Short answer

The -E4 version of the WattsOn-Mark II serves its metering data over BACnet IP from an Ethernet or Wi-Fi module. Metering objects use the Modbus register offset as the instance: totals and per-phase power, voltage, current, power factor and angles, plus energy registers by quadrant. Writable Analog Values set CT/PT ratios, demand window, relay alarms and energy reset; the 70000/80000 ranges show network status and settings.

This page lists 210 BACnet objects for the Elkor WattsOn-Mark II -E4 power meter (BACnet IP) — 43 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Elkor’s own free documentation, linked below.

Manufacturer
Elkor
Model
WattsOn-Mark II -E4 power meter (BACnet IP)
Equipment
Power and energy meter (submeter)
Equipment type
Thermostats, sensors & meters
BACnet objects
210 (43 writable)
Transport
BACnet IP
Firmware
Not stated
Also known as
WattsOn-Mark II, WattsOn Mk II, W2-E4, WattsOn-MkII-E4, Elkor WattsOn BACnet IP
Source document
WattsOn-Mark II BACnet/IP (-E4) BACnet Object List
Download CSV 210 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against Elkor’s current documentation and the live device before use. Not official Elkor information. Terms of use.

BMS integration notes: Elkor WattsOn-Mark II -E4 power meter (BACnet IP)

Integration in brief

Set the CT and PT ratios (AV 1280-1295) to match the installation, then read total kW, kWh import, demand, power factor, average current and voltage. Energy totals are zeroed by writing 42405 to Reset_Energy.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 512kW_TotalTotal real power, kWRead
AI 4356kWh_Import_TtlImported energy total, kWhRead
AI 4352kWh_Net_TtlNet energy total, kWhRead
AI 598kW_DemandSliding-window kW demandRead
AI 524PF_TotalTotal power factorRead
AI 522Current_AvgAverage current, ARead
AI 518Volts_LN_AvgAverage line-to-neutral voltage, VRead
AI 526FrequencyLine frequency, HzRead

Network setup

Watch out for

Elkor WattsOn-Mark II -E4 power meter (BACnet IP) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

210 of 210 shown
Type
Access
Show
Elkor WattsOn-Mark II -E4 power meter (BACnet IP) BACnet Points List
DescriptionStates
AImin512kW_TotalkWRead
AI514kVAR_TotalkvarRead
AI516kVA_TotalkVARead
AImin518Volts_LN_AvgVRead
AI520Volts_LL_AvgVRead
AImin522Current_AvgARead
AImin524PF_TotalRead
AImin526FrequencyHzRead
AI528Volts_Angle_Avg°Read
AI530Quadrant_TotalRead
AI544Volts_ANVRead
AI546Volts_BNVRead
AI548Volts_CNVRead
AI550Volts_ABVRead
AI552Volts_BCVRead
AI554Volts_ACVRead
AI556Current_AARead
AI558Current_BARead
AI560Current_CARead
AI562kW_AkWRead
AI564kW_BkWRead
AI566kW_CkWRead
AI568kVAR_AkvarRead
AI570kVAR_BkvarRead
AI572kVAR_CkvarRead
AI574kVA_AkVARead
AI576kVA_BkVARead
AI578kVA_CkVARead
AI580PF_ARead
AI582PF_BRead
AI584PF_CRead
AI586Volts_Angle_AB°Read
AI588Volts_Angle_BC°Read
AI590Volts_Angle_AC°Read
AI592Quadrant_ARead
AI594Quadrant_BRead
AI596Quadrant_CRead
AImin598kW_DemandkWRead
AImin4352kWh_Net_TtlkWhRead
AI4354kVAh_Net_TtlkVAhRead
AImin4356kWh_Import_TtlkWhRead
AI4358kWh_Export_TtlkWhRead
AI4360kVAh_Import_TtlkVAhRead
AI4362Q1_VARh_TtlkvarhRead
AI4364Q2_VARh_TtlkvarhRead
AI4366Q3_VARh_TtlkvarhRead
AI4368Q4_VARh_TtlkvarhRead
AI4370Q1+Q2_VARh_TtlkvarhRead
AI4372Q3+Q4_VARh_TtlkvarhRead
AI4384kWh_Net_AkWhRead
AI4386kWh_Net_BkWhRead
AI4388kWh_Net_CkWhRead
AI4390kVAh_Net_AkVAhRead
AI4392kVAh_Net_BkVAhRead
AI4394kVAh_Net_CkVAhRead
AI4396kWh_Import_AkWhRead
AI4398kWh_Import_BkWhRead
AI4400kWh_Import_CkWhRead
AI4402kWh_Export_AkWhRead
AI4404kWh_Export_BkWhRead
AI4406kWh_Export_CkWhRead
AI4408kVAh_Import_AkVAhRead
AI4410kVAh_Import_BkVAhRead
AI4412kVAh_Import_CkVAhRead
AI4414kVAh_Export_AkVAhRead
AI4416kVAh_Export_BkVAhRead
AI4418kVAh_Export_CkVAhRead
AI4420kVARh_Q1_AkvarhRead
AI4422kVARh_Q1_BkvarhRead
AI4424kVARh_Q1_CkvarhRead
AI4426kVARh_Q2_AkvarhRead
AI4428kVARh_Q2_BkvarhRead
AI4430kVARh_Q2_CkvarhRead
AI4432kVARh_Q3_AkvarhRead
AI4434kVARh_Q3_BkvarhRead
AI4436kVARh_Q3_CkvarhRead
AI4438kVARh_Q4_AkvarhRead
AI4440kVARh_Q4_BkvarhRead
AI4442kVARh_Q4_CkvarhRead
AV1280CT_Primary_AllCT primary for all three phasesWrite
AV1281CT_Secondary_AllCT secondary for all three phasesWrite
AV1282CT_Primary_AWrite
AV1283CT_Secondary_AWrite
AV1284CT_Primary_BWrite
AV1285CT_Secondary_BWrite
AV1286CT_Primary_CWrite
AV1287CT_Secondary_CWrite
AV1288PT_Primary_AllPT primary for all three phasesWrite
AV1289PT_Secondary_AllPT secondary for all three phasesWrite
AV1290PT_Primary_AWrite
AV1291PT_Secondary_AWrite
AV1292PT_Primary_BWrite
AV1293PT_Secondary_BWrite
AV1294PT_Primary_CWrite
AV1295PT_Secondary_CWrite
AV1316Reset_EnergyWrite 42405 (0xA5A5) to zero the energy totalsWrite
AV1322Phase_Comp_AllPhase compensation, all phasesWrite
AV1323Phase_Comp_AWrite
AV1324Phase_Comp_BWrite
AV1325Phase_Comp_CWrite
AV1326Integer DividerWrite
AV1327Window_LengthSliding-window demand sub-interval, ssWrite
AV1328Window_CountNumber of sliding-window sub-intervalsWrite
AV1329Window_SyncResets the sliding-window demand timerWrite
AV1545Reboot_DeviceWrite 43605 (0xAA55) to reboot; reads 0Write
AI1309Serial_NumberFactory serial numberRead
AI1299Debug_RegisterAlways reads 1234.567 (comms check)Read
AI1311Hardware_VerRead
AI1312Firmware_VerRead
AI1313Bootloader_VerRead
AV2304K1_Reg_OffsetWrite
AV2306K1_Upper_BoundWrite
AV2308K1_Lower_BoundWrite
AV2310K1_Min_DurationWrite
AV2314K2_Reg_OffsetWrite
AV2316K2_Upper_BoundWrite
AV2318K2_Lower_BoundWrite
AV2320K2_Min_DurationWrite
PIV1319PasscodePasscode entry for lock/unlockWrite
BV1321LockLock state; write 0 unlock, 1 lock, 2 change passcodeWrite
BV1330Freq_AutoAuto-select voltage channel for frequencyWrite
MV1331Freq_ChannelVoltage channel for frequency (A, B, C)Write
MV1318PF_Sign_ModeHow the power factor sign is calculatedWrite
MV2305K1_Trigger_TypeWrite
MV2311K1_Active_ModeWrite
MV2315K2_Trigger_TypeWrite
MV2321K2_Active_ModeWrite
FILE10/spiffs/template.jsonRead
MI70000active_connectionActive link: 1 Ethernet, 2 Wi-Fi, 3 Wi-Fi APRead
CSV70000active_ipRead
CSV70001active_nmRead
CSV70002active_gwRead
CSV70003active_dns0Read
CSV70004active_dns1Read
CSV70005eth_macRead
CSV70006wifi_macRead
DTV70000utc_datetimeCurrent date/time (NTP or battery clock)Read
CSV80009Net/mbtcp_portRead
CSV80010Net/http_portRead
CSV80013Net/api_udp_portRead
BI80015Net/post_enRead
CSV80016Net/post_secondsRead
BI80017Net/post_auth_enRead
CSV80018Net/post_timeout_sRead
BI80019Net/post_buf_enRead
CSV80020Net/post_buf_limitRead
BI80021Net/ntp_enRead
CSV80022Net/ntp_listen_portRead
CSV80023Net/ntp_port_0Read
CSV80024Net/ntp_port_1Read
CSV80025Net/ntp_port_2Read
CSV80026Net/ntp_rate_mRead
CSV80027Net/ntp_timeout_msRead
CSV80028Net/ntp_retry_msRead
CSV80029Net/eth_static_ipRead
CSV80030Net/eth_static_nmRead
CSV80031Net/eth_static_gwRead
CSV80032Net/eth_static_dn0Read
CSV80033Net/eth_static_dn1Read
CSV80034Net/wifi_static_ipRead
CSV80035Net/wifi_static_nmRead
CSV80036Net/wifi_static_gwRead
CSV80037Net/wifi_static_dn0Read
CSV80038Net/wifi_static_dn1Read
CSV80040Net/http_sto_msRead
CSV80041Net/http_rto_msRead
CSV80042Net/auto_reboot_sRead
CSV80043Net/reconnect_sRead
CSV80048Net/wifi_chan_startRead
CSV80049Net/wifi_chan_countRead
CSV80050Net/wifi_max_tx_pwrRead
CSV80070Net/bac_portBACnet UDP portRead
CSV80071Net/bac_instanceDevice instance (-1 = from MAC)Read
BI80073Net/mbtcp_enRead
CSV80074Net/bac_apdu_maxRead
CSV80075Net/bac_frgn_reg_ipBBMD address for foreign registrationRead
CSV80076Net/bac_frgn_reg_sForeign registration TTL, sRead
BI80077Net/bac_segment_enRead
CSV80078Net/bac_seg_to_msRead
BI80079Net/mqtt_retain_enRead
CSV80080Net/mqtt_max_flyingRead
CSV80081Net/mqtt_version_idRead
BI80082Net/mqtt_no_cid_enRead
BI80083Net/mqtt_enRead
BI80084Net/mqtt_persist_enRead
BI80085Net/mqtt_aliases_enRead
MI80202Net/eth_modeEthernet mode: 0 static, 1 DHCPRead
MI80203Net/wifi_modeWi-Fi mode: 0 static, 1 DHCPRead
CSV80250Net/nameRead
CSV80251Net/wifi_ssidRead
CSV80254Net/post_urlRead
CSV80255Net/post_auth_userRead
CSV80257Net/ntp_server_0Read
CSV80258Net/ntp_server_1Read
CSV80259Net/ntp_server_2Read
CSV80260Net/post_file_0Read
CSV80261Net/post_file_1Read
CSV80262Net/post_file_2Read
CSV80263Net/post_file_3Read
CSV80264Net/post_file_4Read
CSV80270Net/post_methodRead
CSV80271Net/post_headersRead
CSV80272Net/post_ctRead
CSV80273Net/http_headersRead
CSV80279Net/wifi_countryRead
CSV80350Net/post_addr_0Read
CSV80351Net/post_addr_1Read
CSV80352Net/post_addr_2Read
CSV80353Net/post_addr_3Read
CSV80354Net/post_addr_4Read
Object ID lookup: Elkor WattsOn-Mark II -E4 power meter point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the WattsOn-Mark II -E4 power meter (BACnet IP) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Elkor WattsOn-Mark II -E4 power meter (BACnet IP)

How many BACnet points does the Elkor WattsOn-Mark II -E4 power meter (BACnet IP) have?

This list has 210 BACnet objects: 84 analog inputs, 34 analog values, 11 binary inputs, 2 binary values, 1 file, 3 multi-state inputs, 6 multi-state values, 67 characterstring values, 1 datetime value, 1 positive integer value. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Elkor WattsOn-Mark II -E4 power meter (BACnet IP) BACnet points are writable?

43 of the 210 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Elkor WattsOn-Mark II -E4 power meter (BACnet IP) BACnet documentation?

The source is WattsOn-Mark II BACnet/IP (-E4) BACnet Object List, published free by Elkor at https://www.elkor.net/pdfs/WattsOn-MkII-BACnet-E4_Object_List.pdf.

What are the minimum BACnet points to integrate the Elkor WattsOn-Mark II -E4 power meter (BACnet IP)?

Start with AI 512 kW_Total (Total real power, kW); AI 4356 kWh_Import_Ttl (Imported energy total, kWh); AI 4352 kWh_Net_Ttl (Net energy total, kWh); AI 598 kW_Demand (Sliding-window kW demand); AI 524 PF_Total (Total power factor); AI 522 Current_Avg (Average current, A); AI 518 Volts_LN_Avg (Average line-to-neutral voltage, V); AI 526 Frequency (Line frequency, Hz).

How do I check these points on the real WattsOn-Mark II -E4 power meter (BACnet IP)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Elkor BACnet points lists

Source: WattsOn-Mark II BACnet/IP (-E4) BACnet Object List. Object names, instances and units are reproduced as published; descriptions are our own.