- E-Mon D-Mon legacy IDR interval data recorder (BACnet)
Electric meter data recorder (pulse) · BACnet points list
E-Mon D-Mon legacy IDR interval data recorder (BACnet) BACnet points list
Updated 12 November 2026Unofficial source
The legacy IDR publishes 32 read-only analog inputs: usage pulses for channels 1-16 (AI 1-16) and peak demand for channels 1-16 (AI 33-48). The demand objects sit at different instances from the current IDR8/IDR16 map.
This page lists 32 BACnet objects for the E-Mon D-Mon legacy IDR interval data recorder (BACnet) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of E-Mon’s documentation hosted by Kele, not by E-Mon itself, so treat it as unofficial.
- Manufacturer
- E-Mon
- Model
- E-Mon D-Mon legacy IDR interval data recorder (BACnet)
- Equipment
- Electric meter data recorder (pulse)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 32 (0 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Also known as
- E-Mon legacy IDR, Legacy IDR, E-Mon interval data recorder (legacy)
- Source document
- E-Mon D-Mon BACnet, ModBus and LonWorks Point Maps: CL3200, CL3400, CL5000 and IDR · rev. 6/21/2012 (unofficial copy, hosted by Kele)
Reference only, provided as-is: verify against E-Mon’s current documentation and the live device before use. Not official E-Mon information. Terms of use.
BMS integration notes: E-Mon D-Mon legacy IDR interval data recorder (BACnet)
Discover the recorder and read the usage (AI 1-16) and peak demand (AI 33-48) channels; scale pulses in the BMS by the meter pulse value.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Usage Channel 1 | Channel 1 usage, pulses | Read |
| AI 33 | Demand Channel 1 | Channel 1 peak demand | Read |
| AI 2 | Usage Channel 2 | Channel 2 usage, pulses | Read |
| AI 34 | Demand Channel 2 | Channel 2 peak demand | Read |
Watch out for
- Values are pulse based, not kWh; apply the pulse value per meter size.
E-Mon D-Mon legacy IDR interval data recorder (BACnet) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Usage Channel 1 | Usage pulses | pulses | Read | |
| AImin | 2 | Usage Channel 2 | Usage pulses | pulses | Read | |
| AI | 3 | Usage Channel 3 | Usage pulses | pulses | Read | |
| AI | 4 | Usage Channel 4 | Usage pulses | pulses | Read | |
| AI | 5 | Usage Channel 5 | Usage pulses | pulses | Read | |
| AI | 6 | Usage Channel 6 | Usage pulses | pulses | Read | |
| AI | 7 | Usage Channel 7 | Usage pulses | pulses | Read | |
| AI | 8 | Usage Channel 8 | Usage pulses | pulses | Read | |
| AI | 9 | Usage Channel 9 | Usage pulses | pulses | Read | |
| AI | 10 | Usage Channel 10 | Usage pulses | pulses | Read | |
| AI | 11 | Usage Channel 11 | Usage pulses | pulses | Read | |
| AI | 12 | Usage Channel 12 | Usage pulses | pulses | Read | |
| AI | 13 | Usage Channel 13 | Usage pulses | pulses | Read | |
| AI | 14 | Usage Channel 14 | Usage pulses | pulses | Read | |
| AI | 15 | Usage Channel 15 | Usage pulses | pulses | Read | |
| AI | 16 | Usage Channel 16 | Usage pulses | pulses | Read | |
| AImin | 33 | Demand Channel 1 | Peak demand | Read | ||
| AImin | 34 | Demand Channel 2 | Peak demand | Read | ||
| AI | 35 | Demand Channel 3 | Peak demand | Read | ||
| AI | 36 | Demand Channel 4 | Peak demand | Read | ||
| AI | 37 | Demand Channel 5 | Peak demand | Read | ||
| AI | 38 | Demand Channel 6 | Peak demand | Read | ||
| AI | 39 | Demand Channel 7 | Peak demand | Read | ||
| AI | 40 | Demand Channel 8 | Peak demand | Read | ||
| AI | 41 | Demand Channel 9 | Peak demand | Read | ||
| AI | 42 | Demand Channel 10 | Peak demand | Read | ||
| AI | 43 | Demand Channel 11 | Peak demand | Read | ||
| AI | 44 | Demand Channel 12 | Peak demand | Read | ||
| AI | 45 | Demand Channel 13 | Peak demand | Read | ||
| AI | 46 | Demand Channel 14 | Peak demand | Read | ||
| AI | 47 | Demand Channel 15 | Peak demand | Read | ||
| AI | 48 | Demand Channel 16 | Peak demand | Read |
No points match these filters.
Object ID lookup: E-Mon D-Mon legacy IDR interval data recorder point IDs by name
AI1Usage Channel 1AI2Usage Channel 2AI3Usage Channel 3AI4Usage Channel 4AI5Usage Channel 5AI6Usage Channel 6AI7Usage Channel 7AI8Usage Channel 8AI9Usage Channel 9AI10Usage Channel 10AI11Usage Channel 11AI12Usage Channel 12AI13Usage Channel 13AI14Usage Channel 14AI15Usage Channel 15AI16Usage Channel 16AI33Demand Channel 1AI34Demand Channel 2AI35Demand Channel 3AI36Demand Channel 4AI37Demand Channel 5AI38Demand Channel 6AI39Demand Channel 7AI40Demand Channel 8AI41Demand Channel 9AI42Demand Channel 10AI43Demand Channel 11AI44Demand Channel 12AI45Demand Channel 13AI46Demand Channel 14AI47Demand Channel 15AI48Demand Channel 16
Integration notes
- Object names are the Description column of the "BACnet Object Descriptors" tables; every object is a read-only analog input (Present Value).
- Usage units are printed as Pulse and demand as Peak Demand.
- PICS: MS/TP master at 9.6k-76.8k bps or BACnet IP.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the E-Mon D-Mon legacy IDR interval data recorder (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the E-Mon D-Mon legacy IDR interval data recorder (BACnet)
How many BACnet points does the E-Mon D-Mon legacy IDR interval data recorder (BACnet) have?
This list has 32 BACnet objects: 32 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which E-Mon D-Mon legacy IDR interval data recorder (BACnet) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official E-Mon D-Mon legacy IDR interval data recorder (BACnet) BACnet documentation?
E-Mon does not publish it on its own website. This list comes from E-Mon D-Mon BACnet, ModBus and LonWorks Point Maps: CL3200, CL3400, CL5000 and IDR, revision 6/21/2012, a copy hosted by Kele at https://assets.kele.com/Catalog/17%20Power%20Monitoring/PDFs/Class%205000%20Protocol%20Data%20Point%20Map.pdf. Ask E-Mon or its representative for the current revision.
What are the minimum BACnet points to integrate the E-Mon D-Mon legacy IDR interval data recorder (BACnet)?
Start with AI 1 Usage Channel 1 (Channel 1 usage, pulses); AI 33 Demand Channel 1 (Channel 1 peak demand); AI 2 Usage Channel 2 (Channel 2 usage, pulses); AI 34 Demand Channel 2 (Channel 2 peak demand).
How do I check these points on the real E-Mon D-Mon legacy IDR interval data recorder (BACnet)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More E-Mon BACnet points lists
- Electric meter (kWh / demand)
E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)
E-Mon D-Mon Class 3200, 3400 and 5000 electric submeters with the BACnet option, and the older (legacy) Class 3000 and 5000 meters, which use the same object map.
Also known as: E-Mon Class 3200, E-Mon Class 3400, E-Mon Class 5000, CL3200, CL3400, CL5000, E32-208100-RBACKIT, E34-480200-R05KIT, E50-480200-R03KIT, Honeywell E-Mon, E-Mon D-Mon, E-Mon Class 3000, E-Mon legacy Class 5000, Legacy CL3000, Legacy CL5000, E-Mon D-Mon legacy meter - Electric meter data recorder (pulse)
E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet)
E-Mon D-Mon IDR8 and IDR16 interval data recorders that collect pulses from up to 8 or 16 E-Mon meters.
Also known as: E-Mon IDR, IDR8, IDR16, EIDR-8-R05RJ, E-Mon interval data recorder
Source: E-Mon D-Mon BACnet, ModBus and LonWorks Point Maps: CL3200, CL3400, CL5000 and IDR · rev. 6/21/2012. Object names, instances and units are reproduced as published; descriptions are our own.