Updated 6 November 2026

Short answer

The ETBAC object map shows how the gateway presents each connected WattsOn power meter: a block of read-only Analog Inputs per meter with ratios, serial number, totals, per-phase voltage, current, power, power factor and energy. One Analog Value sets the polling delay. Meter 1 uses instances 100128-100852, meter 2 the same offsets from 200000.

This page lists 41 BACnet objects for the Elkor ETBAC BACnet gateway for WattsOn meters — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Elkor’s own free documentation, linked below.

Manufacturer
Elkor
Model
ETBAC BACnet gateway for WattsOn meters
Equipment
BACnet gateway for power meters (WattsOn)
Equipment type
Thermostats, sensors & meters
BACnet objects
41 (0 writable)
Transport
—
Firmware
Not stated
Also known as
ETBAC, Elkor ETBAC, WattsOn BACnet gateway, ETBAC object map
Source document
ETBAC BACnet Object Map
Download CSV 41 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Elkor’s current documentation and the live device before use. Not official Elkor information. Terms of use.

BMS integration notes: Elkor ETBAC BACnet gateway for WattsOn meters

Integration in brief

Discover the gateway, then map the meter block for each WattsOn (100xxx for meter 1, 200xxx for meter 2). Read total real power, total energy, demand, power factor, average current and voltages.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 100770DEVICE-1/PWR_ELECMeter 1 total real power, kWRead
AI 100768DEVICE-1/ENERGY_ELEC_ACCUMMeter 1 total energy, kWhRead
AI 100786DEVICE-1/DEMANDMeter 1 sliding-window kW demandRead
AI 100782DEVICE-1/PWR_FACTORMeter 1 system power factorRead
AI 100780DEVICE-1/CURRENT_LNMeter 1 average current, ARead
AI 100788DEVICE-1/VOLTAGE_LN-AMeter 1 phase A to neutral voltageRead
AI 100784DEVICE-1/FREQUENCYMeter 1 frequency, HzRead

Network setup

Watch out for

Elkor ETBAC BACnet gateway for WattsOn meters BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

Note: the source document has no read/write column, so access here is inferred from the object type (inputs read-only, values writable). Confirm on the live controller before writing.

41 of 41 shown
Type
Show
Elkor ETBAC BACnet gateway for WattsOn meters BACnet Points List
DescriptionStates
AV1POLL_DELAYPolling DelaysRead
AI100128DEVICE-1/PT_RATIO_PRIMARYPT Ratio (Primary)Read
AI100129DEVICE-1/PT_RATIO_SECONDARYPT Ratio (Secondary)Read
AI100130DEVICE-1/CT_RATIO_PRIMARYCT Ratio (Primary)Read
AI100131DEVICE-1/CT_RATIO_SECONDARYCT Ratio (Secondary)Read
AI100149DEVICE-1/SERIAL_NUMBERSerial NumberRead
AImin100768DEVICE-1/ENERGY_ELEC_ACCUMTotal Energy ConsumptionkWhRead
AImin100770DEVICE-1/PWR_ELECTotal Real PowerkWRead
AI100772DEVICE-1/PWR_ELEC_REACTTotal Reactive PowerkvarRead
AI100774DEVICE-1/PWR_ELEC_APPARTotal Apparent PowerkVARead
AImin100780DEVICE-1/CURRENT_LNAverage CurrentARead
AImin100782DEVICE-1/PWR_FACTORTotal (System) Power FactorRead
AImin100784DEVICE-1/FREQUENCYFrequencyHzRead
AImin100786DEVICE-1/DEMANDSliding Window Real Power Demand (Tot.)kWRead
AImin100788DEVICE-1/VOLTAGE_LN-AVoltage phase A to NeutralVRead
AI100790DEVICE-1/VOLTAGE_LN-BVoltage phase B to NeutralVRead
AI100792DEVICE-1/VOLTAGE_LN-CVoltage phase C to NeutralVRead
AI100794DEVICE-1/VOLTAGE_LL-ABVoltage phase A to phase BVRead
AI100796DEVICE-1/VOLTAGE_LL-BCVoltage phase B to phase CVRead
AI100798DEVICE-1/VOLTAGE_LL-CAVoltage phase A to phase CVRead
AI100800DEVICE-1/CURRENT_LN-ACurrent phase AARead
AI100802DEVICE-1/CURRENT_LN-BCurrent phase BARead
AI100804DEVICE-1/CURRENT_LN-CCurrent phase CARead
AI100806DEVICE-1/PWR_ELEC-AReal Power phase AkWRead
AI100808DEVICE-1/PWR_ELEC-BReal Power phase BkWRead
AI100810DEVICE-1/PWR_ELEC-CReal Power phase CkWRead
AI100824DEVICE-1/PWR_FACTOR-APower Factor phase ARead
AI100826DEVICE-1/PWR_FACTOR-BPower Factor phase BRead
AI100828DEVICE-1/PWR_FACTOR-CPower Factor phase CRead
AI100830DEVICE-1/SOFTWARE_VERSIONSoftware VersionRead
AI100832DEVICE-1/ENERGY_ELEC_ACCUM_REC-AImport Energy (+) AkWhRead
AI100834DEVICE-1/ENERGY_ELEC_ACCUM_REC-BImport Energy (+) BkWhRead
AI100836DEVICE-1/ENERGY_ELEC_ACCUM_REC-CImport Energy (+) CkWhRead
AI100838DEVICE-1/ENERGY_ELEC_ACCUM_RECTotal Import Energy (+) A+B+CkWhRead
AI100840DEVICE-1/ENERGY_ELEC_ACCUM_DEL-AExport Energy (-) AkWhRead
AI100842DEVICE-1/ENERGY_ELEC_ACCUM_DEL-BExport Energy (-) BkWhRead
AI100844DEVICE-1/ENERGY_ELEC_ACCUM_DEL-CExport Energy (-) CkWhRead
AI100846DEVICE-1/ENERGY_ELEC_ACCUM_DELTotal Export Energy (-) A+B+CkWhRead
AI100848DEVICE-1/ENERGY_ELEC_ACCUM_NET-ANet Total Energy (+/-) AkWhRead
AI100850DEVICE-1/ENERGY_ELEC_ACCUM_NET-BNet Total Energy (+/-) BkWhRead
AI100852DEVICE-1/ENERGY_ELEC_ACCUM_NET-CNet Total Energy (+/-) CkWhRead
Object ID lookup: Elkor ETBAC BACnet gateway for WattsOn meters point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the ETBAC BACnet gateway for WattsOn meters and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Elkor ETBAC BACnet gateway for WattsOn meters

How many BACnet points does the Elkor ETBAC BACnet gateway for WattsOn meters have?

This list has 41 BACnet objects: 40 analog inputs, 1 analog value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Elkor ETBAC BACnet gateway for WattsOn meters BACnet points are writable?

None of the listed objects are marked writable in the source documentation. The source has no read/write column, so this is inferred from object type.

Where is the official Elkor ETBAC BACnet gateway for WattsOn meters BACnet documentation?

The source is ETBAC BACnet Object Map, published free by Elkor at https://www.elkor.net/pdfs/ETBAC_Object_List.pdf.

What are the minimum BACnet points to integrate the Elkor ETBAC BACnet gateway for WattsOn meters?

Start with AI 100770 DEVICE-1/PWR_ELEC (Meter 1 total real power, kW); AI 100768 DEVICE-1/ENERGY_ELEC_ACCUM (Meter 1 total energy, kWh); AI 100786 DEVICE-1/DEMAND (Meter 1 sliding-window kW demand); AI 100782 DEVICE-1/PWR_FACTOR (Meter 1 system power factor); AI 100780 DEVICE-1/CURRENT_LN (Meter 1 average current, A); AI 100788 DEVICE-1/VOLTAGE_LN-A (Meter 1 phase A to neutral voltage); AI 100784 DEVICE-1/FREQUENCY (Meter 1 frequency, Hz).

How do I check these points on the real ETBAC BACnet gateway for WattsOn meters?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Elkor BACnet points lists

Source: ETBAC BACnet Object Map. Object names, instances and units are reproduced as published; descriptions are our own.