Easy BACnet
  1. Home
  2. BACnet points lists
  3. Gree
  4. GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI

Split AC BACnet gateway · BACnet points list

Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI BACnet points list

Updated 28 October 2026

Short answer

Same Gree GMS gateway as the R-series entry, but for M/W/P/X series units on a DWUNI wired controller. The common Class 0 objects are identical; the Class 1 series-specific objects use their own numbering.

This page lists 23 BACnet objects for the Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI — 19 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Gree’s own free documentation, linked below.

Manufacturer
Gree
Model
GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI
Equipment
Split AC BACnet gateway
Equipment type
VRF & split air conditioners
BACnet objects
23 (19 writable)
Transport
BACnet IP, BACnet MS/TP
Firmware
Not stated
Also known as
GMS GW 1, GMS GW 12, GMVGMSGW, DWUNI, Gree Multi BACnet
Source document
Gree Mini Split (GMS) BACnet Converter User Manual · 1.1 · rev. 2023-12-11 (Version 1.1)
Download CSV 23 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI

Integration in brief

Address each split unit from its DWUNI wired controller, pick BACnet/IP or MS/TP, set a unique device instance from the LCD menu, then map each unit's object block using the instance formula. Control uses the common on/off, mode, fan and setpoint objects.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 256ON/OFFStart/stop the split unitWrite
MV 257Operation ModeCool/heat/auto/dry/fanWrite
AV 256SetPoint TemperatureRoom temperature setpoint, °C/°FWrite
MV 256Fan SpeedLow / medium / high / auto (plus extra speeds)Write
AI 256Room TemperatureRoom temperature, °C/°FRead
BI 256split unit Failure StatusFailure flag; Active_Text carries the codeRead

Enable & remote start

No enable point; a unit is controllable once it has a unique remote control address on line L1 or L2. BV 'Global Lock' and the two Lock BVs stop local wired-controller changes.

Network setup

Watch out for

Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

23 of 23 shown
Type
Multi-stateOther
Access
Show
Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI BACnet Points List
DescriptionStates
BImin256split unit Failure StatusUnit failure; Active_Text holds the failure codeRead0=No Failure, 1=Failure
BVmin256ON/OFFUnit on/offWrite0=Off, 1=On
BV258Lock (prohibit) ON/OFF change from Wired ControllerLock on/off at the wired controllerWrite
BV259Lock (prohibit) Operation Mode change from Wired ControllerLock mode change at the wired controllerWrite
BV261Global LockLock all wired-controller changesWrite
AImin256Room TemperatureRoom temperature°C/°FRead
AVmin256SetPoint TemperatureTemperature setpoint°C/°FWrite
MVmin256Fan SpeedFan speedWrite0=Low, 1=Medium, 2=High, 3=Auto, 4=Top, 5=Very Low, 6=Super High
MVmin257Operation ModeOperating modeWrite0=Cool, 1=Heat, 2=Auto, 3=Dry, 5=Fan
MV258Louver Position (swing)Louver swingWrite5=Auto (swing), 6=OFF (stop)
BV1048836Health FunctionHealth function on/offWrite
BV1048837I-Demand FunctionI-Demand function on/offWrite
BV1048838Dry FunctionDry function on/offWrite
BV1048839Quiet ModeQuiet mode on/offWrite
BV1048840Memory FunctionMemory function on/offWrite
BV1048841Wired Controller Temperature PresentationWired controller display unitsWrite0=Celsius, 1=Fahrenheit
BV1048842Absence FunctionAbsence function on/offWrite
BV1048843Low Temperature Dry FunctionLow temperature dry on/offWrite
BV1048844Set Point Limits EnableEnable setpoint limitsWrite
AV1048834Cooling Set Point LimitCooling setpoint limit°C/°FWrite
AV1048835Heating Set Point LimitHeating setpoint limit°C/°FWrite
PIV1048832Modbus AddressUnit Modbus addressRead
PIV1048833Outdoor Temperature °COutdoor temperature°CRead

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI

How many BACnet points does the Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI have?

This list has 23 BACnet objects: 1 analog input, 3 analog values, 1 binary input, 13 binary values, 3 multi-state values, 2 positive integer values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI BACnet points are writable?

19 of the 23 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done. The source has no read/write column, so this is inferred from object type.

Where is the official Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI BACnet documentation?

The source is Gree Mini Split (GMS) BACnet Converter User Manual (1.1), revision 2023-12-11 (Version 1.1), published free by Gree at https://www.greecomfort.com/assets/our-products/mini-split-controls/documents/cool-automation-mini-split-controls-user-manual.pdf.

What are the minimum BACnet points to integrate the Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI?

Start with BV 256 ON/OFF (Start/stop the split unit); MV 257 Operation Mode (Cool/heat/auto/dry/fan); AV 256 SetPoint Temperature (Room temperature setpoint, °C/°F); MV 256 Fan Speed (Low / medium / high / auto (plus extra speeds)); AI 256 Room Temperature (Room temperature, °C/°F); BI 256 split unit Failure Status (Failure flag; Active_Text carries the code).

How do I enable BMS control of the Gree GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI?

No enable point; a unit is controllable once it has a unique remote control address on line L1 or L2. BV 'Global Lock' and the two Lock BVs stop local wired-controller changes.

How do I check these points on the real GMS BACnet Converter (GMS GW) - M/W/P/X series with DWUNI?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Gree BACnet points lists

Source: Gree Mini Split (GMS) BACnet Converter User Manual · 1.1 · rev. 2023-12-11 (Version 1.1). Object names, instances and units are reproduced as published; descriptions are our own.