Power and energy meter (submeter) · BACnet points list

Elkor WattsOn-Mark II -M2 power meter (BACnet MS/TP) BACnet points list

Updated 6 November 2026

Short answer

The -M2 version of the WattsOn-Mark II replaces the Modbus/RTU port with native BACnet MS/TP. It exposes 87 read-only Analog Inputs (totals and per-phase power, voltage, current, power factor, angles, energy by quadrant and device info) and 42 writable Analog Values for CT/PT ratios, demand window, relay alarms, locking and energy reset. The instance scheme is not the same as the -E4 BACnet IP version.

This page lists 129 BACnet objects for the Elkor WattsOn-Mark II -M2 power meter (BACnet MS/TP) — 42 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Elkor’s own free documentation, linked below.

Manufacturer
Elkor
Model
WattsOn-Mark II -M2 power meter (BACnet MS/TP)
Equipment
Power and energy meter (submeter)
Equipment type
Thermostats, sensors & meters
BACnet objects
129 (42 writable)
Transport
BACnet MS/TP
Firmware
Firmware V10.60, application V1.300 (PICS, November 2015)
Default device instance
28xxxxx (xxxxx = serial number)
Also known as
WattsOn-Mark II, W2-M2, WattsOn Mk II BACnet MS/TP, Elkor WattsOn BACnet MS/TP
Source document
WattsOn-Mark II BACnet MS/TP (-M2) Addendum · rev. 2015-11 (Revision 1)
Download CSV 129 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Elkor’s current documentation and the live device before use. Not official Elkor information. Terms of use.

BMS integration notes: Elkor WattsOn-Mark II -M2 power meter (BACnet MS/TP)

Integration in brief

Set the MAC, baud and device instance, then write the CT and PT ratios (AV 0-15) to match the installation. Read total kW, imported kWh, demand, power factor, average current and voltage.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 4kW_TotalTotal real power, kWRead
AI 45kWh_Import_TtlImported energy total, kWhRead
AI 43kWh_Net_TtlNet energy total, kWhRead
AI 42kW_DemandSliding-window kW demandRead
AI 10PF_TotalTotal power factorRead
AI 9Current_AvgAverage current, ARead
AI 7Volts_LN_AvgAverage line-to-neutral voltage, VRead
AI 11FrequencyLine frequency, HzRead

Network setup

Watch out for

Elkor WattsOn-Mark II -M2 power meter (BACnet MS/TP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

129 of 129 shown
Type
Access
Show
Elkor WattsOn-Mark II -M2 power meter (BACnet MS/TP) BACnet Points List
DescriptionStates
AI1UptimeTime since power-upsRead
AImin4kW_TotalkWRead
AI5kVAR_TotalkvarRead
AI6kVA_TotalkVARead
AImin7Volts_LN_AvgVRead
AI8Volts_LL_AvgVRead
AImin9Current_AvgARead
AImin10PF_TotalRead
AImin11FrequencyHzRead
AI12Volts_Angle_Avg°Read
AI13Quadrant_TotalRead
AI14Volts_ANVRead
AI15Volts_BNVRead
AI16Volts_CNVRead
AI17Volts_ABVRead
AI18Volts_BCVRead
AI20Volts_ACVRead
AI21Current_AARead
AI22Current_BARead
AI23Current_CARead
AI24kW_AkWRead
AI25kW_BkWRead
AI26kW_CkWRead
AI27kVAR_AkvarRead
AI28kVAR_BkvarRead
AI29kVAR_CkvarRead
AI30kVA_AkVARead
AI31kVA_BkVARead
AI32kVA_CkVARead
AI33PF_ARead
AI34PF_BRead
AI35PF_CRead
AI36Volts_Angle_AB°Read
AI37Volts_Angle_BC°Read
AI38Volts_Angle_AC°Read
AI39Quadrant_ARead
AI40Quadrant_BRead
AI41Quadrant_CRead
AImin42kW_DemandkWRead
AImin43kWh_Net_TtlkWhRead
AI44kVAh_Net_TtlkVAhRead
AImin45kWh_Import_TtlkWhRead
AI46kWh_Export_TtlkWhRead
AI47kVAh_Import_TtlkVAhRead
AI48Q1_VARh_TtlkvarhRead
AI49Q2_VARh_TtlkvarhRead
AI50Q3_VARh_TtlkvarhRead
AI51Q4_VARh_TtlkvarhRead
AI52Q1+Q2_VARh_TtlkvarhRead
AI53Q3+Q4_VARh_TtlkvarhRead
AI54kWh_Net_AkWhRead
AI55kWh_Net_BkWhRead
AI56kWh_Net_CkWhRead
AI57kVA_Net_AkVAhRead
AI58kVA_Net_BkVAhRead
AI59kVA_Net_CkVAhRead
AI60kWh_Import_AkWhRead
AI61kWh_Import_BkWhRead
AI62kWh_Import_CkWhRead
AI63kWh_Export_AkWhRead
AI64kWh_Export_BkWhRead
AI65kWh_Export_CkWhRead
AI66kVA_Import_AkVAhRead
AI67kVA_Import_BkVAhRead
AI68kVA_Import_CkVAhRead
AI69kVA_Export_AkVAhRead
AI70kVA_Export_BkVAhRead
AI71kVA_Export_CkVAhRead
AI72kVARh_Q1_AkvarhRead
AI73kVARh_Q1_BkvarhRead
AI74kVARh_Q1_CkvarhRead
AI75kVARh_Q2_AkvarhRead
AI76kVARh_Q2_BkvarhRead
AI77kVARh_Q2_CkvarhRead
AI78kVARh_Q3_AkvarhRead
AI79kVARh_Q3_BkvarhRead
AI80kVARh_Q3_CkvarhRead
AI81kVARh_Q4_AkvarhRead
AI82kVARh_Q4_BkvarhRead
AI83kVARh_Q4_CkvarhRead
AV0CT_Primary_AllCT primary for all three phasesWrite
AV1CT_Secondary_AllCT secondary for all three phasesWrite
AV2CT_Primary_AWrite
AV3CT_Secondary_AWrite
AV4CT_Primary_BWrite
AV5CT_Secondary_BWrite
AV6CT_Primary_CWrite
AV7CT_Secondary_CWrite
AV8PT_Primary_AllPT primary for all three phasesWrite
AV9PT_Secondary_AllPT secondary for all three phasesWrite
AV10PT_Primary_AWrite
AV11PT_Secondary_AWrite
AV12PT_Primary_BWrite
AV13PT_Secondary_BWrite
AV14PT_Primary_CWrite
AV15PT_Secondary_CWrite
AV16Phase_Comp_AllPhase compensation, all phasesWrite
AV17Phase_Comp_AWrite
AV18Phase_Comp_BWrite
AV19Phase_Comp_CWrite
AV20Window_LengthSliding-window demand sub-interval, ssWrite
AV21Window_CountNumber of sliding-window sub-intervalsWrite
AV22Window_SyncResets the sliding-window demand timerWrite
AV23Freq_AutoAuto-select voltage channel for frequencyWrite
AV24Freq_ChannelVoltage channel for frequency (0 A, 1 B, 2 C)Write
AV25PF_Sign_ModeHow the power factor sign is calculatedWrite
AI100Serial_NumberFactory serial numberRead
AI101Debug_RegisterAlways reads 1234.567 (comms check)Read
AI102Hardware_VerRead
AI103Firmware_VerRead
AI104Bootloader_VerRead
AI105Model_NumberModel code; 19762 = M2Read
AI106Input_ConfigCT type: 1 mA, 2 mV, 3 5 A, 4 Rogowski, 0 customRead
AV26K1_Reg_OffsetWrite
AV27K1_Trigger_TypeWrite
AV28K1_Upper_BoundWrite
AV29K1_Lower_BoundWrite
AV30K1_Min_DurationWrite
AV31K1_Active_ModeWrite
AV32K2_Reg_OffsetWrite
AV33K2_Trigger_TypeWrite
AV34K2_Upper_BoundWrite
AV35K2_Lower_BoundWrite
AV36K2_Min_DurationWrite
AV37K2_Active_ModeWrite
AV38PasscodePasscode entry for lock/unlockWrite
AV39LockLock state; write 0 unlock, 1 lock, 2 change passcodeWrite
AV40Reset_EnergyWrite 42405 (0xA5A5) to zero the energy totalsWrite
AV41Reboot_DeviceWrite 43605 (0xAA55) to reboot; reads 0Write
Object ID lookup: Elkor WattsOn-Mark II -M2 power meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WattsOn-Mark II -M2 power meter (BACnet MS/TP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Elkor WattsOn-Mark II -M2 power meter (BACnet MS/TP)

How many BACnet points does the Elkor WattsOn-Mark II -M2 power meter (BACnet MS/TP) have?

This list has 129 BACnet objects: 87 analog inputs, 42 analog values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Elkor WattsOn-Mark II -M2 power meter (BACnet MS/TP) BACnet points are writable?

42 of the 129 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Elkor WattsOn-Mark II -M2 power meter (BACnet MS/TP) BACnet documentation?

The source is WattsOn-Mark II BACnet MS/TP (-M2) Addendum, revision 2015-11 (Revision 1), published free by Elkor at https://www.elkor.net/pdfs/W2-BACnet_MSTP_Guide.pdf.

What are the minimum BACnet points to integrate the Elkor WattsOn-Mark II -M2 power meter (BACnet MS/TP)?

Start with AI 4 kW_Total (Total real power, kW); AI 45 kWh_Import_Ttl (Imported energy total, kWh); AI 43 kWh_Net_Ttl (Net energy total, kWh); AI 42 kW_Demand (Sliding-window kW demand); AI 10 PF_Total (Total power factor); AI 9 Current_Avg (Average current, A); AI 7 Volts_LN_Avg (Average line-to-neutral voltage, V); AI 11 Frequency (Line frequency, Hz).

How do I check these points on the real WattsOn-Mark II -M2 power meter (BACnet MS/TP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Elkor BACnet points lists

Source: WattsOn-Mark II BACnet MS/TP (-M2) Addendum · rev. 2015-11 (Revision 1). Object names, instances and units are reproduced as published; descriptions are our own.