Valve controller (energy valve interface) · BACnet points list

FlowCon FIT / Energy FIT intelligent interface (ACC40023) BACnet points list

Updated 12 November 2026

Short answer

The FIT interface sits between the BMS and a FlowCon PICV actuator and adds supply/return temperature (and optional pressure) sensors. It can run as a delta T energy valve, as a comfort (flow) PICV, or in a smart mode that balances room temperature against delta T, and it logs energy use. MV 6 sets which actuator and sensor set is fitted; many objects only work in some configurations.

This page lists 71 BACnet objects for the FlowCon FIT / Energy FIT intelligent interface (ACC40023) — 43 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from FlowCon’s own free documentation, linked below.

Manufacturer
FlowCon
Model
FIT / Energy FIT intelligent interface (ACC40023)
Equipment
Valve controller (energy valve interface)
Equipment type
Valves & actuators
BACnet objects
71 (43 writable)
Transport
BACnet MS/TP
Firmware
Firmware 3.0.4, application 1.05
Also known as
FlowCon FIT, FlowCon Energy FIT, ACC40023, FIT Intelligent Interface, FlowCon FIT Energy System
Source document
Protocol Implementation Conformance Statement (PICS) for FlowCon FIT · rev. 2026-06-26
Download CSV 71 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against FlowCon’s current documentation and the live device before use. Not official FlowCon information. Terms of use.

BMS integration notes: FlowCon FIT / Energy FIT intelligent interface (ACC40023)

Integration in brief

Set MV 6 to the fitted actuator/sensor set and MV 5 to the control strategy, then write the delta T target (AV 4) or room values (AV 6/AV 7) or the control signal (AV 141). Read flow, delta T and energy; watch the alarm BVs.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
MV 5Flow ControlControl strategy (delta T, comfort, smart)Write
AV 141AnalogControlSignalControl signal, %Write
AV 4WaterTempDeltaTargetDelta T targetWrite
AV 7RoomTargetTempRoom temperature targetWrite
AV 6RoomTemperatureRoom temperature from the BMSWrite
AV 68FlowRateCurrent flow rateRead
AV 3WaterTempDeltaDelta TRead
AV 10EnergyConsumptionCurrent energy rateRead
BV 62BACnetFallback-AlarmBACnet fallback activeWrite
BV 59PowerFailAlarmPower failure alarmRead

Enable & remote start

MV 5 picks how FIT controls the valve: 1/4 delta T target, 2 comfort (set flow), 3/5 smart (room temperature with delta T).

Heartbeat & communication loss

AV 143 sets the BACnet control fallback timeout (1-60 min, config 1); MV 43 shows the fallback action and BV 62 flags it.

Sensors & values from the BMS

Room temperature AV 6 and its target AV 7 are writable for the comfort and smart modes.

Network setup

Watch out for

FlowCon FIT / Energy FIT intelligent interface (ACC40023) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

71 of 71 shown
Type
AnalogBinaryMulti-state
Access
Show
FlowCon FIT / Energy FIT intelligent interface (ACC40023) BACnet Points List
DescriptionStates
AV1WaterTemperature1T1, temperature sensor 1°C or °F (per MV 3)Read
AV2WaterTemperature2T2, temperature sensor 2°C or °F (per MV 3)Read
AVmin3WaterTempDeltaDelta T (T1 - T2)°C or °F (per MV 3)Read
AVmin4WaterTempDeltaTargetDelta T target (default 10), for delta T control°C or °F (per MV 3)Write
AV5WaterTempDeltaDeadbandDelta T target deadband (default 0.5)°C or °F (per MV 3)Write
AVmin6RoomTemperatureRoom temperature (default 23)°C or °F (per MV 3)Write
AVmin7RoomTargetTempRoom temperature target (default 23)°C or °F (per MV 3)Write
AV8RoomTargetDeadbandRoom target deadband (default 1)°C or °F (per MV 3)Write
AV9TargetEvalIntervalTemperature check interval, 3-3600 s (default 10)sWrite
AVmin10EnergyConsumptionCurrent energy rate, kW or BTU/hkW/kWh or BTU/h/BTU (per MV 4)Read
AV11EnergyAccumulationCycle1Accumulated energy, cycle 1kW/kWh or BTU/h/BTU (per MV 4)Read
AV12EnergyAccumCycleCount1Length of energy cycle 1 in days (default 1)daysWrite
AV13EnergyAccumulationCycle2Accumulated energy, cycle 2kW/kWh or BTU/h/BTU (per MV 4)Read
AV14EnergyAccumCycleCount2Length of energy cycle 2 in days (default 30)daysWrite
AV15EnergyLogOldestDataIndexIndex of oldest entry in the energy trend logRead
AV16Temp1CorrectCorrection value for temperature sensor 1°C or °F (per MV 3)Write
AV17Temp2CorrectCorrection value for temperature sensor 2°C or °F (per MV 3)Write
AV18Pressure1Pressure sensor 1 (config 1, 2, 4)kPa or psi (per MV 7)Read
AV19Pressure2Pressure sensor 2 (config 1, 2, 4)kPa or psi (per MV 7)Read
AV20PressureDeltaDelta P (P1 - P2) (config 1, 2, 4)kPa or psi (per MV 7)Read
AV21Press1CorrectPressure sensor 1 correctionkPa or psi (per MV 7)Write
AV22Press2CorrectPressure sensor 2 correctionkPa or psi (per MV 7)Write
AV23SystemOnCounterMinutes the system has been onminRead
AV62MaxFlowMaximum flow rate; range follows the valve modelper MV 39Write
AVmin68FlowRateCurrent flow rateper MV 39Read
AV98MotorPositionMotor position / valve opening%Read
AV138ControlSigMinAnalog control signal minimum (no function)VWrite
AV139ControlSigMaxAnalog control signal maximum (no function)VWrite
AV140BatteryCapacityActuator battery capacity (config 1)%Read
AVmin141AnalogControlSignalAnalog control signal value, %%Write
AV143BACnetFallbackTimeoutBACnet control fallback timeout, 1-60 min (config 1)minWrite
AV164FeedbackSignalFeedback signal value (no function)VRead
AV165WaterT1T1 written back to actuator display (config 1)°CWrite
AV166WaterT2T2 written back to actuator display (config 1)°CWrite
AV167WaterdTDelta T written back to actuator display (config 1)°CWrite
AV168dPDelta P written back to actuator display (config 1)kPaDWrite
BV1PressureDeltaAlarmDelta P alarm (config 1, 2, 4)Read0=OFF, 1=ON
BV2RestartUnitRestart unitWrite0=Not activate, 1=Activated
BV3ActuatorCommsResetRestart comms port to the attached actuatorWrite0=Disabled, 1=Enabled
BV4EnergyAccumulationResetReset accumulated energy logWrite0=Disabled, 1=Enabled
BV17RotationDirectionMotor rotation directionWrite0=NO, 1=NC
BV18FailsafeDirectionFailsafe rotation directionWrite0=Open, 1=Close
BV53FlushModeFlush mode enableWrite0=Disabled, 1=Enabled
BV54PasswordPassword enableWrite0=Disabled, 1=Enabled
BV55OvertorquedAlarmOvertorqued alarmRead0=Off, 1=On
BV56OvertorquedInPastAlarmOvertorqued in past alarmWrite0=Off, 1=On
BV57OverTemperatureAlarmCritical over temperature alarmRead0=Off, 1=On
BV58HighTemperatureAlarmUncritical high temperature alarmRead0=Off, 1=On
BVmin59PowerFailAlarmPower failure / out of range alarmRead0=Off, 1=On
BV60NoCtrlSignalAlarmNo control signal alarmRead0=Off, 1=On
BV61BattErrorAlarmBattery error alarmRead0=Off, 1=On
BVmin62BACnetFallback-AlarmBACnet fallback alarmWrite0=Off, 1=On
BV63AutostrokeStart auto-stroke; returns to 0 when doneWrite0=Disabled, 1=Enabled
MV1Baud RateFIT baud rateWrite1=9600, 2=19200, 3=38400, 4=57600, 5=76800, 6=115200
MV2MS/TP MAC AddressFIT MS/TP MAC address, 0-127Write
MV3TemperatureFIT workable temperature unitsWrite1=°C, 2=°F
MV4Energy UnitsFIT workable energy unitsWrite1=BTU and BTU/h, 2=kWh and kW
MVmin5Flow ControlControl strategy: delta T, comfort (flow) or smartWrite1=ΔT Control (Delta T Target), 2=Comfort Control (Set Flow), 3=Smart Control (Room temp. in combi with ΔT), 4=ΔT Control 90% close, 5=Smart Control 90% close
MV6ConfigurationFIT system configuration (actuator/sensor set)Write1=SM.0.0.0.5/6, 2=SM.0.0.0.3/4, 3=FN/FH w/o pressure sensors, 4=FN/FH w pressure sensors
MV7Pressure UnitsFIT workable pressure unitWrite1=kPa, 2=psi
MV8ValveModelGValve model, FlowCon Green (config 3 and 4)Write1=Green.0, 2=Green.1, 3=Green.2, 4=Green.3
MV38ValveModelValve model, FlowCon SM (config 1 and 2)Write1=SM.0.0, 2=SM.1.1, 3=SM.2.1, 4=SM.3.0, 5=SM.3.1, 6=SM.3.2, 7=SM.4.1, 8=SM.4.2, 9=SM.4.3, 10=SM.5.1, 11=SM.5.2, 12=SM.6.2
MV39FlowScaleUnitFlow scale unitWrite1=l/sec, 2=GPM, 3=l/hr
MV40ControlSignalModeControl signal mode; only BACnet is validRead1=2-10VDC, 2=4-20mA, 3=Digital, 4=BACnet
MV41FeedbackSignalModeFeedback signal mode (no function)Read1=2-10VDC, 2=0-10VDC, 3=4-20mA, 4=Auto
MV43BACnetFallbackActionActuator action on BACnet fallback (config 1)Read1=Close, 2=Stop, 3=Open, 4=Midway
MV44PressureRange_kPaDPICV pressure range (kPaD) for the valve in MV 38Read1=NA (SM.0.0), 2=32-320 (SM.1.1), 3=40-320 (SM.2.1), 4=30-800 (SM.3.0), 5=30-800 (SM.3.1), 6=35-800 (SM.3.2), 7=30-800 (SM.4.1), 8=35-800 (SM.4.2), 9=50-800 (SM.4.3), 10=30-800 (SM.5.1), 11=35-800 (SM.5.2), 12=35-800 (SM.6.2)
MV45ActuatorStateActuator operating state (config 1)Read1=Normal, 2=Calibration, 3=Flush, 4=Auto-stroke, 5=Alarm, 6=Failsafe
MV46ControlCurveModeActuator control curve; only linear flow is validWrite1=Linear flow, 2=Equal%, 3=Linear rotation, 4=Linear signal
CSV1Bluetooth Ad NameBluetooth advertised name (default FlowCon FIT)Write
TL1Energy dataDaily energy trend log, 1200 entries, rolloverRead
Object ID lookup: FlowCon FIT / Energy FIT intelligent interface point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FIT / Energy FIT intelligent interface (ACC40023) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the FlowCon FIT / Energy FIT intelligent interface (ACC40023)

How many BACnet points does the FlowCon FIT / Energy FIT intelligent interface (ACC40023) have?

This list has 71 BACnet objects: 36 analog values, 17 binary values, 16 multi-state values, 1 trend log, 1 characterstring value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which FlowCon FIT / Energy FIT intelligent interface (ACC40023) BACnet points are writable?

43 of the 71 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official FlowCon FIT / Energy FIT intelligent interface (ACC40023) BACnet documentation?

The source is Protocol Implementation Conformance Statement (PICS) for FlowCon FIT, revision 2026-06-26, published free by FlowCon at https://flowcon.com/fileadmin/user_upload/Pdf/Certificates/BACnet_PICS/FlowCon-BACnet-PICS-Statement-FlowCon-FIT.pdf.

What are the minimum BACnet points to integrate the FlowCon FIT / Energy FIT intelligent interface (ACC40023)?

Start with MV 5 Flow Control (Control strategy (delta T, comfort, smart)); AV 141 AnalogControlSignal (Control signal, %); AV 4 WaterTempDeltaTarget (Delta T target); AV 7 RoomTargetTemp (Room temperature target); AV 6 RoomTemperature (Room temperature from the BMS); AV 68 FlowRate (Current flow rate); AV 3 WaterTempDelta (Delta T); AV 10 EnergyConsumption (Current energy rate); BV 62 BACnetFallback-Alarm (BACnet fallback active); BV 59 PowerFailAlarm (Power failure alarm).

How do I enable BMS control of the FlowCon FIT / Energy FIT intelligent interface (ACC40023)?

MV 5 picks how FIT controls the valve: 1/4 delta T target, 2 comfort (set flow), 3/5 smart (room temperature with delta T).

Does the FlowCon FIT / Energy FIT intelligent interface (ACC40023) need a BACnet heartbeat or have a communication timeout?

AV 143 sets the BACnet control fallback timeout (1-60 min, config 1); MV 43 shows the fallback action and BV 62 flags it.

Can the BMS supply sensor values to the FlowCon FIT / Energy FIT intelligent interface (ACC40023)?

Room temperature AV 6 and its target AV 7 are writable for the comfort and smart modes.