- SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)
Valve actuator (PICV) · BACnet points list
FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) BACnet points list
Updated 12 November 2026
Rotary actuators for FlowCon SM pressure-independent valves with BACnet MS/TP or Modbus. MV 6 picks the control source (voltage, mA, digital or serial bus); with serial control the BMS writes the demand to AV 4. The actuator reports position, flow, state, alarm flags and, on the SM.0.0.1.6, battery status for the power fail-safe.
This page lists 32 BACnet objects for the FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) — 20 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from FlowCon’s own free documentation, linked below.
- Manufacturer
- FlowCon
- Model
- SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)
- Equipment
- Valve actuator (PICV)
- Equipment type
- Valves & actuators
- BACnet objects
- 32 (20 writable)
- Transport
- BACnet MS/TP
- Firmware
- Actuator software FL1 V206, BACnet firmware V110
- Also known as
- SM.0.0.1.5, SM.0.0.1.6, FlowCon SM actuator, FlowCon SM-1516
Reference only, provided as-is: verify against FlowCon’s current documentation and the live device before use. Not official FlowCon information. Terms of use.
BMS integration notes: FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)
Set MV 13 to BACnet and MV 6 to Serial (BUS), then write the demand to AV 4. Read AV 22 for flow, MV 2 for state and BSV 2 for alarms; PIV 30 sets how long the actuator waits before treating the bus as lost.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 6 | Actuator Control Signal | 4 = Serial (BUS) control | Write |
| AV 4 | Actuator Control Demand | Control demand, 0-100 % | Write |
| MV 2 | Actuator State | Operating state | Read |
| AV 22 | Current Flow | Current flow rate | Read |
| AV 1 | Actuator Position | Current position, degrees | Read |
| Other 2 | Actuator Alarm Flags | Alarm bits | Read |
Enable & remote start
MV 13 selects the communication mode (BACnet) and MV 6 = 4 (Serial) makes the actuator follow AV 4.
Heartbeat & communication loss
PIV 30 sets the network timeout (1-60 min); BSV 2 bit 12 flags a network timeout. AV 18 sets the position on control signal loss (-1 = stay in place).
Network setup
- MS/TP MAC (1-127) and baud rate (autobaud or 9600-115200) are set in the Network Port object.
Watch out for
- BV 1 resets the actuator to factory settings.
- BV 2 and BV 3 clear error codes 2 (over torque) and 7 (lack of valve).
FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 2 | Control Signal | Control signal; min./max. also set here | V or mA (per MV 6) | Write | |
| AI | 3 | Power Supply Voltage | Power supply voltage | V | Read | |
| AI | 4 | Battery Voltage | Battery voltage (SM.0.0.1.6 fail-safe only) | V | Read | |
| AO | 1 | Feedback Signal | Feedback signal; span and unit per MV 7 | Read | ||
| AVmin | 1 | Actuator Position | Current position (0-2160°, SM.6.2 0-3600°) | ° | Read | |
| AV | 2 | Actuator Position Setpoint | Position set point (0-2160°, SM.6.2 0-3600°) | ° | Read | |
| AVmin | 4 | Actuator Control Demand | BACnet control demand, 0-100 % | % | Write | |
| AV | 9 | Internal Temperature | Actuator’s internal temperature | °C | Read | |
| AV | 16 | Max Flow | Max. flow setting; range follows valve in MV 4 | per MV 5 | Write | |
| AV | 17 | Power Failsafe Position | Position on power loss; -1 = in place (SM.0.0.1.6) | % | Write | |
| AV | 18 | Control Signal Failsafe Position | Position on control signal loss; -1 = in place | % | Write | |
| AVmin | 22 | Current Flow | Current flow rate | per MV 5 | Read | |
| BI | 5 | Digital Open Signal | Digital open status input | Read | 0=Inactive, 1=Active | |
| BI | 6 | Digital Close Signal | Digital close status input | Read | 0=Inactive, 1=Active | |
| BV | 1 | Factory Reset Request | Reset actuator to factory settings | Write | 0=Inactive, 1=Active | |
| BV | 2 | Reset Error#2 Request | Reset error 2 (over torque warning) | Write | 0=Inactive, 1=Active | |
| BV | 3 | Reset Error#7 Request | Reset error 7 (lack of valve) | Write | 0=Inactive, 1=Active | |
| MVmin | 2 | Actuator State | Actuator’s current state | Read | 1=Auto Stroke, 2=Standby, 3=Normal, 4=Alarm, 5=Not Active, 6=Failsafe / Failure, 7=Calibration, 8=Flushing, 9=Service Override (Service Ovrd) | |
| MV | 3 | Actuator Rotation Direction | Actuator’s rotation direction | Write | 1=NC, 2=NO | |
| MV | 4 | Valve Model | Valve model on which the actuator is fitted | Write | 1=SM.1.1, 2=SM.2.1, 3=SM.3.0, 4=SM.3.1, 5=SM.3.2, 6=SM.4.1, 7=SM.4.2, 8=SM.4.3, 9=SM.5.1, 10=SM.5.2, 11=SM.6.2, 12=SM.0.0 | |
| MV | 5 | Flow Unit Scale | Flow unit | Write | 1=l/sec, 2=GPM, 3=l/hr | |
| MVmin | 6 | Actuator Control Signal | Actuator’s control signal | Write | 1=Volt, 2=mA, 3=Digital, 4=Serial (= BUS) | |
| MV | 7 | Feedback Signal | Actuator’s feedback signal | Write | 1=2-10 Volt, 2=0-10 Volt, 3=4-20 mA, 4=AU (=automatic) | |
| MV | 8 | Actuator Mode | Actuator’s control mode | Write | 1=LIN FLO (=linear flow), 2=EQ PCT (=equal %), 3=LIN ROT (=linear rotation) | |
| MV | 12 | Battery Status | Battery status | Read | 1=None (=no battery), 2=Lost (=battery lost or loose), 3=Charge level 0 (=battery level low), 4=Charge level 1 (=battery level medium low), 5=Charge level 2 (=battery level medium high), 6=Charge level 3 (=battery level full) | |
| MV | 13 | Actuator Communication Mode | Actuator’s communication mode | Write | 1=Disabled, 2=BACnet, 3=Modbus | |
| Othermin | 2 | Actuator Alarm Flags | Bitstring: power fail, no valve, hardware, overtorque, temp, network timeout... | Read | ||
| Other | 3 | User Configuration Flags | Bitstring: password, flush, 15-min fail-safe delay | Write | ||
| CSV | 1 | User Custom String | Free user text | Write | ||
| PIV | 22 | Auto-Stroke Frequency (days) | Days between auto-stroke runs (default 7, 0 = off) | days | Write | |
| PIV | 30 | Network Timeout | Communication timeout, 1-60 min | min | Write | |
| Other | 1 | BACnet MS/TP Port | Network Port: baud (auto or 9600-115200), MAC 1-127 | Write |
No points match these filters.
Object ID lookup: FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator point IDs by name
AI2Control SignalAI3Power Supply VoltageAI4Battery VoltageAO1Feedback SignalAV1Actuator PositionAV2Actuator Position SetpointAV4Actuator Control DemandAV9Internal TemperatureAV16Max FlowAV17Power Failsafe PositionAV18Control Signal Failsafe PositionAV22Current FlowBI5Digital Open SignalBI6Digital Close SignalBV1Factory Reset RequestBV2Reset Error#2 RequestBV3Reset Error#7 RequestMV2Actuator StateMV3Actuator Rotation DirectionMV4Valve ModelMV5Flow Unit ScaleMV6Actuator Control SignalMV7Feedback SignalMV8Actuator ModeMV12Battery StatusMV13Actuator Communication ModeCSV1User Custom StringPIV22Auto-Stroke Frequency (days)PIV30Network Timeout
Integration notes
- Bitstring Value objects BSV 2 (alarm flags) and BSV 3 (user configuration flags) and Network Port 1 are listed as Other with their printed instance numbers.
- BSV 2 bits: 0 power fail, 1 no valve, 2 hardware, 3/4 overtorque CW/CCW, 5 over temperature, 7 no control signal, 8 battery fail, 9 power low, 10 was overtorqued, 12 network timeout.
- AI 4, AV 17 and MV 12 only apply to the SM.0.0.1.6 fail-safe version.
- Flow values (AV 16, AV 22) use the unit chosen in MV 5.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)
How many BACnet points does the FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) have?
This list has 32 BACnet objects: 3 analog inputs, 1 analog output, 8 analog values, 2 binary inputs, 3 binary values, 9 multi-state values, 1 characterstring value, 2 positive integer values, 3 others. The exact set on a given unit depends on its firmware, installed options and configuration.
Which FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) BACnet points are writable?
20 of the 32 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) BACnet documentation?
The source is BACnet PICS for FlowCon SM.0.0.1.5/SM.0.0.1.6, revision 2026-07-17, published free by FlowCon at https://flowcon.com/fileadmin/user_upload/Pdf/Certificates/BACnet_PICS/FlowCon-BACnet-PICS-Statement-FlowCon-SM-1516.pdf.
What are the minimum BACnet points to integrate the FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)?
Start with MV 6 Actuator Control Signal (4 = Serial (BUS) control); AV 4 Actuator Control Demand (Control demand, 0-100 %); MV 2 Actuator State (Operating state); AV 22 Current Flow (Current flow rate); AV 1 Actuator Position (Current position, degrees); Other 2 Actuator Alarm Flags (Alarm bits).
How do I enable BMS control of the FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)?
MV 13 selects the communication mode (BACnet) and MV 6 = 4 (Serial) makes the actuator follow AV 4.
Does the FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV) need a BACnet heartbeat or have a communication timeout?
PIV 30 sets the network timeout (1-60 min); BSV 2 bit 12 flags a network timeout. AV 18 sets the position on control signal loss (-1 = stay in place).
How do I check these points on the real SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More FlowCon BACnet points lists
- Valve actuator (PICV)
FlowCon FH-BUS / FN.0.2-BUS PICV actuator
FlowCon FH-BUS actuator (FlowCon Green.3 PICV) and FN.0.2-BUS actuator (FlowCon Green and GreEQ PICVs) with BACnet MS/TP.
Also known as: FH-BUS, FN.0.2-BUS, FN02-BUS, FlowCon FH actuator, FlowCon FN actuator, FlowCon Green.3 actuator, FlowCon GreEQ actuator - Valve controller (energy valve interface)
FlowCon FIT / Energy FIT intelligent interface (ACC40023)
FlowCon FIT intelligent interface (ACC40023) that turns a FlowCon PICV (SM, FN or FH actuator) plus temperature and pressure sensors into an energy valve, BACnet MS/TP.
Also known as: FlowCon FIT, FlowCon Energy FIT, ACC40023, FIT Intelligent Interface, FlowCon FIT Energy System
Source: BACnet PICS for FlowCon SM.0.0.1.5/SM.0.0.1.6 · rev. 2026-07-17. Object names, instances and units are reproduced as published; descriptions are our own.