Grow room dehumidifier (air handler) controller · BACnet points list

Desert Aire IAQ Grow Room Program (GR 3.0.4 and later) BACnet points list

Updated 28 October 2026

Short answer

The grow-room version of Desert Aire's IAQ program uses a lights-on/lights-off signal to switch between day and night temperature and RH setpoints. Over BACnet the BMS can set the lights state, write the four day/night setpoints, tune deadbands, limits and PID terms, and send its own zone temperature and RH. Readbacks cover up to four compressor circuits, EXV positions, water temperatures and a status and alarm code.

This page lists 89 BACnet objects for the Desert Aire IAQ Grow Room Program (GR 3.0.4 and later) — 30 of them writable — with each object’s type, instance number, name, engineering units and access. It is re-typed from Desert Aire’s own free documentation, linked below.

Manufacturer
Desert Aire
Model
IAQ Grow Room Program (GR 3.0.4 and later)
Equipment
Grow room dehumidifier (air handler) controller
Equipment type
Dehumidifiers
BACnet objects
89 (30 writable)
Transport
—
Firmware
GR 3.0.4 and later
Also known as
Desert Aire GR, IAQ-GR, GR 3.0.4, Grow Room program, GrowAire
Source document
BACnet Points List - Unit Type IAQ Grow Room Program Versions GR 3.0.4 & Above · rev. 2016-08-26
Download CSV 89 rows Download EDE B.I.G.-EU JSON Manufacturer PDF ↗ Download Easy BACnet Mobile App Google Play

BMS integration notes: Desert Aire IAQ Grow Room Program (GR 3.0.4 and later)

Integration in brief

Write the lights state with BV 1 so the unit uses its lights-on or lights-off setpoints, and set those setpoints in AV 20-23. Monitor Unit Status (AV 1001), zone temperature and RH, and alarms through BV 3 (inverted) and the alarm code (AV 1006). Use BV 14 to reset alarms.

Minimum points to map

The short list most integrators start with — enough to run the unit from a BMS. Map more as the job needs.

ObjectNameWhyAccess
BV 1Network Lights On InputLights-on input (1 = on); picks day/night setpointsWrite
AV 20Lights On Temp. Set PointLights-on temperature setpoint, 45-90 °FWrite
AV 21Lights Off Temp. Set PointLights-off temperature setpoint, 45-90 °FWrite
AV 22Lights On RH Set PointLights-on RH setpoint, %Write
AV 23Lights Off RH Set PointLights-off RH setpoint, %Write
BV 14Remote ResetWrite 1 to resetWrite
AV 1001Unit StatusOperating state code (0-12)Read
AV 9Zone Air TemperatureMeasured zone temperature, °FRead
AV 10Zone Air Relative HumidityMeasured zone RH, %Read
BV 3Alarm ActiveUnit alarm; 0 = alarm, 1 = normalRead

Enable & remote start

No network on/off object is listed. BV 1 Network Lights On Input tells the unit whether the grow lights are on (1) or off (0); BV 2 confirms the state and BV 15 shows the photo cell input.

Sensors & values from the BMS

The BMS can write zone temperature (AV 58) and zone RH (AV 59). The list does not say how the unit chooses between these and its own sensors.

Network setup

Watch out for

Desert Aire IAQ Grow Room Program (GR 3.0.4 and later) BACnet objects

Type: AI, AO, AV, BI, BO, BV, MI/MO/MV (multi-state) · Access: Read read-only, Write writable, Command writable with a priority array.

89 of 89 shown
Type
AnalogBinary
Access
Show
Desert Aire IAQ Grow Room Program (GR 3.0.4 and later) BACnet Points List
DescriptionStates
AV1Suction PressureRange 0 to 250 psig (sent in tenths)psigRead
AV2Discharge PressureRange 0 to 650 psig (sent in tenths)psigRead
AV3Intake Air Relative HumidityRange 0 to 100 % (sent in tenths)%Read
AV4Intake Air TemperatureRange -42 to 137 °F (sent in tenths)°FRead
AV5Intake Air Dew Point°FRead
AV6Supply Air TemperatureRange -58 to 212 °F (sent in tenths)°FRead
AV7Supply Air Relative HumidityRange 0 to 100 % (sent in tenths)%Read
AV8Supply Air Dew Point°FRead
AVmin9Zone Air TemperatureRange -58 to 212 °F (sent in tenths)°FRead
AVmin10Zone Air Relative HumidityRange 0 to 100 % (sent in tenths)%Read
AV11Zone Air Dew Point°FRead
AV12Suction Press Circuit BRange 0 to 250 psig (sent in tenths)psigRead
AV13Discharge Press Circuit BRange 0 to 650 psig (sent in tenths)psigRead
AV14Auxiliary Heating Comm.Range 0 to 100 % (sent in tenths)%Read
AV15Outside Air Damper Comm.Range 0 to 100 % (sent in tenths)%Read
AV16Recirc. Damper CommandRange 0 to 100 % (sent in tenths)%Read
AV17Off Evap Temperature ARange -58 to 212 °F (sent in tenths)°FRead
AV18Off Evap Temperature BRange -58 to 212 °F (sent in tenths)°FRead
AV19Outside Air TemperatureRange -58 to 212 °F (sent in tenths)°FRead
AVmin20Lights On Temp. Set PointSettable 45.0 to 90.0 °F (sent in tenths)°FWrite
AVmin21Lights Off Temp. Set PointSettable 45.0 to 90.0 °F (sent in tenths)°FWrite
AVmin22Lights On RH Set PointSettable 0 to 100 % (sent in tenths)%Write
AVmin23Lights Off RH Set PointSettable 0 to 100 % (sent in tenths)%Write
AV24Cooling Dead BandSettable 0.0 to 99.9 °F (sent in tenths)°FWrite
AV25Heating Dead BandSettable 0.0 to 99.9 °F (sent in tenths)°FWrite
AV26Cool Stage Dead BandSettable 0.0 to 99.9 °F (sent in tenths)°FWrite
AV27Heat/Cool DifferentialSettable 0.0 to 9.9 °F (sent in tenths)°FWrite
AV28Dew Point Dead BandSettable 0.0 to 100.0 % (sent in tenths)%Write
AV29Dew Point DifferentialSettable 0.0 to 100.0 % (sent in tenths)%Write
AV30Calculated Temp. Set PointRange -58 to 212 °F (sent in tenths)°FRead
AV31Calculated Dew Point Set PointRange -58 to 212 °F (sent in tenths)°FRead
AV32Zone Reset Proportional BandSettable 0.0 to 999.9 °F (sent in tenths)°FWrite
AV33Hot Gas Proportional BandSettable 0.0 to 999.9 °F (sent in tenths)°FWrite
AV34Circuit A Super HeatRange -58 to 212 °F (sent in tenths)°FRead
AV35Circuit B Super HeatRange -58 to 212 °F (sent in tenths)°FRead
AV36Circuit A Suction Temp.Range -58 to 212 °F (sent in tenths)°FRead
AV37Circuit B Suction Temp.Range -58 to 212 °F (sent in tenths)°FRead
AV38Circuit A Liquid PressureRange 0.0 to 650.0 psig (sent in tenths)psigRead
AV39Circuit B Liquid PressureRange 0.0 to 650.0 psig (sent in tenths)psigRead
AV40Circuit A Liquid Temp.Range -58 to 212 °F (sent in tenths)°FRead
AV41Circuit B Liquid Temp.Range -58 to 212 °F (sent in tenths)°FRead
AV42Water Inlet TemperatureRange -58 to 212 °F (sent in tenths)°FRead
AV43Water Outlet TemperatureRange -58 to 212 °F (sent in tenths)°FRead
AV44EC Speed CommandRange 0.0 to 100.0 % (sent in tenths)%Read
AV45EXV 1-1 PositionRange 0.0 to 100.0 % (sent in tenths)%Read
AV46EXV 1-2 PositionRange 0.0 to 100.0 % (sent in tenths)%Read
AV47EXV 2-1 PositionRange 0.0 to 100.0 % (sent in tenths)%Read
AV48EXV 2-2 PositionRange 0.0 to 100.0 % (sent in tenths)%Read
AV49EXV 3-1 PositionRange 0.0 to 100.0 % (sent in tenths)%Read
AV50EXV 3-2 PositionRange 0.0 to 100.0 % (sent in tenths)%Read
AV51EXV 4-1 PositionRange 0.0 to 100.0 % (sent in tenths)%Read
AV52EXV 4-2 PositionRange 0.0 to 100.0 % (sent in tenths)%Read
AV53Temperature High LimitSettable 45.0 to 90.0 °F (sent in tenths)°FWrite
AV54Temperature Low LimitSettable 45.0 to 90.0 °F (sent in tenths)°FWrite
AV55Zone Dew Point Proportional BandSettable 0.0 to 999.9 °F (sent in tenths)°FWrite
AV56Dew Point High Limit FactorSettable 0.0 to 9.9 °F (sent in tenths)°FWrite
AV57Dew Point Low LimitSettable 0.0 to 99.9 °F (sent in tenths)°FWrite
AV58Network Zone TemperatureBMS zone temperature input°FWrite
AV59Network Zone RHBMS zone RH input%Write
AVmin1001Unit StatusCurrent operating state code (listed as INT)Read0=Unit Satisfied / Unit Off, 1=Heating Required, 2=Cooling Required, 3=Dehumidification Required, 4=Dehum and Heating Required, 5=Dehum and Cooling Required, 6=Low Suction Pressure Condition, 7=EXV Initialization, 8=Damper Opening, 9=High Discharge Pressure Limiting, 10=Pump Down Required, 11=Compressor Switched Off, 12=Variable Speed Comp. Limiting
AV1002Zone Reset Integral TermListed as INTWrite
AV1003Zone Reset Derivative TermListed as INTWrite
AV1004Hot Gas Integral TermListed as INTWrite
AV1005Hot Gas Derivative TermListed as INTWrite
AV1006Alarm CodeActive alarm code (listed as INT)Read1=Low Suction Pressure, 2=Motor Overloads, 3=High Discharge Pressure A, 4=High Discharge Pressure B, 5=Multiple Low Pressure A, 6=Multiple Low Pressure B, 7=Temperature Sensor Fault, 8=pAD Network Fault, 9=SAT Out of Range, 10=Air Filter Clogged, 11=Low Voltage Fault, 12=High Condensate Level, 13=Low Water Flow, 14=Smoke Alarm, 15=Low Air Flow, 16=Freeze Stat Alarm, 17=Condenser Overload Alarm, 18=ModBus Comm. Fault, 19=High Refr. Discharge Temperature, 20=High Super Heat, 21=Low Oil Level Alarm, 22=Fixed Speed Comp. Phase Fault
AV1007Supply Blower Pressure DropInteger in thousandths (1452 = 1.452 in. w.c.) (listed as INT)in. w.c.Read
AV1008First Compressor Start Delay0-99 seconds (listed as INT)sRead
AV1009SAT/Zone Reset SelectionControl basis (listed as INT)Write0=SAT, 1=Zone Reset
AV1010Zone Dew Point Integral TermListed as INTWrite
AV1011Zone Dew Point Derivative TermListed as INTWrite
BVmin1Network Lights On InputLights on/off command (day/night setpoints)Write0=Lights Off, 1=Lights On
BV2Lights On StatusLights on/off stateRead0=Lights Off, 1=Lights On
BVmin3Alarm ActiveUnit alarm state (inverted)Read0=Alarm, 1=Normal
BV4Air FlowRead0=No Flow, 1=Flow
BV5Supply FanRead0=Off, 1=On
BV6Compressor #1Read0=Off, 1=On
BV7Compressor #2Read0=Off, 1=On
BV8Compressor #3Read0=Off, 1=On
BV9Compressor #4Read0=Off, 1=On
BV10Condenser Fan #1Read0=Off, 1=On
BV11Condenser Fan #2Read0=Off, 1=On
BV12Condenser Fan #3Read0=Off, 1=On
BV13Condenser Fan #4Read0=Off, 1=On
BVmin14Remote ResetWrite 1 to reset; clears itself after a scanWrite
BV15Photo CellPhoto cell input stateRead
BV16ROC ActiveROC active commandWrite0=ROC Inactive, 1=ROC Active
BV17Alarm PointInverted alarm conditionRead
BV19HPC OnHPC on command; source comment unclearWrite
BV28Digital Input 7Digital input 7 state; listed as instance 28Read

Integration notes

Check it against the live device. A points list tells you what the controller can expose; the unit in front of you may differ by firmware or installed options. Easy BACnet scans a network for BACnet IP devices from an Android phone, reads every object on the IAQ Grow Room Program (GR 3.0.4 and later) and exports what it actually has to Excel — free. New to BACnet? Start with what a BACnet points list is and what the object types mean.

Questions about the Desert Aire IAQ Grow Room Program (GR 3.0.4 and later)

How many BACnet points does the Desert Aire IAQ Grow Room Program (GR 3.0.4 and later) have?

This list has 89 BACnet objects: 70 analog values, 19 binary values. The exact set on a given unit depends on its firmware, installed options and configuration.

Which Desert Aire IAQ Grow Room Program (GR 3.0.4 and later) BACnet points are writable?

30 of the 89 objects accept a write. Points marked Command have a priority array: a write holds until it is released, so release it back to automatic when you are done.

Where is the official Desert Aire IAQ Grow Room Program (GR 3.0.4 and later) BACnet documentation?

The source is BACnet Points List - Unit Type IAQ Grow Room Program Versions GR 3.0.4 & Above, revision 2016-08-26, published free by Desert Aire at https://www.desert-aire.com/wp-content/uploads/2025/04/IAQ-GR-BACnet-Points-Ver-3_0_4.pdf.

What are the minimum BACnet points to integrate the Desert Aire IAQ Grow Room Program (GR 3.0.4 and later)?

Start with BV 1 Network Lights On Input (Lights-on input (1 = on); picks day/night setpoints); AV 20 Lights On Temp. Set Point (Lights-on temperature setpoint, 45-90 °F); AV 21 Lights Off Temp. Set Point (Lights-off temperature setpoint, 45-90 °F); AV 22 Lights On RH Set Point (Lights-on RH setpoint, %); AV 23 Lights Off RH Set Point (Lights-off RH setpoint, %); BV 14 Remote Reset (Write 1 to reset); AV 1001 Unit Status (Operating state code (0-12)); AV 9 Zone Air Temperature (Measured zone temperature, °F); AV 10 Zone Air Relative Humidity (Measured zone RH, %); BV 3 Alarm Active (Unit alarm; 0 = alarm, 1 = normal).

How do I enable BMS control of the Desert Aire IAQ Grow Room Program (GR 3.0.4 and later)?

No network on/off object is listed. BV 1 Network Lights On Input tells the unit whether the grow lights are on (1) or off (0); BV 2 confirms the state and BV 15 shows the photo cell input.

Can the BMS supply sensor values to the Desert Aire IAQ Grow Room Program (GR 3.0.4 and later)?

The BMS can write zone temperature (AV 58) and zone RH (AV 59). The list does not say how the unit chooses between these and its own sensors.

How do I check these points on the real IAQ Grow Room Program (GR 3.0.4 and later)?

Scan the network with a BACnet IP browser such as Easy BACnet, open the device and compare its object list with this table. Anything missing is usually an option that isn't installed or a point that is disabled in the controller's configuration.

More Desert Aire BACnet points lists

Source: BACnet Points List - Unit Type IAQ Grow Room Program Versions GR 3.0.4 & Above · rev. 2016-08-26. Object names, instances and units are reproduced as published; descriptions are our own.