Air handling / make-up air unit controller (BMS command points) · BACnet points list

Engineered Air CenCon_SW EMS Command Device (CenCon controller) BACnet points list

Updated 6 November 2026

Short answer

CenCon is Engineered Air's unit controller, with BACnet MS/TP (19200 or 38400 baud), BACnet IP and Modbus RTU. It works as a virtual BACnet gateway, and CenCon_SW (device Gateway ID + 55) is the software device that holds every writable EMS point: the fan start enable, module enables, dehumidification, reheat, pre-cool and economizer overrides, the discharge, DX, humidity and damper setpoints and the XP_XM spare outputs. It also reports the heating, cooling, humidification, recovery, dehumidification, reheat and pre-cool demands.

This page lists 50 BACnet objects for the Engineered Air CenCon_SW EMS Command Device (CenCon controller) — 42 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Engineered Air’s own free documentation, linked below.

Manufacturer
Engineered Air
Model
CenCon_SW EMS Command Device (CenCon controller)
Equipment
Air handling / make-up air unit controller (BMS command points)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
50 (42 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
CenCon version 3.0.0 or higher
Default device instance
Gateway ID + 55 (default Gateway ID 270000, so 270055)
Also known as
CenCon, CenCon_SW, CenCon SW, IOM65, EngA CenCon
Source document
CenCon Communication Manual for Modbus and BACnet (MSTP and IP) · IOM65 R106 · rev. 2025-05
Download CSV 50 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Engineered Air’s current documentation and the live device before use. Not official Engineered Air information. Terms of use.

BMS integration notes: Engineered Air CenCon_SW EMS Command Device (CenCon controller)

Integration in brief

Set the Gateway ID, MAC and baud (MS/TP) or IP settings on the CenCon service display, save and cycle power. On the CenCon_SW device (Gateway ID + 55) write EMS_Fan_Enable to start the unit and Discharge_Air_Setpoint in tenths of °F, at priority 3-7. Read the demand AIs here and the sensors, fan and alarm status from the CenCon device.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 0EMS_Fan_EnableStart/enable commandCommand
AO 0Discharge_Air_SetpointDischarge air setpoint, tenths of °F (780 = 78 °F)Command
AO 1Damper_Minimum_PositionOA damper minimum position, mVCommand
AI 0Heating_DemandHeating demand, %Read
AI 1Cooling_DemandCooling demand, %Read

Enable & remote start

EMS_Fan_Enable (BO 0) is the BMS start enable. Separate binaries enable each expansion module (cooling, gas heat, humidifier, electric heat, energy recovery), dehumidification, maximum reheat and pre-cool; EMS_Economizer_Disable turns off the economizer.

Network setup

Watch out for

Engineered Air CenCon_SW EMS Command Device (CenCon controller) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

50 of 50 shown
Type
Access
Show
Engineered Air CenCon_SW EMS Command Device (CenCon controller) BACnet Points List
DescriptionStates
AOmin0Discharge_Air_SetpointDischarge air setpoint, sent x10 (780 = 78.0 °F)°FCommand
AOmin1Damper_Minimum_PositionOA damper minimum position signal, mV (0-10000)mVCommand
AO3Humidification_Setpoint%Command
AO4Dehumidification_Setpoint%Command
AO5DX_SetpointDX leaving temperature setpoint, sent x10°FCommand
AO6EMS_XP_XM_MODULE_1_AO1_VOLTAGEmVCommand
AO7EMS_XP_XM_MODULE_1_AO2_VOLTAGEmVCommand
AO8EMS_XP_XM_MODULE_2_AO1_VOLTAGEmVCommand
AO9EMS_XP_XM_MODULE_2_AO2_VOLTAGEmVCommand
AO10EMS_XP_XM_MODULE_3_AO1_VOLTAGEmVCommand
AO11EMS_XP_XM_MODULE_3_AO2_VOLTAGEmVCommand
AO12EMS_XP_XM_MODULE_4_AO1_VOLTAGEmVCommand
AO13EMS_XP_XM_MODULE_4_AO2_VOLTAGEmVCommand
AO14EMS_Econ_MA_SetpointEconomizer mixed air setpointmVCommand
BOmin0EMS_Fan_EnableStart enable for system operationCommand
BO1EMS_C_XM_EnableCommand
BO2EMS_J_XM_EnableCommand
BO3EMS_G_XM_EnableCommand
BO4EMS_M_XM_EnableCommand
BO5EMS_S_XM_EnableCommand
BO6EMS_H_XM_EnableCommand
BO7EMS_ER_XM_EnableCommand
BO8EMS_Dehum_EnableEnable dehumidification (cooling with reheat units)Command
BO9EMS_Reheat_EnableOverride to maximum reheatCommand
BO10EMS_XP_XM_MODULE_1_DO1_EnableCommand
BO11EMS_XP_XM_MODULE_1_DO2_EnableCommand
BO12EMS_XP_XM_MODULE_1_DO3_EnableCommand
BO13EMS_XP_XM_MODULE_1_DO4_EnableCommand
BO14EMS_XP_XM_MODULE_2_DO1_EnableCommand
BO15EMS_XP_XM_MODULE_2_DO2_EnableCommand
BO16EMS_XP_XM_MODULE_2_DO3_EnableCommand
BO17EMS_XP_XM_MODULE_2_DO4_EnableCommand
BO18EMS_XP_XM_MODULE_3_DO1_EnableCommand
BO19EMS_XP_XM_MODULE_3_DO2_EnableCommand
BO20EMS_XP_XM_MODULE_3_DO3_EnableCommand
BO21EMS_XP_XM_MODULE_3_DO4_EnableCommand
BO22EMS_XP_XM_MODULE_4_DO1_EnableCommand
BO23EMS_XP_XM_MODULE_4_DO2_EnableCommand
BO24EMS_XP_XM_MODULE_4_DO3_EnableCommand
BO25EMS_XP_XM_MODULE_4_DO4_EnableCommand
BO26EMS_PRECOOL_C_XM_EnableEnable pre-cool if fittedCommand
BO27EMS_Economizer_DisableDisable economizer if fittedCommand
AImin0Heating_Demand%Read
AImin1Cooling_Demand%Read
AI2Humidification_Demand%Read
AI3Recovery_Demand%Read
AI4Dehumidification_Demand%Read
AI5Modulating_Reheat_Demand%Read
AI6Pre-Cool_Demand%Read
BI0Wheel_Rotation_PresentEnergy recovery wheel rotation detectedRead
Object ID lookup: Engineered Air CenCon_SW EMS Command Device point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CenCon_SW EMS Command Device (CenCon controller) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Engineered Air CenCon_SW EMS Command Device (CenCon controller)

How many BACnet points does the Engineered Air CenCon_SW EMS Command Device (CenCon controller) have?

This list has 50 BACnet objects: 7 analog inputs, 14 analog outputs, 1 binary input, 28 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Engineered Air CenCon_SW EMS Command Device (CenCon controller) BACnet points are writable?

42 of the 50 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Engineered Air CenCon_SW EMS Command Device (CenCon controller) BACnet documentation?

The source is CenCon Communication Manual for Modbus and BACnet (MSTP and IP) (IOM65 R106), revision 2025-05, published free by Engineered Air at https://www.engineeredair.com/wp-content/uploads/2025/07/CenCon-Communication-R106-2025-07-optimized.pdf.

What are the minimum BACnet points to integrate the Engineered Air CenCon_SW EMS Command Device (CenCon controller)?

Start with BO 0 EMS_Fan_Enable (Start/enable command); AO 0 Discharge_Air_Setpoint (Discharge air setpoint, tenths of °F (780 = 78 °F)); AO 1 Damper_Minimum_Position (OA damper minimum position, mV); AI 0 Heating_Demand (Heating demand, %); AI 1 Cooling_Demand (Cooling demand, %).

How do I enable BMS control of the Engineered Air CenCon_SW EMS Command Device (CenCon controller)?

EMS_Fan_Enable (BO 0) is the BMS start enable. Separate binaries enable each expansion module (cooling, gas heat, humidifier, electric heat, energy recovery), dehumidification, maximum reheat and pre-cool; EMS_Economizer_Disable turns off the economizer.

How do I check these points on the real CenCon_SW EMS Command Device (CenCon controller)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Engineered Air BACnet points lists

Source: CenCon Communication Manual for Modbus and BACnet (MSTP and IP) · IOM65 R106 · rev. 2025-05. Object names, instances and units are reproduced as published; descriptions are our own.