- FIT / Energy FIT intelligent interface (ACC40023)
Valve controller (energy valve interface) · BACnet points list
FlowCon FIT / Energy FIT intelligent interface (ACC40023) BACnet points list
Updated 12 November 2026
The FIT interface sits between the BMS and a FlowCon PICV actuator and adds supply/return temperature (and optional pressure) sensors. It can run as a delta T energy valve, as a comfort (flow) PICV, or in a smart mode that balances room temperature against delta T, and it logs energy use. MV 6 sets which actuator and sensor set is fitted; many objects only work in some configurations.
This page lists 71 BACnet objects for the FlowCon FIT / Energy FIT intelligent interface (ACC40023) — 43 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from FlowCon’s own free documentation, linked below.
- Manufacturer
- FlowCon
- Model
- FIT / Energy FIT intelligent interface (ACC40023)
- Equipment
- Valve controller (energy valve interface)
- Equipment type
- Valves & actuators
- BACnet objects
- 71 (43 writable)
- Transport
- BACnet MS/TP
- Firmware
- Firmware 3.0.4, application 1.05
- Also known as
- FlowCon FIT, FlowCon Energy FIT, ACC40023, FIT Intelligent Interface, FlowCon FIT Energy System
Reference only, provided as-is: verify against FlowCon’s current documentation and the live device before use. Not official FlowCon information. Terms of use.
BMS integration notes: FlowCon FIT / Energy FIT intelligent interface (ACC40023)
Set MV 6 to the fitted actuator/sensor set and MV 5 to the control strategy, then write the delta T target (AV 4) or room values (AV 6/AV 7) or the control signal (AV 141). Read flow, delta T and energy; watch the alarm BVs.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| MV 5 | Flow Control | Control strategy (delta T, comfort, smart) | Write |
| AV 141 | AnalogControlSignal | Control signal, % | Write |
| AV 4 | WaterTempDeltaTarget | Delta T target | Write |
| AV 7 | RoomTargetTemp | Room temperature target | Write |
| AV 6 | RoomTemperature | Room temperature from the BMS | Write |
| AV 68 | FlowRate | Current flow rate | Read |
| AV 3 | WaterTempDelta | Delta T | Read |
| AV 10 | EnergyConsumption | Current energy rate | Read |
| BV 62 | BACnetFallback-Alarm | BACnet fallback active | Write |
| BV 59 | PowerFailAlarm | Power failure alarm | Read |
Enable & remote start
MV 5 picks how FIT controls the valve: 1/4 delta T target, 2 comfort (set flow), 3/5 smart (room temperature with delta T).
Heartbeat & communication loss
AV 143 sets the BACnet control fallback timeout (1-60 min, config 1); MV 43 shows the fallback action and BV 62 flags it.
Sensors & values from the BMS
Room temperature AV 6 and its target AV 7 are writable for the comfort and smart modes.
Network setup
- MS/TP MAC is MV 2 (0-127) and baud rate MV 1 (9600-115200).
- Choose units first: MV 3 temperature, MV 4 energy, MV 7 pressure, MV 39 flow.
Watch out for
- MV 6 Configuration is flagged in the PICS with "!!"; set it once to match the hardware.
- BV 4 resets the accumulated energy log.
FlowCon FIT / Energy FIT intelligent interface (ACC40023) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AV | 1 | WaterTemperature1 | T1, temperature sensor 1 | °C or °F (per MV 3) | Read | |
| AV | 2 | WaterTemperature2 | T2, temperature sensor 2 | °C or °F (per MV 3) | Read | |
| AVmin | 3 | WaterTempDelta | Delta T (T1 - T2) | °C or °F (per MV 3) | Read | |
| AVmin | 4 | WaterTempDeltaTarget | Delta T target (default 10), for delta T control | °C or °F (per MV 3) | Write | |
| AV | 5 | WaterTempDeltaDeadband | Delta T target deadband (default 0.5) | °C or °F (per MV 3) | Write | |
| AVmin | 6 | RoomTemperature | Room temperature (default 23) | °C or °F (per MV 3) | Write | |
| AVmin | 7 | RoomTargetTemp | Room temperature target (default 23) | °C or °F (per MV 3) | Write | |
| AV | 8 | RoomTargetDeadband | Room target deadband (default 1) | °C or °F (per MV 3) | Write | |
| AV | 9 | TargetEvalInterval | Temperature check interval, 3-3600 s (default 10) | s | Write | |
| AVmin | 10 | EnergyConsumption | Current energy rate, kW or BTU/h | kW/kWh or BTU/h/BTU (per MV 4) | Read | |
| AV | 11 | EnergyAccumulationCycle1 | Accumulated energy, cycle 1 | kW/kWh or BTU/h/BTU (per MV 4) | Read | |
| AV | 12 | EnergyAccumCycleCount1 | Length of energy cycle 1 in days (default 1) | days | Write | |
| AV | 13 | EnergyAccumulationCycle2 | Accumulated energy, cycle 2 | kW/kWh or BTU/h/BTU (per MV 4) | Read | |
| AV | 14 | EnergyAccumCycleCount2 | Length of energy cycle 2 in days (default 30) | days | Write | |
| AV | 15 | EnergyLogOldestDataIndex | Index of oldest entry in the energy trend log | Read | ||
| AV | 16 | Temp1Correct | Correction value for temperature sensor 1 | °C or °F (per MV 3) | Write | |
| AV | 17 | Temp2Correct | Correction value for temperature sensor 2 | °C or °F (per MV 3) | Write | |
| AV | 18 | Pressure1 | Pressure sensor 1 (config 1, 2, 4) | kPa or psi (per MV 7) | Read | |
| AV | 19 | Pressure2 | Pressure sensor 2 (config 1, 2, 4) | kPa or psi (per MV 7) | Read | |
| AV | 20 | PressureDelta | Delta P (P1 - P2) (config 1, 2, 4) | kPa or psi (per MV 7) | Read | |
| AV | 21 | Press1Correct | Pressure sensor 1 correction | kPa or psi (per MV 7) | Write | |
| AV | 22 | Press2Correct | Pressure sensor 2 correction | kPa or psi (per MV 7) | Write | |
| AV | 23 | SystemOnCounter | Minutes the system has been on | min | Read | |
| AV | 62 | MaxFlow | Maximum flow rate; range follows the valve model | per MV 39 | Write | |
| AVmin | 68 | FlowRate | Current flow rate | per MV 39 | Read | |
| AV | 98 | MotorPosition | Motor position / valve opening | % | Read | |
| AV | 138 | ControlSigMin | Analog control signal minimum (no function) | V | Write | |
| AV | 139 | ControlSigMax | Analog control signal maximum (no function) | V | Write | |
| AV | 140 | BatteryCapacity | Actuator battery capacity (config 1) | % | Read | |
| AVmin | 141 | AnalogControlSignal | Analog control signal value, % | % | Write | |
| AV | 143 | BACnetFallbackTimeout | BACnet control fallback timeout, 1-60 min (config 1) | min | Write | |
| AV | 164 | FeedbackSignal | Feedback signal value (no function) | V | Read | |
| AV | 165 | WaterT1 | T1 written back to actuator display (config 1) | °C | Write | |
| AV | 166 | WaterT2 | T2 written back to actuator display (config 1) | °C | Write | |
| AV | 167 | WaterdT | Delta T written back to actuator display (config 1) | °C | Write | |
| AV | 168 | dP | Delta P written back to actuator display (config 1) | kPaD | Write | |
| BV | 1 | PressureDeltaAlarm | Delta P alarm (config 1, 2, 4) | Read | 0=OFF, 1=ON | |
| BV | 2 | RestartUnit | Restart unit | Write | 0=Not activate, 1=Activated | |
| BV | 3 | ActuatorCommsReset | Restart comms port to the attached actuator | Write | 0=Disabled, 1=Enabled | |
| BV | 4 | EnergyAccumulationReset | Reset accumulated energy log | Write | 0=Disabled, 1=Enabled | |
| BV | 17 | RotationDirection | Motor rotation direction | Write | 0=NO, 1=NC | |
| BV | 18 | FailsafeDirection | Failsafe rotation direction | Write | 0=Open, 1=Close | |
| BV | 53 | FlushMode | Flush mode enable | Write | 0=Disabled, 1=Enabled | |
| BV | 54 | Password | Password enable | Write | 0=Disabled, 1=Enabled | |
| BV | 55 | OvertorquedAlarm | Overtorqued alarm | Read | 0=Off, 1=On | |
| BV | 56 | OvertorquedInPastAlarm | Overtorqued in past alarm | Write | 0=Off, 1=On | |
| BV | 57 | OverTemperatureAlarm | Critical over temperature alarm | Read | 0=Off, 1=On | |
| BV | 58 | HighTemperatureAlarm | Uncritical high temperature alarm | Read | 0=Off, 1=On | |
| BVmin | 59 | PowerFailAlarm | Power failure / out of range alarm | Read | 0=Off, 1=On | |
| BV | 60 | NoCtrlSignalAlarm | No control signal alarm | Read | 0=Off, 1=On | |
| BV | 61 | BattErrorAlarm | Battery error alarm | Read | 0=Off, 1=On | |
| BVmin | 62 | BACnetFallback-Alarm | BACnet fallback alarm | Write | 0=Off, 1=On | |
| BV | 63 | Autostroke | Start auto-stroke; returns to 0 when done | Write | 0=Disabled, 1=Enabled | |
| MV | 1 | Baud Rate | FIT baud rate | Write | 1=9600, 2=19200, 3=38400, 4=57600, 5=76800, 6=115200 | |
| MV | 2 | MS/TP MAC Address | FIT MS/TP MAC address, 0-127 | Write | ||
| MV | 3 | Temperature | FIT workable temperature units | Write | 1=°C, 2=°F | |
| MV | 4 | Energy Units | FIT workable energy units | Write | 1=BTU and BTU/h, 2=kWh and kW | |
| MVmin | 5 | Flow Control | Control strategy: delta T, comfort (flow) or smart | Write | 1=ΔT Control (Delta T Target), 2=Comfort Control (Set Flow), 3=Smart Control (Room temp. in combi with ΔT), 4=ΔT Control 90% close, 5=Smart Control 90% close | |
| MV | 6 | Configuration | FIT system configuration (actuator/sensor set) | Write | 1=SM.0.0.0.5/6, 2=SM.0.0.0.3/4, 3=FN/FH w/o pressure sensors, 4=FN/FH w pressure sensors | |
| MV | 7 | Pressure Units | FIT workable pressure unit | Write | 1=kPa, 2=psi | |
| MV | 8 | ValveModelG | Valve model, FlowCon Green (config 3 and 4) | Write | 1=Green.0, 2=Green.1, 3=Green.2, 4=Green.3 | |
| MV | 38 | ValveModel | Valve model, FlowCon SM (config 1 and 2) | Write | 1=SM.0.0, 2=SM.1.1, 3=SM.2.1, 4=SM.3.0, 5=SM.3.1, 6=SM.3.2, 7=SM.4.1, 8=SM.4.2, 9=SM.4.3, 10=SM.5.1, 11=SM.5.2, 12=SM.6.2 | |
| MV | 39 | FlowScaleUnit | Flow scale unit | Write | 1=l/sec, 2=GPM, 3=l/hr | |
| MV | 40 | ControlSignalMode | Control signal mode; only BACnet is valid | Read | 1=2-10VDC, 2=4-20mA, 3=Digital, 4=BACnet | |
| MV | 41 | FeedbackSignalMode | Feedback signal mode (no function) | Read | 1=2-10VDC, 2=0-10VDC, 3=4-20mA, 4=Auto | |
| MV | 43 | BACnetFallbackAction | Actuator action on BACnet fallback (config 1) | Read | 1=Close, 2=Stop, 3=Open, 4=Midway | |
| MV | 44 | PressureRange_kPaD | PICV pressure range (kPaD) for the valve in MV 38 | Read | 1=NA (SM.0.0), 2=32-320 (SM.1.1), 3=40-320 (SM.2.1), 4=30-800 (SM.3.0), 5=30-800 (SM.3.1), 6=35-800 (SM.3.2), 7=30-800 (SM.4.1), 8=35-800 (SM.4.2), 9=50-800 (SM.4.3), 10=30-800 (SM.5.1), 11=35-800 (SM.5.2), 12=35-800 (SM.6.2) | |
| MV | 45 | ActuatorState | Actuator operating state (config 1) | Read | 1=Normal, 2=Calibration, 3=Flush, 4=Auto-stroke, 5=Alarm, 6=Failsafe | |
| MV | 46 | ControlCurveMode | Actuator control curve; only linear flow is valid | Write | 1=Linear flow, 2=Equal%, 3=Linear rotation, 4=Linear signal | |
| CSV | 1 | Bluetooth Ad Name | Bluetooth advertised name (default FlowCon FIT) | Write | ||
| TL | 1 | Energy data | Daily energy trend log, 1200 entries, rollover | Read |
No points match these filters.
Object ID lookup: FlowCon FIT / Energy FIT intelligent interface point IDs by name
AV1WaterTemperature1AV2WaterTemperature2AV3WaterTempDeltaAV4WaterTempDeltaTargetAV5WaterTempDeltaDeadbandAV6RoomTemperatureAV7RoomTargetTempAV8RoomTargetDeadbandAV9TargetEvalIntervalAV10EnergyConsumptionAV11EnergyAccumulationCycle1AV12EnergyAccumCycleCount1AV13EnergyAccumulationCycle2AV14EnergyAccumCycleCount2AV15EnergyLogOldestDataIndexAV16Temp1CorrectAV17Temp2CorrectAV18Pressure1AV19Pressure2AV20PressureDeltaAV21Press1CorrectAV22Press2CorrectAV23SystemOnCounterAV62MaxFlowAV68FlowRateAV98MotorPositionAV138ControlSigMinAV139ControlSigMaxAV140BatteryCapacityAV141AnalogControlSignalAV143BACnetFallbackTimeoutAV164FeedbackSignalAV165WaterT1AV166WaterT2AV167WaterdTAV168dPBV1PressureDeltaAlarmBV2RestartUnitBV3ActuatorCommsResetBV4EnergyAccumulationResetBV17RotationDirectionBV18FailsafeDirectionBV53FlushModeBV54PasswordBV55OvertorquedAlarmBV56OvertorquedInPastAlarmBV57OverTemperatureAlarmBV58HighTemperatureAlarmBV59PowerFailAlarmBV60NoCtrlSignalAlarmBV61BattErrorAlarmBV62BACnetFallback-AlarmBV63AutostrokeMV1Baud RateMV2MS/TP MAC AddressMV3TemperatureMV4Energy UnitsMV5Flow ControlMV6ConfigurationMV7Pressure UnitsMV8ValveModelGMV38ValveModelMV39FlowScaleUnitMV40ControlSignalModeMV41FeedbackSignalModeMV43BACnetFallbackActionMV44PressureRange_kPaDMV45ActuatorStateMV46ControlCurveModeCSV1Bluetooth Ad NameTL1Energy data
Integration notes
- Several objects only work in certain configurations (MV 6); the PICS marks them "Works in config. ...".
- AV 138, AV 139, AV 164 and MV 41 are printed as no function.
- AV 165-168 are values FIT writes back to the actuator display; FIT overwrites them.
- TL 1 is a daily energy trend log with 1200 entries that rolls over.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the FIT / Energy FIT intelligent interface (ACC40023) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the FlowCon FIT / Energy FIT intelligent interface (ACC40023)
How many BACnet points does the FlowCon FIT / Energy FIT intelligent interface (ACC40023) have?
This list has 71 BACnet objects: 36 analog values, 17 binary values, 16 multi-state values, 1 trend log, 1 characterstring value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which FlowCon FIT / Energy FIT intelligent interface (ACC40023) BACnet points are writable?
43 of the 71 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official FlowCon FIT / Energy FIT intelligent interface (ACC40023) BACnet documentation?
The source is Protocol Implementation Conformance Statement (PICS) for FlowCon FIT, revision 2026-06-26, published free by FlowCon at https://flowcon.com/fileadmin/user_upload/Pdf/Certificates/BACnet_PICS/FlowCon-BACnet-PICS-Statement-FlowCon-FIT.pdf.
What are the minimum BACnet points to integrate the FlowCon FIT / Energy FIT intelligent interface (ACC40023)?
Start with MV 5 Flow Control (Control strategy (delta T, comfort, smart)); AV 141 AnalogControlSignal (Control signal, %); AV 4 WaterTempDeltaTarget (Delta T target); AV 7 RoomTargetTemp (Room temperature target); AV 6 RoomTemperature (Room temperature from the BMS); AV 68 FlowRate (Current flow rate); AV 3 WaterTempDelta (Delta T); AV 10 EnergyConsumption (Current energy rate); BV 62 BACnetFallback-Alarm (BACnet fallback active); BV 59 PowerFailAlarm (Power failure alarm).
How do I enable BMS control of the FlowCon FIT / Energy FIT intelligent interface (ACC40023)?
MV 5 picks how FIT controls the valve: 1/4 delta T target, 2 comfort (set flow), 3/5 smart (room temperature with delta T).
Does the FlowCon FIT / Energy FIT intelligent interface (ACC40023) need a BACnet heartbeat or have a communication timeout?
AV 143 sets the BACnet control fallback timeout (1-60 min, config 1); MV 43 shows the fallback action and BV 62 flags it.
Can the BMS supply sensor values to the FlowCon FIT / Energy FIT intelligent interface (ACC40023)?
Room temperature AV 6 and its target AV 7 are writable for the comfort and smart modes.
How do I check these points on the real FIT / Energy FIT intelligent interface (ACC40023)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More FlowCon BACnet points lists
- Valve actuator (PICV)
FlowCon FH-BUS / FN.0.2-BUS PICV actuator
FlowCon FH-BUS actuator (FlowCon Green.3 PICV) and FN.0.2-BUS actuator (FlowCon Green and GreEQ PICVs) with BACnet MS/TP.
Also known as: FH-BUS, FN.0.2-BUS, FN02-BUS, FlowCon FH actuator, FlowCon FN actuator, FlowCon Green.3 actuator, FlowCon GreEQ actuator - Valve actuator (PICV)
FlowCon SM.0.0.1.5 / SM.0.0.1.6 actuator (FlowCon SM PICV)
FlowCon SM.0.0.1.5 and SM.0.0.1.6 (fail-safe) actuators for FlowCon SM large pressure-independent control valves, BACnet MS/TP.
Also known as: SM.0.0.1.5, SM.0.0.1.6, FlowCon SM actuator, FlowCon SM-1516
Source: Protocol Implementation Conformance Statement (PICS) for FlowCon FIT · rev. 2026-06-26. Object names, instances and units are reproduced as published; descriptions are our own.