  4. E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)

Electric meter (kWh / demand) · BACnet points list

E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) BACnet points list

Updated 12 November 2026Unofficial source

Short answer

E-Mon Class 3200, 3400 and 5000 meters are kWh/demand submeters; with the BACnet option they act as B-SS devices on MS/TP or (3400/5000) BACnet IP. Each meter publishes 43 read-only analog inputs: energy delivered/received, real/reactive/apparent power, power factor, peak demand, per-phase current, voltage and phase angle, and two external pulse inputs.

This page lists 43 BACnet objects for the E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of E-Mon’s documentation hosted by Kele, not by E-Mon itself, so treat it as unofficial.

Manufacturer
E-Mon
Model
E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)
Equipment
Electric meter (kWh / demand)
Equipment type
Thermostats, sensors & meters
BACnet objects
43 (0 writable)
Transport
BACnet MS/TP, BACnet IP
Firmware
Not stated
Also known as
E-Mon Class 3200, E-Mon Class 3400, E-Mon Class 5000, CL3200, CL3400, CL5000, E32-208100-RBACKIT, E34-480200-R05KIT, E50-480200-R03KIT, Honeywell E-Mon, E-Mon D-Mon, E-Mon Class 3000, E-Mon legacy Class 5000, Legacy CL3000, Legacy CL5000, E-Mon D-Mon legacy meter
Source document
E-Mon D-Mon BACnet, ModBus and LonWorks Point Maps: CL3200, CL3400, CL5000 and IDR · rev. 6/21/2012 (unofficial copy, hosted by Kele)
Download CSV 43 rows Download EDE B.I.G.-EU JSON Source PDF (unofficial copy) ↗ Compare with your scan Download Easy BACnet Mobile App Google Play

Reference only, provided as-is: verify against E-Mon’s current documentation and the live device before use. Not official E-Mon information. Terms of use.

BMS integration notes: E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)

Integration in brief

Set the meter address and baud rate (MS/TP) or IP settings, discover the device and read the AIs. Energy totals AI 1-4 are the main points; AI 5-14 give the three-phase summary and AI 15-38 the per-phase detail.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
AI 1Energy deliveredEnergy delivered, kWhRead
AI 2Energy receivedEnergy received, kWhRead
AI 5Real powerReal power, kWRead
AI 9Peak demandPeak demand, kWRead
AI 8Power factorPower factorRead
AI 10Current averageAverage current, ARead
AI 11Voltage line-neutralVoltage line-neutral, VRead

Network setup

Watch out for

E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

43 of 43 shown
Type
Analog
Show
E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) BACnet Points List
DescriptionStates
AImin1Energy deliveredkWhRead
AImin2Energy receivedkWhRead
AI3Reactive energy deliveredkVARhRead
AI4Reactive energy receivedkVARhRead
AImin5Real powerkWRead
AI6Reactive powerkVARRead
AI7Apparent powerkVARead
AImin8Power factor% PFRead
AImin9Peak demandkWRead
AImin10Current averageARead
AImin11Voltage line-neutralVRead
AI12Voltage line-lineVRead
AI13FrequencyHzRead
AI14Phase angle°Read
AI15Real power phase AkWRead
AI16Real power phase BkWRead
AI17Real power phase CkWRead
AI18Reactive power phase AkVARRead
AI19Reactive power phase BkVARRead
AI20Reactive power phase CkVARRead
AI21Apparent power phase AkVARead
AI22Apparent power phase BkVARead
AI23Apparent power phase CkVARead
AI24Power factor phase A% PFRead
AI25Power factor phase B% PFRead
AI26Power factor phase C% PFRead
AI27Current phase AARead
AI28Current phase BARead
AI29Current phase CARead
AI30Voltage line-neutral phase A-NVRead
AI31Voltage line-neutral phase B-NVRead
AI32Voltage line-neutral phase C-NVRead
AI33Voltage line-line phase A-BVRead
AI34Voltage line-line phase B-CVRead
AI35Voltage line-line phase C-AVRead
AI36Phase angle phase A°Read
AI37Phase angle phase B°Read
AI38Phase angle phase C°Read
AI39Reserve AReservedRead
AI40Reserve BReservedRead
AI41Reserve CReservedRead
AI42External Input 1Pulse count from external input (CL5000 standard, CL3400 option)pulsesRead
AI43External Input 2Pulse count from external input (CL5000 standard, CL3400 option)pulsesRead
Object ID lookup: E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 point IDs by name

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)

How many BACnet points does the E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) have?

This list has 43 BACnet objects: 43 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.

Which E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) BACnet points are writable?

None of the listed objects are marked writable in the source documentation.

Where is the official E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) BACnet documentation?

E-Mon does not publish it on its own website. This list comes from E-Mon D-Mon BACnet, ModBus and LonWorks Point Maps: CL3200, CL3400, CL5000 and IDR, revision 6/21/2012, a copy hosted by Kele at https://assets.kele.com/Catalog/17%20Power%20Monitoring/PDFs/Class%205000%20Protocol%20Data%20Point%20Map.pdf. Ask E-Mon or its representative for the current revision.

What are the minimum BACnet points to integrate the E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)?

Start with AI 1 Energy delivered (Energy delivered, kWh); AI 2 Energy received (Energy received, kWh); AI 5 Real power (Real power, kW); AI 9 Peak demand (Peak demand, kW); AI 8 Power factor (Power factor); AI 10 Current average (Average current, A); AI 11 Voltage line-neutral (Voltage line-neutral, V).

How do I check these points on the real E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More E-Mon BACnet points lists

Source: E-Mon D-Mon BACnet, ModBus and LonWorks Point Maps: CL3200, CL3400, CL5000 and IDR · rev. 6/21/2012. Object names, instances and units are reproduced as published; descriptions are our own.