Valve actuator (PICV) · BACnet points list
FlowCon FH-BUS / FN.0.2-BUS PICV actuator BACnet points list
Updated 12 November 2026
Modulating bus actuators for FlowCon pressure-independent control valves, talking BACnet MS/TP or Modbus. The BMS can drive the valve directly (AV 1 flow set point) or let the actuator run room temperature, thermal power or return temperature control from its own PI loop, with two configurable sensor ports. It also reports flow, delta T, thermal power, energy and several fault flags.
This page lists 72 BACnet objects for the FlowCon FH-BUS / FN.0.2-BUS PICV actuator — 44 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from FlowCon’s own free documentation, linked below.
- Manufacturer
- FlowCon
- Model
- FH-BUS / FN.0.2-BUS PICV actuator
- Equipment
- Valve actuator (PICV)
- Equipment type
- Valves & actuators
- BACnet objects
- 72 (44 writable)
- Transport
- BACnet MS/TP
- Firmware
- Software 2.11, protocol revision 1.22
- Also known as
- FH-BUS, FN.0.2-BUS, FN02-BUS, FlowCon FH actuator, FlowCon FN actuator, FlowCon Green.3 actuator, FlowCon GreEQ actuator
- Source document
- BACnet PICS for FlowCon FH-BUS · rev. 2026-03-02
Reference only, provided as-is: verify against FlowCon’s current documentation and the live device before use. Not official FlowCon information. Terms of use.
BMS integration notes: FlowCon FH-BUS / FN.0.2-BUS PICV actuator
Set MV 4 to 1 (external control signal) and write the flow demand to AV 1, or pick a local control mode and write its set point. Set MV 6 to choose what the actuator does if the bus goes quiet, and watch BI 3-7 for faults.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 4 | Operating mode | Control mode; 1 = follow AV 1 | Write |
| AV 1 | External control signal | Flow set point, 0-100 % | Write |
| MV 9 | Choose HVAC mode (Changeover) | Changeover: shut-off, heating, cooling, auto | Write |
| AI 6 | Actual value control signal | Actual flow, % of max. | Read |
| AI 7 | Actual volume flow rate | Actual flow, l/h | Read |
| AI 8 | Differential temperature | Water delta T | Read |
| BI 3 | Actuator is busy | Not following the control signal | Read |
| BI 4 | Actuator in malfunction | Hardware fault | Read |
| BI 6 | Error: valve blocking | Valve blocked | Read |
Enable & remote start
MV 4 = 1 makes the actuator follow AV 1; other MV 4 values hand control to the built-in room temperature, thermal power or return temperature loop.
Heartbeat & communication loss
MV 6 sets the action on communication loss: fail in place, or after 120 s close, open or go to the AV 8 position (default 30 %).
Sensors & values from the BMS
Supply/return temperatures (AV 4/AV 5) and room temperature (AV 17) can be written by the BMS when MV 5 / MV 10 select BUS as the source.
Network setup
- MS/TP MAC is AV 28 (1-127), writable only with the DIP switches set to 63.
- Baud rate is MV 7 (default 38400); a change needs an actuator restart.
Watch out for
- MV 1 service commands include reset to factory settings; write it only on purpose.
- AV 2/AV 3 limit the control signal range; AV 22/AV 23 limits can override AV 1 (BI 8 shows when).
FlowCon FH-BUS / FN.0.2-BUS PICV actuator BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AI | 1 | Serial number, software version | Serial number and software version (xxxxxx.xx / x.xx) | Read | ||
| AI | 2 | Analog input P(ort) 1 | Measured value at port 1 | °C, K or % (per sensor type) | Read | |
| AI | 3 | Analog input P(ort)2 | Measured value at port 2 | °C, K or % (per sensor type) | Read | |
| AI | 4 | Target position | Target position for the actuator piston | mm | Read | |
| AI | 5 | Actual position | Actual position of the actuator piston | mm | Read | |
| AImin | 6 | Actual value control signal | Actual flow in percent of max. flow setting | % | Read | |
| AImin | 7 | Actual volume flow rate | Calculated flow rate from valve parameters | l/h | Read | |
| AImin | 8 | Differential temperature | Water delta T from supply and return temperatures | K | Read | |
| AI | 9 | Flush timer actual value | Time left to next flush (hours, last hour in minutes) | h | Read | |
| AI | 10 | Valve blocking protection timer actual value | Time left to next valve blocking protection run | h | Read | |
| AI | 11 | Operating hours | Total actuator operating time | h | Read | |
| AI | 12 | Distance counter | Total actuator travel distance | mm | Read | |
| AI | 13 | Overall stroke | Distance between upper and lower end position | mm | Read | |
| AI | 15 | Actual volume flow rate limitation | Max. flow for the selected valve (from MV 8) | l/h | Read | |
| AI | 16 | Actual value of thermal power | Thermal power through the valve (PICV only) | kW | Read | |
| AI | 17 | Energy since 0:00 o’clock | Energy used since midnight (PICV only) | kWh | Read | |
| AI | 18 | Energy in the last 24h | Energy used over the last 24 h (PICV only) | kWh | Read | |
| AO | 1 | Analog output P(ort) 2 | Port 2 0-10 V output value (when MV 3 = 9) | % | Write | |
| AVmin | 1 | External control signal | Flow set point / actuating signal, 0-100 % (-10 to 110) | % | Write | |
| AV | 2 | Minimum control signal | Set minimum control signal limit | % | Write | |
| AV | 3 | Maximum control signal | Set maximum control signal limit | % | Write | |
| AV | 4 | Supply temperature | Supply water temperature; write-protected if from a port | °C | Write | |
| AV | 5 | Return temperature | Return water temperature; write-protected if from a port | °C | Write | |
| AV | 6 | Correction value P(ort) 1 | Correction for port 1, -10 to +10 | Write | ||
| AV | 7 | Correction value P(ort) 2 | Correction for port 2, -10 to +10 | Write | ||
| AV | 8 | Emergency position | Fail-safe position on bus loss (default 30 %) | % | Write | |
| AV | 10 | Valve blocking protection timer | Time between valve blocking protection runs; 0 = off | h | Write | |
| AV | 11 | Hydraulic balancing value for heating | Balancing flow for heating mode | l/h | Write | |
| AV | 12 | Hydraulic balancing value for cooling | Balancing flow for cooling mode | l/h | Write | |
| AV | 13 | Valve lift | Valve stroke 0.5-9 mm; 0 = automatic detection | mm | Write | |
| AV | 14 | Medium energy constant | Medium energy constant (4183 = water) | J/(kg·K) | Write | |
| AV | 15 | Xp | PI controller proportional gain, 2-6000 | Write | ||
| AV | 16 | Tn | PI controller time constant | s | Write | |
| AV | 17 | Room temperature actual value | Room temperature; write-protected if from a port | °C | Write | |
| AV | 18 | Room temperature setpoint | Room temperature set point (0-50 °C; 0-100 °C on FN.0.2) | °C | Write | |
| AV | 19 | Thermal power setpoint | Thermal power setpoint | kW | Write | |
| AV | 20 | Return temperature setpoint | Return water temperature setpoint | °C | Write | |
| AV | 22 | Maximum thermal power limiting value | Thermal power limit; 0 = not active | kW | Write | |
| AV | 23 | Return temperature limiting value | Return water temperature limit; 0 = not active | °C | Write | |
| AV | 28 | MAC address | MS/TP MAC 1-127; writable when DIP switches set to 63 | Write | ||
| AV | 29 | Close when adjusting range | End-position range where actuator stays at the end, 0-5 % | % | Write | |
| AV | 30 | Kvs value of the selected valve | No function; value set by valve selection in MV 8 | Read | ||
| AV | 31 | Sensitivity constant thermal power limitation | Gain for thermal power limitation, 2-6000 | Write | ||
| AV | 32 | Sensitivity constant return temperature limitation | Gain for return temperature limitation, 2-6000 | Write | ||
| AV | 35 | Flush timer | Time between flushing runs; 0 = off | h | Write | |
| BI | 1 | Binary input P(ort) 1 | Input in port 1 | Read | 0=Off, 1=On | |
| BI | 2 | Binary input P(ort) 2 | Input in port 2 | Read | 0=Off, 1=On | |
| BImin | 3 | Actuator is busy | Actuator busy, not following the control signal | Read | 0=Normal operation, 1=Actuator is not available for control signal | |
| BImin | 4 | Actuator in malfunction | Hardware fault (e.g. port range exceeded) | Read | 0=Normal operation, 1=Hardware fault | |
| BI | 5 | Error during valve adaption | Valve calibration error | Read | 0=Normal operation, 1=Error during valve adaption | |
| BImin | 6 | Error: valve blocking | Valve blocked error | Read | 0=Normal operation, 1=Error, valve is blocked | |
| BI | 7 | Warning: leak detected | Leak warning: dT above 8 K with valve closed 6 h+ | Read | 0=No warning, 1=Leak detected | |
| BI | 8 | Limit function active | Control signal overridden by a limit function | Read | ||
| BV | 1 | P(ort) 1 inversion (binary input) | Port 1 binary input direct/inverse (MV 2 = 2) | Write | 0=Direct, 1=Inverted | |
| BV | 2 | P(ort) 2 inversion (binary input) | Port 2 binary input direct/inverse (MV 3 = 2) | Write | 0=Direct, 1=Inverted | |
| BV | 3 | P(ort) 2 inversion (analog output) | Port 2 analog output direct/inverse (MV 3 = 9) | Write | 0=Direct, 1=Inverted | |
| BV | 4 | Inversion of the valve actuating direction | Actuator direction | Write | 0=Normally closed, 1=Normally open | |
| MI | 1 | Status of HVAC mode (Changeover) | Current changeover mode | Read | 1=Shut-off, 2=Heating, 3=Cooling | |
| MV | 1 | Service command | Service command | Write | 1=Normal operation mode, 2=Calibration mode, 3=Flush mode, 4=Synchronize valve, 5=Reset error messages, 6=Reset BUS, 7=Reset to factory settings | |
| MV | 2 | Sensor type P(ort) 1 | Port 1 sensor type | Write | 1=OFF, 2=Binary input, 3=0-10V input, 4=KP10, 5=Ni1000-DIN, 6=Ni1000-LG, 7=PT100 (PT1000 on FN.0.2), 8=Potentiometer 10kΩ, 9=Potentiometer 10kΩ +/-3kΩ, 10=Potentiometer 10kΩ +/-5kΩ | |
| MV | 3 | Sensor/Output type P(ort) 2 | Port 2 sensor type / output | Write | 1=OFF, 2=Binary input, 3=0-10V input, 4=KP10, 5=Ni1000-DIN, 6=Ni1000-LG, 7=PT1000, 8=Potentiometer 10kΩ, 9=0-10V output (AO 1), 10=0-10V Y position feedback (AI 6), 11=Changeover signal for 6-way valve (MV 9) | |
| MVmin | 4 | Operating mode | Control mode and where its set points come from | Write | 1=External control signal (AV 1), 2=Open ~100%, 3=Closed ~0%, 4=Minimum position (AV 2), 5=NOT ACTIVE, 6=Maximum position (AV 3), 7=Room temperature (AV 17, AV 18), 8=Control by thermal power (AI 16, AV 19), 9=Return water temperature (AV 5, AV 20) | |
| MV | 5 | Source of supply and return temperature | Water temperature source, supply and return | Write | 1=BUS (AV 4 and AV 5), 2=Port 1 supply, Port 2 return, 3=Port 2 supply, Port 1 return, 4=Port 1 supply, BUS return, 5=Port 2 supply, BUS return, 6=BUS supply, Port 1 return, 7=BUS supply, Port 2 return | |
| MV | 6 | Communication failure mode | Action in case of communication failure | Write | 1=fail in place, 2=close (after 120 s), 3=open (after 120 s), 4=fail position AV 8 (after 120 s) | |
| MV | 7 | Select RS485 baud rate | RS-485 baud rate; takes effect after restart | Write | 1=Default (38400), 2=9600, 3=19200, 4=38400, 5=57600, 6=76800, 7=115200 | |
| MV | 8 | Select valve type | Valve type and characteristic | Write | FH-BUS: 1=Linear (generic), 2=Green.3, 3=EQ% (generic), 4=User-Valve; FN.0.2-BUS: 1=Linear (generic), 2=Green.0, 3=Green.1, 4=Green.2, 5=Green.1HF, 6=GreEQ.0, 7=GreEQ.1, 8=GreEQ.2, 9=EQ% (generic), 10=User-Valve | |
| MVmin | 9 | Choose HVAC mode (Changeover) | Changeover mode command | Write | 1=Shut-off, 2=Heating, 3=Cooling, 4=Automatic based on supply temperature (MV 3 not 11) | |
| MV | 10 | Select source for room temperature | Room temperature source | Write | 1=BUS (set AV.17), 2=Port 1, 3=Port 2 | |
| MV | 11 | LED mode | LED indication | Write | 1=OFF, 2=ON without BUS, 3=ON with BUS | |
| MV | 12 | Actuating speed | Actuator speed | Write | 1=22 s/mm, 2=28 s/mm, 3=16 s/mm | |
| MV | 13 | Actuator Control Curve | Actuator control curve (input and feedback) | Write | 1=Linear, 2=Equal%, 3=Equal% inverse | |
| Other | 1 | Network port MS/TP | Network Port object (MS/TP) | Read |
No points match these filters.
Object ID lookup: FlowCon FH-BUS / FN.0.2-BUS PICV actuator point IDs by name
AI1Serial number, software versionAI2Analog input P(ort) 1AI3Analog input P(ort)2AI4Target positionAI5Actual positionAI6Actual value control signalAI7Actual volume flow rateAI8Differential temperatureAI9Flush timer actual valueAI10Valve blocking protection timer actual valueAI11Operating hoursAI12Distance counterAI13Overall strokeAI15Actual volume flow rate limitationAI16Actual value of thermal powerAI17Energy since 0:00 o’clockAI18Energy in the last 24hAO1Analog output P(ort) 2AV1External control signalAV2Minimum control signalAV3Maximum control signalAV4Supply temperatureAV5Return temperatureAV6Correction value P(ort) 1AV7Correction value P(ort) 2AV8Emergency positionAV10Valve blocking protection timerAV11Hydraulic balancing value for heatingAV12Hydraulic balancing value for coolingAV13Valve liftAV14Medium energy constantAV15XpAV16TnAV17Room temperature actual valueAV18Room temperature setpointAV19Thermal power setpointAV20Return temperature setpointAV22Maximum thermal power limiting valueAV23Return temperature limiting valueAV28MAC addressAV29Close when adjusting rangeAV30Kvs value of the selected valveAV31Sensitivity constant thermal power limitationAV32Sensitivity constant return temperature limitationAV35Flush timerBI1Binary input P(ort) 1BI2Binary input P(ort) 2BI3Actuator is busyBI4Actuator in malfunctionBI5Error during valve adaptionBI6Error: valve blockingBI7Warning: leak detectedBI8Limit function activeBV1P(ort) 1 inversion (binary input)BV2P(ort) 2 inversion (binary input)BV3P(ort) 2 inversion (analog output)BV4Inversion of the valve actuating directionMI1Status of HVAC mode (Changeover)MV1Service commandMV2Sensor type P(ort) 1MV3Sensor/Output type P(ort) 2MV4Operating modeMV5Source of supply and return temperatureMV6Communication failure modeMV7Select RS485 baud rateMV8Select valve typeMV9Choose HVAC mode (Changeover)MV10Select source for room temperatureMV11LED modeMV12Actuating speedMV13Actuator Control Curve
Integration notes
- The FH-BUS and FN.0.2-BUS PICS print the same 72 objects; they differ only in MV 8 valve choices, the PT100/PT1000 option in MV 2 and the AV 18 range.
- Network Port 1 (MS/TP) is listed as Other 1.
- AV 4, AV 5 and AV 17 are writable only when MV 5 / MV 10 selects BUS as the source.
- Thermal power and energy values (AI 16-18) are only valid on PICVs.
- Instance numbers skip AI 14, AV 9, AV 21 and AV 24-27, AV 33-34 as printed.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FH-BUS / FN.0.2-BUS PICV actuator and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the FlowCon FH-BUS / FN.0.2-BUS PICV actuator
How many BACnet points does the FlowCon FH-BUS / FN.0.2-BUS PICV actuator have?
This list has 72 BACnet objects: 17 analog inputs, 1 analog output, 27 analog values, 8 binary inputs, 4 binary values, 1 multi-state input, 13 multi-state values, 1 other. The exact set on a given unit depends on its firmware, installed options and configuration.
Which FlowCon FH-BUS / FN.0.2-BUS PICV actuator BACnet points are writable?
44 of the 72 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official FlowCon FH-BUS / FN.0.2-BUS PICV actuator BACnet documentation?
The source is BACnet PICS for FlowCon FH-BUS, revision 2026-03-02, published free by FlowCon at https://flowcon.com/fileadmin/user_upload/Pdf/Certificates/BACnet_PICS/FlowCon-BACnet-PICS-Statement-FlowCon-FH-BUS.pdf.
What are the minimum BACnet points to integrate the FlowCon FH-BUS / FN.0.2-BUS PICV actuator?
Start with MV 4 Operating mode (Control mode; 1 = follow AV 1); AV 1 External control signal (Flow set point, 0-100 %); MV 9 Choose HVAC mode (Changeover) (Changeover: shut-off, heating, cooling, auto); AI 6 Actual value control signal (Actual flow, % of max); AI 7 Actual volume flow rate (Actual flow, l/h); AI 8 Differential temperature (Water delta T); BI 3 Actuator is busy (Not following the control signal); BI 4 Actuator in malfunction (Hardware fault); BI 6 Error: valve blocking (Valve blocked).
How do I enable BMS control of the FlowCon FH-BUS / FN.0.2-BUS PICV actuator?
MV 4 = 1 makes the actuator follow AV 1; other MV 4 values hand control to the built-in room temperature, thermal power or return temperature loop.
Does the FlowCon FH-BUS / FN.0.2-BUS PICV actuator need a BACnet heartbeat or have a communication timeout?
MV 6 sets the action on communication loss: fail in place, or after 120 s close, open or go to the AV 8 position (default 30 %).
Can the BMS supply sensor values to the FlowCon FH-BUS / FN.0.2-BUS PICV actuator?
Supply/return temperatures (AV 4/AV 5) and room temperature (AV 17) can be written by the BMS when MV 5 / MV 10 select BUS as the source.
How do I check these points on the real FH-BUS / FN.0.2-BUS PICV actuator?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More FlowCon BACnet points lists
- Valve controller (energy valve interface)
FlowCon FIT / Energy FIT intelligent interface (ACC40023)
FlowCon FIT intelligent interface (ACC40023) that turns a FlowCon PICV (SM, FN or FH actuator) plus temperature and pressure sensors into an energy valve, BACnet MS/TP.
Also known as: FlowCon FIT, FlowCon Energy FIT, ACC40023, FIT Intelligent Interface, FlowCon FIT Energy System - Valve actuator (PICV)
FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)
FlowCon SM.0.0.1.5 and SM.0.0.1.6 (fail-safe) actuators for FlowCon SM large pressure-independent control valves, BACnet MS/TP.
Also known as: SM.0.0.1.5, SM.0.0.1.6, FlowCon SM actuator, FlowCon SM-1516
Source: BACnet PICS for FlowCon FH-BUS · rev. 2026-03-02. Object names, instances and units are reproduced as published; descriptions are our own.