://www.greecomfort.com/assets/our-products/mini-split-controls/documents/cool-automation-mini-split-controls-user-manual.pdf.
What are the minimum BACnet points to integrate the Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI?
Start with BV 256 ON/OFF (Start/stop the split unit); MV 257 Operation Mode (Cool/heat/auto/dry/fan); AV 256 SetPoint Temperature (Room temperature setpoint, °C/°F); MV 256 Fan Speed (Low / medium / high / auto (plus extra speeds)); AI 256 Room Temperature (Room temperature, °C/°F); BI 256 split unit Failure Status (Failure flag; Active_Text carries the code).
How do I enable BMS control of the Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI?
No enable point; a unit is controllable once it has a unique remote control address on line L1 or L2. BV 'Global Lock' and the two Lock BVs stop local wired-controller changes.
How do I check these points on the real GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Gree BACnet points lists
Source: Gree Mini Split (GMS) BACnet Converter User Manual · 1.1 · rev. 2023-12-11 (Version 1.1). Object names, instances and units are reproduced as published; descriptions are our own.