- E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)
Electric meter (kWh / demand) · BACnet points list
E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) BACnet points list
Updated 12 November 2026Unofficial source
E-Mon Class 3200, 3400 and 5000 meters are kWh/demand submeters; with the BACnet option they act as B-SS devices on MS/TP or (3400/5000) BACnet IP. Each meter publishes 43 read-only analog inputs: energy delivered/received, real/reactive/apparent power, power factor, peak demand, per-phase current, voltage and phase angle, and two external pulse inputs.
This page lists 43 BACnet objects for the E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) — 0 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from a copy of E-Mon’s documentation hosted by Kele, not by E-Mon itself, so treat it as unofficial.
- Manufacturer
- E-Mon
- Model
- E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)
- Equipment
- Electric meter (kWh / demand)
- Equipment type
- Thermostats, sensors & meters
- BACnet objects
- 43 (0 writable)
- Transport
- BACnet MS/TP, BACnet IP
- Firmware
- Not stated
- Also known as
- E-Mon Class 3200, E-Mon Class 3400, E-Mon Class 5000, CL3200, CL3400, CL5000, E32-208100-RBACKIT, E34-480200-R05KIT, E50-480200-R03KIT, Honeywell E-Mon, E-Mon D-Mon, E-Mon Class 3000, E-Mon legacy Class 5000, Legacy CL3000, Legacy CL5000, E-Mon D-Mon legacy meter
- Source document
- E-Mon D-Mon BACnet, ModBus and LonWorks Point Maps: CL3200, CL3400, CL5000 and IDR · rev. 6/21/2012 (unofficial copy, hosted by Kele)
Reference only, provided as-is: verify against E-Mon’s current documentation and the live device before use. Not official E-Mon information. Terms of use.
BMS integration notes: E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)
Set the meter address and baud rate (MS/TP) or IP settings, discover the device and read the AIs. Energy totals AI 1-4 are the main points; AI 5-14 give the three-phase summary and AI 15-38 the per-phase detail.
Minimum points to map
The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.
| Object | Name | Why | Access |
|---|---|---|---|
| AI 1 | Energy delivered | Energy delivered, kWh | Read |
| AI 2 | Energy received | Energy received, kWh | Read |
| AI 5 | Real power | Real power, kW | Read |
| AI 9 | Peak demand | Peak demand, kW | Read |
| AI 8 | Power factor | Power factor | Read |
| AI 10 | Current average | Average current, A | Read |
| AI 11 | Voltage line-neutral | Voltage line-neutral, V | Read |
Network setup
- MS/TP master at 9.6k, 19.2k, 38.4k or 76.8k bps; BACnet IP on the Class 3400 and 5000 only.
- B-SS device: read-only, no segmentation, no device address binding.
Watch out for
- Totals are reset at the meter display (jumper J6 closed), which also resets the external inputs.
- AI 39-41 are reserved.
E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) BACnet objects
Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.
| Description | States | |||||
|---|---|---|---|---|---|---|
| AImin | 1 | Energy delivered | kWh | Read | ||
| AImin | 2 | Energy received | kWh | Read | ||
| AI | 3 | Reactive energy delivered | kVARh | Read | ||
| AI | 4 | Reactive energy received | kVARh | Read | ||
| AImin | 5 | Real power | kW | Read | ||
| AI | 6 | Reactive power | kVAR | Read | ||
| AI | 7 | Apparent power | kVA | Read | ||
| AImin | 8 | Power factor | % PF | Read | ||
| AImin | 9 | Peak demand | kW | Read | ||
| AImin | 10 | Current average | A | Read | ||
| AImin | 11 | Voltage line-neutral | V | Read | ||
| AI | 12 | Voltage line-line | V | Read | ||
| AI | 13 | Frequency | Hz | Read | ||
| AI | 14 | Phase angle | ° | Read | ||
| AI | 15 | Real power phase A | kW | Read | ||
| AI | 16 | Real power phase B | kW | Read | ||
| AI | 17 | Real power phase C | kW | Read | ||
| AI | 18 | Reactive power phase A | kVAR | Read | ||
| AI | 19 | Reactive power phase B | kVAR | Read | ||
| AI | 20 | Reactive power phase C | kVAR | Read | ||
| AI | 21 | Apparent power phase A | kVA | Read | ||
| AI | 22 | Apparent power phase B | kVA | Read | ||
| AI | 23 | Apparent power phase C | kVA | Read | ||
| AI | 24 | Power factor phase A | % PF | Read | ||
| AI | 25 | Power factor phase B | % PF | Read | ||
| AI | 26 | Power factor phase C | % PF | Read | ||
| AI | 27 | Current phase A | A | Read | ||
| AI | 28 | Current phase B | A | Read | ||
| AI | 29 | Current phase C | A | Read | ||
| AI | 30 | Voltage line-neutral phase A-N | V | Read | ||
| AI | 31 | Voltage line-neutral phase B-N | V | Read | ||
| AI | 32 | Voltage line-neutral phase C-N | V | Read | ||
| AI | 33 | Voltage line-line phase A-B | V | Read | ||
| AI | 34 | Voltage line-line phase B-C | V | Read | ||
| AI | 35 | Voltage line-line phase C-A | V | Read | ||
| AI | 36 | Phase angle phase A | ° | Read | ||
| AI | 37 | Phase angle phase B | ° | Read | ||
| AI | 38 | Phase angle phase C | ° | Read | ||
| AI | 39 | Reserve A | Reserved | Read | ||
| AI | 40 | Reserve B | Reserved | Read | ||
| AI | 41 | Reserve C | Reserved | Read | ||
| AI | 42 | External Input 1 | Pulse count from external input (CL5000 standard, CL3400 option) | pulses | Read | |
| AI | 43 | External Input 2 | Pulse count from external input (CL5000 standard, CL3400 option) | pulses | Read |
No points match these filters.
Object ID lookup: E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 point IDs by name
AI1Energy deliveredAI2Energy receivedAI3Reactive energy deliveredAI4Reactive energy receivedAI5Real powerAI6Reactive powerAI7Apparent powerAI8Power factorAI9Peak demandAI10Current averageAI11Voltage line-neutralAI12Voltage line-lineAI13FrequencyAI14Phase angleAI15Real power phase AAI16Real power phase BAI17Real power phase CAI18Reactive power phase AAI19Reactive power phase BAI20Reactive power phase CAI21Apparent power phase AAI22Apparent power phase BAI23Apparent power phase CAI24Power factor phase AAI25Power factor phase BAI26Power factor phase CAI27Current phase AAI28Current phase BAI29Current phase CAI30Voltage line-neutral phase A-NAI31Voltage line-neutral phase B-NAI32Voltage line-neutral phase C-NAI33Voltage line-line phase A-BAI34Voltage line-line phase B-CAI35Voltage line-line phase C-AAI36Phase angle phase AAI37Phase angle phase BAI38Phase angle phase CAI39Reserve AAI40Reserve BAI41Reserve CAI42External Input 1AI43External Input 2
Integration notes
- Object names are the Description column of the "BACnet Object Descriptors" tables; every object is a read-only analog input (Present Value).
- The same point-map document also gives Modbus and LonWorks maps; only the BACnet table for this meter family is listed here.
- PICS: MS/TP master at 9.6k, 19.2k, 38.4k or 76.8k bps, or BACnet IP; the Class 3200 meter does not support BACnet IP.
- AI 1-41 apply to all three classes; AI 42-43 (external inputs) are standard on the Class 5000 and part of the expanded feature package on the Class 3400, and are not available on the Class 3200.
- kWh/kVARh are cleared from the meter display (reset kW/kWh, jumper J6 closed), not over BACnet.
- Legacy Class 3000/5000 meters use the same 43 AIs except AI 9, which is "Current total" (A) instead of Peak demand. On legacy meters the totals can only be cleared over Modbus RTU (jumper J2 closed, BACnet IP module removed).
Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. This list is provided as-is for reference only and may contain mistakes — confirming it before you write, map or commission anything is up to you (terms). Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.
Questions about the E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)
How many BACnet points does the E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) have?
This list has 43 BACnet objects: 43 analog inputs. The exact set on a given unit depends on its firmware, installed options and configuration.
Which E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) BACnet points are writable?
None of the listed objects are marked writable in the source documentation.
Where is the official E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet) BACnet documentation?
E-Mon does not publish it on its own website. This list comes from E-Mon D-Mon BACnet, ModBus and LonWorks Point Maps: CL3200, CL3400, CL5000 and IDR, revision 6/21/2012, a copy hosted by Kele at https://assets.kele.com/Catalog/17%20Power%20Monitoring/PDFs/Class%205000%20Protocol%20Data%20Point%20Map.pdf. Ask E-Mon or its representative for the current revision.
What are the minimum BACnet points to integrate the E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)?
Start with AI 1 Energy delivered (Energy delivered, kWh); AI 2 Energy received (Energy received, kWh); AI 5 Real power (Real power, kW); AI 9 Peak demand (Peak demand, kW); AI 8 Power factor (Power factor); AI 10 Current average (Average current, A); AI 11 Voltage line-neutral (Voltage line-neutral, V).
How do I check these points on the real E-Mon D-Mon Class 3200 / 3400 / 5000 meters, incl. legacy Class 3000 / 5000 (BACnet)?
Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.
More E-Mon BACnet points lists
- Electric meter data recorder (pulse)
E-Mon D-Mon IDR8 / IDR16 interval data recorder (BACnet)
E-Mon D-Mon IDR8 and IDR16 interval data recorders that collect pulses from up to 8 or 16 E-Mon meters.
Also known as: E-Mon IDR, IDR8, IDR16, EIDR-8-R05RJ, E-Mon interval data recorder - Electric meter data recorder (pulse)
E-Mon D-Mon legacy IDR interval data recorder (BACnet)
Older (legacy) E-Mon D-Mon IDR interval data recorders with a BACnet module.
Also known as: E-Mon legacy IDR, Legacy IDR, E-Mon interval data recorder (legacy)
Source: E-Mon D-Mon BACnet, ModBus and LonWorks Point Maps: CL3200, CL3400, CL5000 and IDR · rev. 6/21/2012. Object names, instances and units are reproduced as published; descriptions are our own.