Air handling / make-up air unit controller (I/O and expansion modules) · BACnet points list

Engineered Air CenCon Controller and Expansion Modules (I/O devices) BACnet points list

Updated 6 November 2026

Short answer

CenCon is Engineered Air's unit controller, with BACnet MS/TP (19200 or 38400 baud), BACnet IP and Modbus RTU. It works as a virtual BACnet gateway: the CenCon device (Gateway ID + 1) reports the main sensors, analog outputs, fan, damper and alarm relays and the safety inputs, and each fitted expansion module (DX cooling, indirect and direct gas heat, gas humidifier, energy recovery wheel, electric heat, spare I/O, combustion blower and pressure) appears as its own device. All objects here are read-only; commands go to the CenCon_SW device.

This page lists 152 BACnet objects for the Engineered Air CenCon Controller and Expansion Modules (I/O devices) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Engineered Air’s own free documentation, linked below.

Manufacturer
Engineered Air
Model
CenCon Controller and Expansion Modules (I/O devices)
Equipment
Air handling / make-up air unit controller (I/O and expansion modules)
Equipment type
Rooftop units, AHUs & DOAS
BACnet objects
152 (0 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
CenCon version 3.0.0 or higher
Default device instance
CenCon = Gateway ID + 1 (default 270001); modules Gateway ID + 2 to + 31
Also known as
CenCon, IOM65, C_XM, J_XM, G_XM, M_XM, ER_XM, S_XM, XP_XM, H_XM, CD_XM, P_XM, EngA CenCon
Source document
CenCon Communication Manual for Modbus and BACnet (MSTP and IP) · IOM65 R106 · rev. 2025-05
Download CSV 152 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Engineered Air’s current documentation and the live device before use. Not official Engineered Air information. Terms of use.

BMS integration notes: Engineered Air CenCon Controller and Expansion Modules (I/O devices)

Integration in brief

These devices are read-only: start the unit and write setpoints on CenCon_SW. From the CenCon device read the supply fan and alarm relays, air proving, discharge, return and ambient temperatures, and the module devices for staging and flame/safety status.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BO 2SASupply fan output onRead
BI 2FbBAir proving switchRead
BI 5OCCOccupied/unoccupied inputRead
AI 20DADischarge air temperature, tenths of °FRead
AI 16RAReturn/room temperature, tenths of °FRead
AI 19AAAmbient air temperature, tenths of °FRead
BO 4ALAlarm outputRead

Enable & remote start

Commands are not on these devices; use EMS_Fan_Enable and the module enables on the CenCon_SW device (Gateway ID + 55).

Network setup

Watch out for

Engineered Air CenCon Controller and Expansion Modules (I/O devices) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

152 of 152 shown
Type
Show
Engineered Air CenCon Controller and Expansion Modules (I/O devices) BACnet Points List
DescriptionStates
AO2MCW[CenCon] Modulating CoolingmVRead
AO1MEC[CenCon] Modulating EconomizermVRead
AO0MHW[CenCon] Modulating HeatingmVRead
AO3MSP[CenCon] VFD Command SpeedmVRead
AI6RPM[CenCon] VFD Feedback SpeedmVRead
AI0IAQ[CenCon] IAQ SensormVRead
AI2HuO[CenCon] Outside HumiditymVRead
AI5HR_Pos[CenCon] Dehumidification SPmVRead
AI7FbD[CenCon] Feedback DampermVRead
BI4DES[CenCon] Damper End SwitchRead
BOmin4AL[CenCon] AlarmRead
BOmin2SA[CenCon] Supply AirRead
BO1DM[CenCon] Damper ActuatorRead
BImin5OCC[CenCon] Occupied/UnoccupiedRead
BI6TCB[CenCon] Time Clock BypassRead
BI7EnF[CenCon] Enable FanRead
BI0ALi[CenCon] Secondary BACnet AlarmRead
AI18MA[CenCon] Mixed Air Temperature; value x10°FRead
AImin20DA[CenCon] Discharge Air Temperature; value x10°FRead
AImin19AA[CenCon] Ambient Air Temperature; value x10°FRead
AImin16RA[CenCon] Return/Room Temperature; value x10°FRead
AI8W_Pos[CenCon] Modulating Room ThermostatmVRead
AI9ASP[CenCon] Remote VFD SetpointmVRead
AI17DX[CenCon] DX Coil Temperature; value x10°FRead
BI8DHC[CenCon] DehumidificationRead
BI3BYP[CenCon] VFD BypassRead
AI1DPr[CenCon] (FUTURE)Read
AI4Y_Pos[CenCon] DX Setpoint ResetmVRead
BImin2FbB[CenCon] Air Proving SwitchRead
BI1OLF[CenCon] Economizer DisableRead
AI3HuR[CenCon] Return/Room HumiditymVRead
AO0MCp[C_XM] Modulating CompressormVRead
AO1MF1[C_XM] Modulating Condenser Fan #1mVRead
AO2MF2[C_XM] Modulating Condenser Fan #2mVRead
AO3MRh[C_XM] Modulating ReheatmVRead
BO0C1a[C_XM] Cooling stage #1Read
BO1C2a[C_XM] Cooling stage #2Read
BO2C3a[C_XM] Cooling stage #3Read
BO3C4a[C_XM] Cooling stage #4Read
BO4C5a[C_XM] Cooling stage #5Read
BO5C6a[C_XM] Cooling stage #6Read
BO6F1b[C_XM] Condenser Fan Stage #1Read
BO7F2b[C_XM] Condenser Fan Stage #2Read
BO8R1b[C_XM] Stepped Reheat Stage #1Read
BO9R2b[C_XM] Stepped Reheat Stage #2Read
AI20CW[C_XM] Pre Cool DX Temperature; value x10°FRead
BI0EnH[C_XM] Enable Reheat OverrideRead
BI1EnC[C_XM] Enable CoolingRead
AI2FbG[J_XM] Feedback GasmVRead
AO0MBV[J_XM] Modulating Ball ValvemVRead
BI2CAS[J_XM] Combustion Air SwitchRead
BI0BFS[J_XM] Blocked Flue SwitchRead
BI1EnH[J_XM] Enable HeatRead
BO4PV[J_XM] Pilot ValveRead
BO5SR[J_XM] Safety RelayRead
BO6FR[J_XM] Flame RelayRead
BI4HL[J_XM] High LimitRead
AI4CP[J_XM] Condensate ProbeRead
AO4MX[J_XM] MX ValvemVRead
BI3FbV[J_XM] Gas Valve FeedbackRead
AI2FbG[G_XM] Feedback GasmVRead
AI3FbA[G_XM] Feedback AirmVRead
AO0MBV[G_XM] Modulating Ball ValvemVRead
AO1MCA[G_XM] Modulating Combustion AirmVRead
BI2CAS[G_XM] Combustion Air SwitchRead
BI0BFS[G_XM] Blocked Flue SwitchRead
BI1EnH[G_XM] Enable HeatRead
BO0CB[G_XM] Combustion BlowerRead
BO4PV[G_XM] Pilot ValveRead
BO5SR[G_XM] Safety RelayRead
BO6FR[G_XM] Flame RelayRead
BI4HL[G_XM] High LimitRead
AI4CP[G_XM] Condensate ProbeRead
BI3FbV[G_XM] Gas Valve FeedbackRead
AI2FbG[M_XM] Feedback GasmVRead
AO0MBV[M_XM] Modulating Ball ValvemVRead
AO1MPP[M_XM] Profile Pressure ActuatormVRead
BI0HiE[M_XM] High Speed EnableRead
BI1EnH[M_XM] Enable HeatRead
BO0HiS[M_XM] High SpeedRead
BO1Exl[M_XM] Exhaust Fan InterlockRead
BO2DFR[M_XM] Dual Flame RodRead
BO3WPu[M_XM] Water PumpRead
BO4PV[M_XM] Pilot ValveRead
BO5SR[M_XM] Safety RelayRead
BO6FR[M_XM] Flame RelayRead
BI4FL[M_XM] High LimitRead
AO4MX[M_XM] MX ValvemVRead
BI3FbV[M_XM] Gas Valve FeedbackRead
AO0MFr[ER_XM] Modulating Bypass DampermVRead
AO1MER[ER_XM] Modulating Energy RecoverymVRead
BI0EnH[ER_XM] Enable HeatRead
BI1RoT[ER_XM] Rotation SensorRead
BO0ByD[ER_XM] Bypass DamperRead
BO4ERC[ER_XM] Enable WheelRead
AI19LA[ER_XM] Leaving Air Temperature; value x10°FRead
AI20EA[ER_XM] Exhaust Air Temperature; value x10°FRead
AI0DH_Pos[ER_XM] Leaving Air SetpointmVRead
AI2FbG[S_XM] Feedback GasmVRead
AI3MHL[S_XM] Modulating High LimitmVRead
AO0MBV[S_XM] Modulating Ball ValvemVRead
BI2DHL[S_XM] Duct High LimitRead
BI0BFS[S_XM] Blocked Flue SwitchRead
BI1EnH[S_XM] Enable HeatRead
BO0FV[S_XM] Fill ValveRead
BO1MV[S_XM] Mixing ValveRead
BO2DV[S_XM] Drain ValveRead
BO3FVS[S_XM] Fill Valve SideRead
BO4PV[S_XM] Pilot ValveRead
BO5SR[S_XM] Safety RelayRead
BO6FR[S_XM] Flame RelayRead
BI4HL[S_XM] High LimitRead
AI0DH_Pos[S_XM] Humidity SignalmVRead
AI15Dn[S_XM] Drain Sensor; value x10°FRead
AI4CP[S_XM] Condensate ProbekΩRead
AI6FWP[S_XM] Fill Water ProbekΩRead
AI5LWP[S_XM] Low Water ProbekΩRead
AO4MX[S_XM] MX ValvemVRead
BI3FbV[S_XM] Gas Valve FeedbackRead
AI3S1[XP_XM] value x10°FRead
AI4S2[XP_XM] value x10°FRead
AI1AI1[XP_XM]Read
AI2AI2[XP_XM]Read
AI3AI3[XP_XM]Read
AI4AI4[XP_XM]Read
AO1AO1[XP_XM]Read
AO2AO2[XP_XM]Read
BI0DI1[XP_XM]Read
BI1DI2[XP_XM]Read
BI2DI3[XP_XM]Read
BI3DI4[XP_XM]Read
BO0DO1[XP_XM]Read
BO1DO2[XP_XM]Read
BO2DO3[XP_XM]Read
BO3DO4[XP_XM]Read
BI0EnH[H_XM] Enable HeatRead
BO0H1a[H_XM] Heating Stage #1Read
BO1H2a[H_XM] Heating Stage #2Read
BO2H3a[H_XM] Heating Stage #3Read
BO3H4a[H_XM] Heating Stage #4Read
BO4H5b[H_XM] Heating Stage #5Read
BO5H6c[H_XM] Heating Stage #6 (Ambient stage #1)Read
BO6H7d[H_XM] Heating Stage #7 (Ambient stage #2)Read
BI3DSw[H_XM] Door SwitchRead
BI4HL[H_XM] High LimitRead
BO0CB[CD_XM] Combustion Blower EnableRead
AI1Current RPM[CD_XM] Current RPMRPMRead
AI0Filtered RPM[CD_XM] Filtered RPMRPMRead
AO0RPM SP[CD_XM] Combustion Blower RPM SetpointRPMRead
AI0Current_Pressure[P_XM] Current Pressurein. w.c.Read
AI2Filtered_Pressure[P_XM] Filtered Pressurein. w.c.Read
AO0Pressure_Setpoint[P_XM] Pressure Setpoint (FUTURE)in. w.c.Read
Object ID lookup: Engineered Air CenCon Controller and Expansion Modules point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the CenCon Controller and Expansion Modules (I/O devices) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Engineered Air CenCon Controller and Expansion Modules (I/O devices)

How many BACnet points does the Engineered Air CenCon Controller and Expansion Modules (I/O devices) have?

This list has 152 BACnet objects: 42 analog inputs, 23 analog outputs, 39 binary inputs, 48 binary outputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Engineered Air CenCon Controller and Expansion Modules (I/O devices) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official Engineered Air CenCon Controller and Expansion Modules (I/O devices) BACnet documentation?

The source is CenCon Communication Manual for Modbus and BACnet (MSTP and IP) (IOM65 R106), revision 2025-05, published free by Engineered Air at https://www.engineeredair.com/wp-content/uploads/2025/07/CenCon-Communication-R106-2025-07-optimized.pdf.

What are the minimum BACnet points to integrate the Engineered Air CenCon Controller and Expansion Modules (I/O devices)?

Start with BO 2 SA (Supply fan output on); BI 2 FbB (Air proving switch); BI 5 OCC (Occupied/unoccupied input); AI 20 DA (Discharge air temperature, tenths of °F); AI 16 RA (Return/room temperature, tenths of °F); AI 19 AA (Ambient air temperature, tenths of °F); BO 4 AL (Alarm output).

How do I enable BMS control of the Engineered Air CenCon Controller and Expansion Modules (I/O devices)?

Commands are not on these devices; use EMS_Fan_Enable and the module enables on the CenCon_SW device (Gateway ID + 55).

How do I check these points on the real CenCon Controller and Expansion Modules (I/O devices)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Engineered Air BACnet points lists

Source: CenCon Communication Manual for Modbus and BACnet (MSTP and IP) · IOM65 R106 · rev. 2025-05. Object names, instances and units are reproduced as published; descriptions are our own.