The -E4 version of the WattsOn-Mark II serves its metering data over BACnet IP from an Ethernet or Wi-Fi module. Metering objects use the Modbus register offset as the instance: totals and per-phase power, voltage, current, power factor and angles, plus energy registers by quadrant. Writable Analog Values set CT/PT ratios, demand window, relay alarms and energy reset; the 70000/80000 ranges show network status and settings.
This page lists 210 BACnet objects for the Elkor WattsOn-Mark II -E4 power meter (BACnet IP) — 43 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Elkor’s own free documentation, linked below.
- Manufacturer
- Elkor
- Model
- WattsOn-Mark II -E4 power meter (BACnet IP)
- Equipment
- Power and energy meter (submeter)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 210 (43 writable)
- Transport
- BACnet IP
- Firmware
- Not stated
- Also known as
- WattsOn-Mark II, WattsOn Mk II, W2-E4, WattsOn-MkII-E4, Elkor WattsOn BACnet IP
- Source document
- WattsOn-Mark II BACnet/IP (-E4) BACnet Object List
Reference only, provided as-is: verify against Elkor’s current documentation and the live device before use. Not official Elkor information. Terms of use.
BMS integration notes: Elkor WattsOn-Mark II -E4 power meter (BACnet IP)
Set the CT and PT ratios (AV 1280-1295) to match the installation, then read total kW, kWh import, demand, power factor, average current and voltage. Energy totals are zeroed by writing 42405 to Reset_Energy.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 512 | kW_Total | Total real power, kW | Read |
| AI 4356 | kWh_Import_Ttl | Imported energy total, kWh | Read |
| AI 4352 | kWh_Net_Ttl | Net energy total, kWh | Read |
| AI 598 | kW_Demand | Sliding-window kW demand | Read |
| AI 524 | PF_Total | Total power factor | Read |
| AI 522 | Current_Avg | Average current, A | Read |
| AI 518 | Volts_LN_Avg | Average line-to-neutral voltage, V | Read |
| AI 526 | Frequency | Line frequency, Hz | Read |
Network setup
- BACnet port, device instance (-1 = derived from the MAC), APDU size, segmentation and BBMD foreign registration are set in the web interface; objects 80070-80078 (CSV and BI) show the values.
- Ethernet or Wi-Fi can be static or DHCP; the active link and IP show at MI 70000 and CSV 70000-70006.
- Set CT_Primary/Secondary_All and PT_Primary/Secondary_All (or the per-phase AVs) before trusting readings.
Watch out for
- Reset_Energy only acts on the value 42405 (0xA5A5); Reboot_Device only on 43605 (0xAA55).
- With the meter locked (BV 1321), settings writes need the passcode entered at PIV 1319.
- kVAR/kVA unit text in the source table is swapped; trust the unit codes.
Elkor WattsOn-Mark II -E4 power meter (BACnet IP) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 512 | kW_Total | kW | Read | ||
| AI | 514 | kVAR_Total | kvar | Read | ||
| AI | 516 | kVA_Total | kVA | Read | ||
| AImin | 518 | Volts_LN_Avg | V | Read | ||
| AI | 520 | Volts_LL_Avg | V | Read | ||
| AImin | 522 | Current_Avg | A | Read | ||
| AImin | 524 | PF_Total | Read | |||
| AImin | 526 | Frequency | Hz | Read | ||
| AI | 528 | Volts_Angle_Avg | ° | Read | ||
| AI | 530 | Quadrant_Total | Read | |||
| AI | 544 | Volts_AN | V | Read | ||
| AI | 546 | Volts_BN | V | Read | ||
| AI | 548 | Volts_CN | V | Read | ||
| AI | 550 | Volts_AB | V | Read | ||
| AI | 552 | Volts_BC | V | Read | ||
| AI | 554 | Volts_AC | V | Read | ||
| AI | 556 | Current_A | A | Read | ||
| AI | 558 | Current_B | A | Read | ||
| AI | 560 | Current_C | A | Read | ||
| AI | 562 | kW_A | kW | Read | ||
| AI | 564 | kW_B | kW | Read | ||
| AI | 566 | kW_C | kW | Read | ||
| AI | 568 | kVAR_A | kvar | Read | ||
| AI | 570 | kVAR_B | kvar | Read | ||
| AI | 572 | kVAR_C | kvar | Read | ||
| AI | 574 | kVA_A | kVA | Read | ||
| AI | 576 | kVA_B | kVA | Read | ||
| AI | 578 | kVA_C | kVA | Read | ||
| AI | 580 | PF_A | Read | |||
| AI | 582 | PF_B | Read | |||
| AI | 584 | PF_C | Read | |||
| AI | 586 | Volts_Angle_AB | ° | Read | ||
| AI | 588 | Volts_Angle_BC | ° | Read | ||
| AI | 590 | Volts_Angle_AC | ° | Read | ||
| AI | 592 | Quadrant_A | Read | |||
| AI | 594 | Quadrant_B | Read | |||
| AI | 596 | Quadrant_C | Read | |||
| AImin | 598 | kW_Demand | kW | Read | ||
| AImin | 4352 | kWh_Net_Ttl | kWh | Read | ||
| AI | 4354 | kVAh_Net_Ttl | kVAh | Read | ||
| AImin | 4356 | kWh_Import_Ttl | kWh | Read | ||
| AI | 4358 | kWh_Export_Ttl | kWh | Read | ||
| AI | 4360 | kVAh_Import_Ttl | kVAh | Read | ||
| AI | 4362 | Q1_VARh_Ttl | kvarh | Read | ||
| AI | 4364 | Q2_VARh_Ttl | kvarh | Read | ||
| AI | 4366 | Q3_VARh_Ttl | kvarh | Read | ||
| AI | 4368 | Q4_VARh_Ttl | kvarh | Read | ||
| AI | 4370 | Q1+Q2_VARh_Ttl | kvarh | Read | ||
| AI | 4372 | Q3+Q4_VARh_Ttl | kvarh | Read | ||
| AI | 4384 | kWh_Net_A | kWh | Read | ||
| AI | 4386 | kWh_Net_B | kWh | Read | ||
| AI | 4388 | kWh_Net_C | kWh | Read | ||
| AI | 4390 | kVAh_Net_A | kVAh | Read | ||
| AI | 4392 | kVAh_Net_B | kVAh | Read | ||
| AI | 4394 | kVAh_Net_C | kVAh | Read | ||
| AI | 4396 | kWh_Import_A | kWh | Read | ||
| AI | 4398 | kWh_Import_B | kWh | Read | ||
| AI | 4400 | kWh_Import_C | kWh | Read | ||
| AI | 4402 | kWh_Export_A | kWh | Read | ||
| AI | 4404 | kWh_Export_B | kWh | Read | ||
| AI | 4406 | kWh_Export_C | kWh | Read | ||
| AI | 4408 | kVAh_Import_A | kVAh | Read | ||
| AI | 4410 | kVAh_Import_B | kVAh | Read | ||
| AI | 4412 | kVAh_Import_C | kVAh | Read | ||
| AI | 4414 | kVAh_Export_A | kVAh | Read | ||
| AI | 4416 | kVAh_Export_B | kVAh | Read | ||
| AI | 4418 | kVAh_Export_C | kVAh | Read | ||
| AI | 4420 | kVARh_Q1_A | kvarh | Read | ||
| AI | 4422 | kVARh_Q1_B | kvarh | Read | ||
| AI | 4424 | kVARh_Q1_C | kvarh | Read | ||
| AI | 4426 | kVARh_Q2_A | kvarh | Read | ||
| AI | 4428 | kVARh_Q2_B | kvarh | Read | ||
| AI | 4430 | kVARh_Q2_C | kvarh | Read | ||
| AI | 4432 | kVARh_Q3_A | kvarh | Read | ||
| AI | 4434 | kVARh_Q3_B | kvarh | Read | ||
| AI | 4436 | kVARh_Q3_C | kvarh | Read | ||
| AI | 4438 | kVARh_Q4_A | kvarh | Read | ||
| AI | 4440 | kVARh_Q4_B | kvarh | Read | ||
| AI | 4442 | kVARh_Q4_C | kvarh | Read | ||
| AV | 1280 | CT_Primary_All | CT primary for all three phases | Write | ||
| AV | 1281 | CT_Secondary_All | CT secondary for all three phases | Write | ||
| AV | 1282 | CT_Primary_A | Write | |||
| AV | 1283 | CT_Secondary_A | Write | |||
| AV | 1284 | CT_Primary_B | Write | |||
| AV | 1285 | CT_Secondary_B | Write | |||
| AV | 1286 | CT_Primary_C | Write | |||
| AV | 1287 | CT_Secondary_C | Write | |||
| AV | 1288 | PT_Primary_All | PT primary for all three phases | Write | ||
| AV | 1289 | PT_Secondary_All | PT secondary for all three phases | Write | ||
| AV | 1290 | PT_Primary_A | Write | |||
| AV | 1291 | PT_Secondary_A | Write | |||
| AV | 1292 | PT_Primary_B | Write | |||
| AV | 1293 | PT_Secondary_B | Write | |||
| AV | 1294 | PT_Primary_C | Write | |||
| AV | 1295 | PT_Secondary_C | Write | |||
| AV | 1316 | Reset_Energy | Write 42405 (0xA5A5) to zero the energy totals | Write | ||
| AV | 1322 | Phase_Comp_All | Phase compensation, all phases | Write | ||
| AV | 1323 | Phase_Comp_A | Write | |||
| AV | 1324 | Phase_Comp_B | Write | |||
| AV | 1325 | Phase_Comp_C | Write | |||
| AV | 1326 | Integer Divider | Write | |||
| AV | 1327 | Window_Length | Sliding-window demand sub-interval, s | s | Write | |
| AV | 1328 | Window_Count | Number of sliding-window sub-intervals | Write | ||
| AV | 1329 | Window_Sync | Resets the sliding-window demand timer | Write | ||
| AV | 1545 | Reboot_Device | Write 43605 (0xAA55) to reboot; reads 0 | Write | ||
| AI | 1309 | Serial_Number | Factory serial number | Read | ||
| AI | 1299 | Debug_Register | Always reads 1234.567 (comms check) | Read | ||
| AI | 1311 | Hardware_Ver | Read | |||
| AI | 1312 | Firmware_Ver | Read | |||
| AI | 1313 | Bootloader_Ver | Read | |||
| AV | 2304 | K1_Reg_Offset | Write | |||
| AV | 2306 | K1_Upper_Bound | Write | |||
| AV | 2308 | K1_Lower_Bound | Write | |||
| AV | 2310 | K1_Min_Duration | Write | |||
| AV | 2314 | K2_Reg_Offset | Write | |||
| AV | 2316 | K2_Upper_Bound | Write | |||
| AV | 2318 | K2_Lower_Bound | Write | |||
| AV | 2320 | K2_Min_Duration | Write | |||
| PIV | 1319 | Passcode | Passcode entry for lock/unlock | Write | ||
| BV | 1321 | Lock | Lock state; write 0 unlock, 1 lock, 2 change passcode | Write | ||
| BV | 1330 | Freq_Auto | Auto-select voltage channel for frequency | Write | ||
| MV | 1331 | Freq_Channel | Voltage channel for frequency (A, B, C) | Write | ||
| MV | 1318 | PF_Sign_Mode | How the power factor sign is calculated | Write | ||
| MV | 2305 | K1_Trigger_Type | Write | |||
| MV | 2311 | K1_Active_Mode | Write | |||
| MV | 2315 | K2_Trigger_Type | Write | |||
| MV | 2321 | K2_Active_Mode | Write | |||
| FILE | 10 | /spiffs/template.json | Read | |||
| MI | 70000 | active_connection | Active link: 1 Ethernet, 2 Wi-Fi, 3 Wi-Fi AP | Read | ||
| CSV | 70000 | active_ip | Read | |||
| CSV | 70001 | active_nm | Read | |||
| CSV | 70002 | active_gw | Read | |||
| CSV | 70003 | active_dns0 | Read | |||
| CSV | 70004 | active_dns1 | Read | |||
| CSV | 70005 | eth_mac | Read | |||
| CSV | 70006 | wifi_mac | Read | |||
| DTV | 70000 | utc_datetime | Current date/time (NTP or battery clock) | Read | ||
| CSV | 80009 | Net/mbtcp_port | Read | |||
| CSV | 80010 | Net/http_port | Read | |||
| CSV | 80013 | Net/api_udp_port | Read | |||
| BI | 80015 | Net/post_en | Read | |||
| CSV | 80016 | Net/post_seconds | Read | |||
| BI | 80017 | Net/post_auth_en | Read | |||
| CSV | 80018 | Net/post_timeout_s | Read | |||
| BI | 80019 | Net/post_buf_en | Read | |||
| CSV | 80020 | Net/post_buf_limit | Read | |||
| BI | 80021 | Net/ntp_en | Read | |||
| CSV | 80022 | Net/ntp_listen_port | Read | |||
| CSV | 80023 | Net/ntp_port_0 | Read | |||
| CSV | 80024 | Net/ntp_port_1 | Read | |||
| CSV | 80025 | Net/ntp_port_2 | Read | |||
| CSV | 80026 | Net/ntp_rate_m | Read | |||
| CSV | 80027 | Net/ntp_timeout_ms | Read | |||
| CSV | 80028 | Net/ntp_retry_ms | Read | |||
| CSV | 80029 | Net/eth_static_ip | Read | |||
| CSV | 80030 | Net/eth_static_nm | Read | |||
| CSV | 80031 | Net/eth_static_gw | Read | |||
| CSV | 80032 | Net/eth_static_dn0 | Read | |||
| CSV | 80033 | Net/eth_static_dn1 | Read | |||
| CSV | 80034 | Net/wifi_static_ip | Read | |||
| CSV | 80035 | Net/wifi_static_nm | Read | |||
| CSV | 80036 | Net/wifi_static_gw | Read | |||
| CSV | 80037 | Net/wifi_static_dn0 | Read | |||
| CSV | 80038 | Net/wifi_static_dn1 | Read | |||
| CSV | 80040 | Net/http_sto_ms | Read | |||
| CSV | 80041 | Net/http_rto_ms | Read | |||
| CSV | 80042 | Net/auto_reboot_s | Read | |||
| CSV | 80043 | Net/reconnect_s | Read | |||
| CSV | 80048 | Net/wifi_chan_start | Read | |||
| CSV | 80049 | Net/wifi_chan_count | Read | |||
| CSV | 80050 | Net/wifi_max_tx_pwr | Read | |||
| CSV | 80070 | Net/bac_port | BACnet UDP port | Read | ||
| CSV | 80071 | Net/bac_instance | Device instance (-1 = from MAC) | Read | ||
| BI | 80073 | Net/mbtcp_en | Read | |||
| CSV | 80074 | Net/bac_apdu_max | Read | |||
| CSV | 80075 | Net/bac_frgn_reg_ip | BBMD address for foreign registration | Read | ||
| CSV | 80076 | Net/bac_frgn_reg_s | Foreign registration TTL, s | Read | ||
| BI | 80077 | Net/bac_segment_en | Read | |||
| CSV | 80078 | Net/bac_seg_to_ms | Read | |||
| BI | 80079 | Net/mqtt_retain_en | Read | |||
| CSV | 80080 | Net/mqtt_max_flying | Read | |||
| CSV | 80081 | Net/mqtt_version_id | Read | |||
| BI | 80082 | Net/mqtt_no_cid_en | Read | |||
| BI | 80083 | Net/mqtt_en | Read | |||
| BI | 80084 | Net/mqtt_persist_en | Read | |||
| BI | 80085 | Net/mqtt_aliases_en | Read | |||
| MI | 80202 | Net/eth_mode | Ethernet mode: 0 static, 1 DHCP | Read | ||
| MI | 80203 | Net/wifi_mode | Wi-Fi mode: 0 static, 1 DHCP | Read | ||
| CSV | 80250 | Net/name | Read | |||
| CSV | 80251 | Net/wifi_ssid | Read | |||
| CSV | 80254 | Net/post_url | Read | |||
| CSV | 80255 | Net/post_auth_user | Read | |||
| CSV | 80257 | Net/ntp_server_0 | Read | |||
| CSV | 80258 | Net/ntp_server_1 | Read | |||
| CSV | 80259 | Net/ntp_server_2 | Read | |||
| CSV | 80260 | Net/post_file_0 | Read | |||
| CSV | 80261 | Net/post_file_1 | Read | |||
| CSV | 80262 | Net/post_file_2 | Read | |||
| CSV | 80263 | Net/post_file_3 | Read | |||
| CSV | 80264 | Net/post_file_4 | Read | |||
| CSV | 80270 | Net/post_method | Read | |||
| CSV | 80271 | Net/post_headers | Read | |||
| CSV | 80272 | Net/post_ct | Read | |||
| CSV | 80273 | Net/http_headers | Read | |||
| CSV | 80279 | Net/wifi_country | Read | |||
| CSV | 80350 | Net/post_addr_0 | Read | |||
| CSV | 80351 | Net/post_addr_1 | Read | |||
| CSV | 80352 | Net/post_addr_2 | Read | |||
| CSV | 80353 | Net/post_addr_3 | Read | |||
| CSV | 80354 | Net/post_addr_4 | Read |
No points match these filters.
Object ID lookup: Elkor WattsOn-Mark II -E4 power meter point IDs by name
AI512kW_TotalAI514kVAR_TotalAI516kVA_TotalAI518Volts_LN_AvgAI520Volts_LL_AvgAI522Current_AvgAI524PF_TotalAI526FrequencyAI528Volts_Angle_AvgAI530Quadrant_TotalAI544Volts_ANAI546Volts_BNAI548Volts_CNAI550Volts_ABAI552Volts_BCAI554Volts_ACAI556Current_AAI558Current_BAI560Current_CAI562kW_AAI564kW_BAI566kW_CAI568kVAR_AAI570kVAR_BAI572kVAR_CAI574kVA_AAI576kVA_BAI578kVA_CAI580PF_AAI582PF_BAI584PF_CAI586Volts_Angle_ABAI588Volts_Angle_BCAI590Volts_Angle_ACAI592Quadrant_AAI594Quadrant_BAI596Quadrant_CAI598kW_DemandAI4352kWh_Net_TtlAI4354kVAh_Net_TtlAI4356kWh_Import_TtlAI4358kWh_Export_TtlAI4360kVAh_Import_TtlAI4362Q1_VARh_TtlAI4364Q2_VARh_TtlAI4366Q3_VARh_TtlAI4368Q4_VARh_TtlAI4370Q1+Q2_VARh_TtlAI4372Q3+Q4_VARh_TtlAI4384kWh_Net_AAI4386kWh_Net_BAI4388kWh_Net_CAI4390kVAh_Net_AAI4392kVAh_Net_BAI4394kVAh_Net_CAI4396kWh_Import_AAI4398kWh_Import_BAI4400kWh_Import_CAI4402kWh_Export_AAI4404kWh_Export_BAI4406kWh_Export_CAI4408kVAh_Import_AAI4410kVAh_Import_BAI4412kVAh_Import_CAI4414kVAh_Export_AAI4416kVAh_Export_BAI4418kVAh_Export_CAI4420kVARh_Q1_AAI4422kVARh_Q1_BAI4424kVARh_Q1_CAI4426kVARh_Q2_AAI4428kVARh_Q2_BAI4430kVARh_Q2_CAI4432kVARh_Q3_AAI4434kVARh_Q3_BAI4436kVARh_Q3_CAI4438kVARh_Q4_AAI4440kVARh_Q4_BAI4442kVARh_Q4_CAV1280CT_Primary_AllAV1281CT_Secondary_AllAV1282CT_Primary_AAV1283CT_Secondary_AAV1284CT_Primary_BAV1285CT_Secondary_BAV1286CT_Primary_CAV1287CT_Secondary_CAV1288PT_Primary_AllAV1289PT_Secondary_AllAV1290PT_Primary_AAV1291PT_Secondary_AAV1292PT_Primary_BAV1293PT_Secondary_BAV1294PT_Primary_CAV1295PT_Secondary_CAV1316Reset_EnergyAV1322Phase_Comp_AllAV1323Phase_Comp_AAV1324Phase_Comp_BAV1325Phase_Comp_CAV1326Integer DividerAV1327Window_LengthAV1328Window_CountAV1329Window_SyncAV1545Reboot_DeviceAI1309Serial_NumberAI1299Debug_RegisterAI1311Hardware_VerAI1312Firmware_VerAI1313Bootloader_VerAV2304K1_Reg_OffsetAV2306K1_Upper_BoundAV2308K1_Lower_BoundAV2310K1_Min_DurationAV2314K2_Reg_OffsetAV2316K2_Upper_BoundAV2318K2_Lower_BoundAV2320K2_Min_DurationPIV1319PasscodeBV1321LockBV1330Freq_AutoMV1331Freq_ChannelMV1318PF_Sign_ModeMV2305K1_Trigger_TypeMV2311K1_Active_ModeMV2315K2_Trigger_TypeMV2321K2_Active_ModeFILE10/spiffs/template.jsonMI70000active_connectionCSV70000active_ipCSV70001active_nmCSV70002active_gwCSV70003active_dns0CSV70004active_dns1CSV70005eth_macCSV70006wifi_macDTV70000utc_datetimeCSV80009Net/mbtcp_portCSV80010Net/http_portCSV80013Net/api_udp_portBI80015Net/post_enCSV80016Net/post_secondsBI80017Net/post_auth_enCSV80018Net/post_timeout_sBI80019Net/post_buf_enCSV80020Net/post_buf_limitBI80021Net/ntp_enCSV80022Net/ntp_listen_portCSV80023Net/ntp_port_0CSV80024Net/ntp_port_1CSV80025Net/ntp_port_2CSV80026Net/ntp_rate_mCSV80027Net/ntp_timeout_msCSV80028Net/ntp_retry_msCSV80029Net/eth_static_ipCSV80030Net/eth_static_nmCSV80031Net/eth_static_gwCSV80032Net/eth_static_dn0CSV80033Net/eth_static_dn1CSV80034Net/wifi_static_ipCSV80035Net/wifi_static_nmCSV80036Net/wifi_static_gwCSV80037Net/wifi_static_dn0CSV80038Net/wifi_static_dn1CSV80040Net/http_sto_msCSV80041Net/http_rto_msCSV80042Net/auto_reboot_sCSV80043Net/reconnect_sCSV80048Net/wifi_chan_startCSV80049Net/wifi_chan_countCSV80050Net/wifi_max_tx_pwrCSV80070Net/bac_portCSV80071Net/bac_instanceBI80073Net/mbtcp_enCSV80074Net/bac_apdu_maxCSV80075Net/bac_frgn_reg_ipCSV80076Net/bac_frgn_reg_sBI80077Net/bac_segment_enCSV80078Net/bac_seg_to_msBI80079Net/mqtt_retain_enCSV80080Net/mqtt_max_flyingCSV80081Net/mqtt_version_idBI80082Net/mqtt_no_cid_enBI80083Net/mqtt_enBI80084Net/mqtt_persist_enBI80085Net/mqtt_aliases_enMI80202Net/eth_modeMI80203Net/wifi_modeCSV80250Net/nameCSV80251Net/wifi_ssidCSV80254Net/post_urlCSV80255Net/post_auth_userCSV80257Net/ntp_server_0CSV80258Net/ntp_server_1CSV80259Net/ntp_server_2CSV80260Net/post_file_0CSV80261Net/post_file_1CSV80262Net/post_file_2CSV80263Net/post_file_3CSV80264Net/post_file_4CSV80270Net/post_methodCSV80271Net/post_headersCSV80272Net/post_ctCSV80273Net/http_headersCSV80279Net/wifi_countryCSV80350Net/post_addr_0CSV80351Net/post_addr_1CSV80352Net/post_addr_2CSV80353Net/post_addr_3CSV80354Net/post_addr_4
Integration notes
- Metering, configuration and relay objects use the Modbus register offset as the instance number (0-65535); network status is at 70000-79999 and network settings at 80000-89999.
- The unit text for kVAR and kVA is swapped in the table (kVAR objects say kilovolt-amperes, kVA objects say kilovolt-amperes-reactive), and kVAh_Import/Export_A-C say kilowatt-hours; units here follow the printed BACnet unit codes (12 = kvar, 9 = kVA, 240 = kVAh).
- The 6 Structured View objects (SV 0-5) are not listed here. The network status rows are typed 'CS' in the table and are listed as CharacterString Values.
- Input_Config (CT type: 1 mA, 2 mV, 3 5 A, 4 Rogowski, 0 custom) is printed with no instance number and is left out.
- Network settings (80000 range) are read-only over BACnet and are changed in the web interface.
- MSI 70000, CSV 70000 and DTV 70000 share the instance number but are different object types.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WattsOn-Mark II -E4 power meter (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the Elkor WattsOn-Mark II -E4 power meter (BACnet IP)
How many BACnet points does the Elkor WattsOn-Mark II -E4 power meter (BACnet IP) have?
This list has 210 BACnet objects: 84 analog inputs, 34 analog values, 11 binary inputs, 2 binary values, 1 file, 3 multi-state inputs, 6 multi-state values, 67 characterstring values, 1 datetime value, 1 positive integer value. The exact set on a given unit depends on its firmware, installed options and configuration.
Which Elkor WattsOn-Mark II -E4 power meter (BACnet IP) BACnet points are writable?
43 of the 210 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.
Where is the official Elkor WattsOn-Mark II -E4 power meter (BACnet IP) BACnet documentation?
The source is WattsOn-Mark II BACnet/IP (-E4) BACnet Object List, published free by Elkor at https://www.elkor.net/pdfs/WattsOn-MkII-BACnet-E4_Object_List.pdf.
What are the minimum BACnet points to integrate the Elkor WattsOn-Mark II -E4 power meter (BACnet IP)?
Start with AI 512 kW_Total (Total real power, kW); AI 4356 kWh_Import_Ttl (Imported energy total, kWh); AI 4352 kWh_Net_Ttl (Net energy total, kWh); AI 598 kW_Demand (Sliding-window kW demand); AI 524 PF_Total (Total power factor); AI 522 Current_Avg (Average current, A); AI 518 Volts_LN_Avg (Average line-to-neutral voltage, V); AI 526 Frequency (Line frequency, Hz).
How do I check these points on the real WattsOn-Mark II -E4 power meter (BACnet IP)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More Elkor BACnet points lists
- BACnet gateway for power meters (WattsOn)
Elkor ETBAC BACnet gateway for WattsOn meters
Elkor ETBAC gateway serving one or more Elkor WattsOn power meters as BACnet objects.
Also known as: ETBAC, Elkor ETBAC, WattsOn BACnet gateway, ETBAC object map - Power and energy meter (submeter)
Elkor WattsOn-Mark II -M2 power meter (BACnet MS/TP)
Elkor WattsOn-Mark II three-phase power meters ordered with the -M2 BACnet MS/TP output.
Also known as: WattsOn-Mark II, W2-M2, WattsOn Mk II BACnet MS/TP, Elkor WattsOn BACnet MS/TP - Multi-circuit power and energy meter (submeter)
Elkor WattsOn-MCM modular multi-circuit meter (BACnet IP)
Elkor WattsOn-MCM modular metering systems (main board, MCM-V voltage interface and up to 20 measurement cards) on BACnet IP.
Also known as: WattsOn-MCM, WattsOn MCM, MCM-V, WMC-PM, WMC-IM, Elkor multi-circuit meter BACnet
Source: WattsOn-Mark II BACnet/IP (-E4) BACnet Object List. Object names, instances and units are reproduced as published; descriptions are our own.