- E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet)
Electric meter data recorder (pulse) · BACnet points list
E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet) BACnet points list
Updated 12 November 2026Unofficial source
The IDR8/IDR16 collects pulse outputs from E-Mon Class 1000/2000 meters plugged into its jacks. Over BACnet it publishes 32 read-only analog inputs: usage (AI 1-16) and demand (AI 17-32) per channel, in pulse counts that the BMS multiplies by the meter pulse value.
This page lists 32 BACnet objects for the E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of E-Mon’s documentation hosted by Kele, not by E-Mon itself, so treat it as unofficial.
- Manufacturer
- E-Mon
- Model
- E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet)
- Equipment
- Electric meter data recorder (pulse)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 32 (0 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Also known as
- E-Mon IDR, IDR8, IDR16, EIDR-8-R05RJ, E-Mon interval data recorder
- Source document
- E-Mon D-Mon BACnet, ModBus and LonWorks Point Maps: CL3200, CL3400, CL5000 and IDR · rev. 6/21/2012 (unofficial copy, hosted by Kele)
Reference only, provided as-is: verify against E-Mon’s current documentation and the live device before use. Not official E-Mon information. Terms of use.
BMS integration notes: E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet)
Discover the recorder and read the usage and demand channels. Multiply each value by the pulse value for the meter size plugged into that jack (set it in the BMS) to get kWh and kW.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Usage Channel 1 | Channel 1 usage, pulses | Read |
| AI 17 | Demand Channel 1 | Channel 1 demand, pulses | Read |
| AI 2 | Usage Channel 2 | Channel 2 usage, pulses | Read |
| AI 18 | Demand Channel 2 | Channel 2 demand, pulses | Read |
Network setup
- Set the pulse multiplier per channel in the BMS from the meter-size table in the point map.
Watch out for
- Values are raw pulse counts, not kWh.
- Usage channels are cleared from the IDR display (jumper J6 closed).
E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Usage Channel 1 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AImin | 2 | Usage Channel 2 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 3 | Usage Channel 3 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 4 | Usage Channel 4 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 5 | Usage Channel 5 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 6 | Usage Channel 6 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 7 | Usage Channel 7 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 8 | Usage Channel 8 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 9 | Usage Channel 9 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 10 | Usage Channel 10 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 11 | Usage Channel 11 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 12 | Usage Channel 12 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 13 | Usage Channel 13 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 14 | Usage Channel 14 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 15 | Usage Channel 15 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 16 | Usage Channel 16 | Usage pulses; multiply by the meter pulse value | pulses | Read | |
| AImin | 17 | Demand Channel 1 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AImin | 18 | Demand Channel 2 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 19 | Demand Channel 3 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 20 | Demand Channel 4 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 21 | Demand Channel 5 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 22 | Demand Channel 6 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 23 | Demand Channel 7 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 24 | Demand Channel 8 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 25 | Demand Channel 9 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 26 | Demand Channel 10 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 27 | Demand Channel 11 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 28 | Demand Channel 12 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 29 | Demand Channel 13 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 30 | Demand Channel 14 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 31 | Demand Channel 15 | Demand pulses; multiply by the meter pulse value | pulses | Read | |
| AI | 32 | Demand Channel 16 | Demand pulses; multiply by the meter pulse value | pulses | Read |
No points match these filters.
Object ID lookup: E-Mon D-Mon IDR8 / IDR16 interval data recorder point IDs by name
AI1Usage Channel 1AI2Usage Channel 2AI3Usage Channel 3AI4Usage Channel 4AI5Usage Channel 5AI6Usage Channel 6AI7Usage Channel 7AI8Usage Channel 8AI9Usage Channel 9AI10Usage Channel 10AI11Usage Channel 11AI12Usage Channel 12AI13Usage Channel 13AI14Usage Channel 14AI15Usage Channel 15AI16Usage Channel 16AI17Demand Channel 1AI18Demand Channel 2AI19Demand Channel 3AI20Demand Channel 4AI21Demand Channel 5AI22Demand Channel 6AI23Demand Channel 7AI24Demand Channel 8AI25Demand Channel 9AI26Demand Channel 10AI27Demand Channel 11AI28Demand Channel 12AI29Demand Channel 13AI30Demand Channel 14AI31Demand Channel 15AI32Demand Channel 16
Integration notes
- Object names are the Description column of the "BACnet Object Descriptors" tables; every object is a read-only analog input (Present Value).
- Units are pulse counts; the printed unit is "Pulse * Pulse Value" (usage) and "Demand * Pulse Value" (demand). The document gives the Watt-hour value per pulse for each meter size (25-3200 A), which differs for meters with serial numbers up to 1203XXXX.
- On an IDR8 only channels 1-8 are used.
- PICS: MS/TP master at 9.6k-76.8k bps or BACnet IP.
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet)
How many BACnet points does the E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet) have?
This list has 32 BACnet objects: 32 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet) BACnet documentation?
E-Mon does not publish it on its own website. This list comes from E-Mon D-Mon BACnet, ModBus and LonWorks Point Maps: CL3200, CL3400, CL5000 and IDR, revision 6/21/2012, a copy hosted by Kele at https://assets.kele.com/Catalog/17%20Power%20Monitoring/PDFs/Class%205000%20Protocol%20Data%20Point%20Map.pdf. Ask E-Mon or its representative for the current revision.
What are the minimum BACnet points to integrate the E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet)?
Start with AI 1 Usage Channel 1 (Channel 1 usage, pulses); AI 17 Demand Channel 1 (Channel 1 demand, pulses); AI 2 Usage Channel 2 (Channel 2 usage, pulses); AI 18 Demand Channel 2 (Channel 2 demand, pulses).
How do I check these points on the real E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More E-Mon BACnet points lists
- Electric meter (kWh / demand)
E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)
E-Mon D-Mon Class 3200, 3400 and 5000 electric submeters with the BACnet option, and the older (legacy) Class 3000 and 5000 meters, which use the same object map.
Also known as: E-Mon Class 3200, E-Mon Class 3400, E-Mon Class 5000, CL3200, CL3400, CL5000, E32-208100-RBACKIT, E34-480200-R05KIT, E50-480200-R03KIT, Honeywell E-Mon, E-Mon D-Mon, E-Mon Class 3000, E-Mon legacy Class 5000, Legacy CL3000, Legacy CL5000, E-Mon D-Mon legacy meter - Electric meter data recorder (pulse)
E-Mon D-Mon legacy IDR interval data recorder (BACnet)
Older (legacy) E-Mon D-Mon IDR interval data recorders with a BACnet module.
Also known as: E-Mon legacy IDR, Legacy IDR, E-Mon interval data recorder (legacy)
Source: E-Mon D-Mon BACnet, ModBus and LonWorks Point Maps: CL3200, CL3400, CL5000 and IDR · rev. 6/21/2012. Object names, instances and units are reproduced as published; descriptions are our own.