  4. SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)

Valve actuator (PICV) · BACnet points list

FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) BACnet points list

Updated 12 November 2026

Short answer

Rotary actuators for FlowCon SM pressure-independent valves with BACnet MS/TP or Modbus. MV 6 picks the control source (voltage, mA, digital or serial bus); with serial control the BMS writes the demand to AV 4. The actuator reports position, flow, state, alarm flags and, on the SM.0.0.1.6, battery status for the power fail-safe.

This page lists 32 BACnet objects for the FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from FlowCon’s own free documentation, linked below.

Manufacturer
FlowCon
Model
SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)
Equipment
Valve actuator (PICV)
Equipment type
Valves & actuators
BACnet objects
32 (20 writable)
Transport
BACnet MS/TP
Firmware
Actuator software FL1 V206, BACnet firmware V110
Also known as
SM.0.0.1.5, SM.0.0.1.6, FlowCon SM actuator, FlowCon SM-1516
Source document
BACnet PICS for FlowCon SM.0.0.1.5/SM.0.0.1.6 · rev. 2026-07-17
Download CSV 32 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against FlowCon’s current documentation and the live device before use. Not official FlowCon information. Terms of use.

BMS integration notes: FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)

Integration in brief

Set MV 13 to BACnet and MV 6 to Serial (BUS), then write the demand to AV 4. Read AV 22 for flow, MV 2 for state and BSV 2 for alarms; PIV 30 sets how long the actuator waits before treating the bus as lost.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 6Actuator Control Signal4 = Serial (BUS) controlWrite
AV 4Actuator Control DemandControl demand, 0-100 %Write
MV 2Actuator StateOperating stateRead
AV 22Current FlowCurrent flow rateRead
AV 1Actuator PositionCurrent position, degreesRead
Other 2Actuator Alarm FlagsAlarm bitsRead

Enable & remote start

MV 13 selects the communication mode (BACnet) and MV 6 = 4 (Serial) makes the actuator follow AV 4.

Heartbeat & communication loss

PIV 30 sets the network timeout (1-60 min); BSV 2 bit 12 flags a network timeout. AV 18 sets the position on control signal loss (-1 = stay in place).

Network setup

Watch out for

FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

32 of 32 shown
Type
Multi-state
Access
Show
FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) BACnet Points List
DescriptionStates
AI2Control SignalControl signal; min./max. also set hereV or mA (per MV 6)Write
AI3Power Supply VoltagePower supply voltageVRead
AI4Battery VoltageBattery voltage (SM.0.0.1.6 fail-safe only)VRead
AO1Feedback SignalFeedback signal; span and unit per MV 7Read
AVmin1Actuator PositionCurrent position (0-2160°, SM.6.2 0-3600°)°Read
AV2Actuator Position SetpointPosition set point (0-2160°, SM.6.2 0-3600°)°Read
AVmin4Actuator Control DemandBACnet control demand, 0-100 %%Write
AV9Internal TemperatureActuator’s internal temperature°CRead
AV16Max FlowMax. flow setting; range follows valve in MV 4per MV 5Write
AV17Power Failsafe PositionPosition on power loss; -1 = in place (SM.0.0.1.6)%Write
AV18Control Signal Failsafe PositionPosition on control signal loss; -1 = in place%Write
AVmin22Current FlowCurrent flow rateper MV 5Read
BI5Digital Open SignalDigital open status inputRead0=Inactive, 1=Active
BI6Digital Close SignalDigital close status inputRead0=Inactive, 1=Active
BV1Factory Reset RequestReset actuator to factory settingsWrite0=Inactive, 1=Active
BV2Reset Error#2 RequestReset error 2 (over torque warning)Write0=Inactive, 1=Active
BV3Reset Error#7 RequestReset error 7 (lack of valve)Write0=Inactive, 1=Active
MVmin2Actuator StateActuator’s current stateRead1=Auto Stroke, 2=Standby, 3=Normal, 4=Alarm, 5=Not Active, 6=Failsafe / Failure, 7=Calibration, 8=Flushing, 9=Service Override (Service Ovrd)
MV3Actuator Rotation DirectionActuator’s rotation directionWrite1=NC, 2=NO
MV4Valve ModelValve model on which the actuator is fittedWrite1=SM.1.1, 2=SM.2.1, 3=SM.3.0, 4=SM.3.1, 5=SM.3.2, 6=SM.4.1, 7=SM.4.2, 8=SM.4.3, 9=SM.5.1, 10=SM.5.2, 11=SM.6.2, 12=SM.0.0
MV5Flow Unit ScaleFlow unitWrite1=l/sec, 2=GPM, 3=l/hr
MVmin6Actuator Control SignalActuator’s control signalWrite1=Volt, 2=mA, 3=Digital, 4=Serial (= BUS)
MV7Feedback SignalActuator’s feedback signalWrite1=2-10 Volt, 2=0-10 Volt, 3=4-20 mA, 4=AU (=automatic)
MV8Actuator ModeActuator’s control modeWrite1=LIN FLO (=linear flow), 2=EQ PCT (=equal %), 3=LIN ROT (=linear rotation)
MV12Battery StatusBattery statusRead1=None (=no battery), 2=Lost (=battery lost or loose), 3=Charge level 0 (=battery level low), 4=Charge level 1 (=battery level medium low), 5=Charge level 2 (=battery level medium high), 6=Charge level 3 (=battery level full)
MV13Actuator Communication ModeActuator’s communication modeWrite1=Disabled, 2=BACnet, 3=Modbus
Othermin2Actuator Alarm FlagsBitstring: power fail, no valve, hardware, overtorque, temp, network timeout...Read
Other3User Configuration FlagsBitstring: password, flush, 15-min fail-safe delayWrite
CSV1User Custom StringFree user textWrite
PIV22Auto-Stroke Frequency (days)Days between auto-stroke runs (default 7, 0 = off)daysWrite
PIV30Network TimeoutCommunication timeout, 1-60 minminWrite
Other1BACnet MS/TP PortNetwork Port: baud (auto or 9600-115200), MAC 1-127Write
Object ID lookup: FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)

How many BACnet points does the FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) have?

This list has 32 BACnet objects: 3 analog inputs, 1 analog output, 8 analog values, 2 binary inputs, 3 binary values, 9 multi-state values, 1 characterstring value, 2 positive integer values, 3 others. The exact set on a given unit depends on its firmware, installed options and configuration.

Which FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) BACnet points are writable?

20 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) BACnet documentation?

The source is BACnet PICS for FlowCon SM.0.0.1.5/SM.0.0.1.6, revision 2026-07-17, published free by FlowCon at https://flowcon.com/fileadmin/user_upload/Pdf/Certificates/BACnet_PICS/FlowCon-BACnet-PICS-Statement-FlowCon-SM-1516.pdf.

What are the minimum BACnet points to integrate the FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)?

Start with MV 6 Actuator Control Signal (4 = Serial (BUS) control); AV 4 Actuator Control Demand (Control demand, 0-100 %); MV 2 Actuator State (Operating state); AV 22 Current Flow (Current flow rate); AV 1 Actuator Position (Current position, degrees); Other 2 Actuator Alarm Flags (Alarm bits).

How do I enable BMS control of the FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)?

MV 13 selects the communication mode (BACnet) and MV 6 = 4 (Serial) makes the actuator follow AV 4.

Does the FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) need a BACnet heartbeat or have a communication timeout?

PIV 30 sets the network timeout (1-60 min); BSV 2 bit 12 flags a network timeout. AV 18 sets the position on control signal loss (-1 = stay in place).

How do I check these points on the real SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More FlowCon BACnet points lists

Source: BACnet PICS for FlowCon SM.0.0.1.5/SM.0.0.1.6 · rev. 2026-07-17. Object names, instances and units are reproduced as published; descriptions are our own.